inductive proximity switch dccr 80 k 50 psol-kl · dccr 80 k 50 psol-kl inductive proximity switch...

1
207842 © di-soric | Subject to modifications | 12/12/14 | Page 1 (1) DCCR 80 K 50 PSOL-KL Inductive Proximity Switch di-soric GmbH & Co. KG Steinbeisstraße 6 DE-73660 Urbach Fon + 49 (0) 71 81 / 98 79 - 0 Fax + 49 (0) 71 81 / 98 79 - 179 [email protected] www.di-soric.com TECHNICAL INFORMATION (typ.) +20°C, 24V DC Operating principle Inductive Evaluation digital Size 80 x 80 x 40 mm (Dimensions) Design cuboid design Mounting non-flush Operating distance 50 mm Standardized measuring plate 150 x 150 x 1 mm Service voltage 10 ... 30 V DC Internal power consumption < 10 mA Switching output pnp, 200 mA, NO/NC, exclusive OR Switching hysteresis < 15 % LED indicator yes Voltage drop < 2,4 V Operating frequency 100 Hz Ambient temperature -25 … +70 °C Insulation voltage endurance 500 V Protection class IP 67 Casing material plastics (polycarbonate - PC) Connection Connection compartment for 4 x 1,5 mm² 80 80 65 65 5 PG 13,5 11 BN = brown BK = black WH = white BU = blue BN BK BU 1 4 3 pnp WH 2 S S pnp Safety instructions The Instruments are not to be used for safety applications, in particular applications in which safety of persons depends on proper operation of the instruments. These instruments shall exclusively be used by qualified personnel. Connection clamps Protection against short-circuit and reverse polarity LED indicatior for output state High protection class IP 67

Upload: buihanh

Post on 02-Feb-2019

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Inductive Proximity Switch DCCR 80 K 50 PSOL-KL · DCCR 80 K 50 PSOL-KL Inductive Proximity Switch di-soric GmbH & Co. KG Steinbeisstraße 6 DE-73660 Urbach Fon + 49 (0) 71 81 / 98

207842

© di-soric | Subject to modifications | 12/12/14 | Page 1 (1)

DCCR 80 K 50 PSOL-KL

Inductive Proximity Switch

di-soric GmbH & Co. KG Steinbeisstraße 6 DE-73660 Urbach

Fon + 49 (0) 71 81 / 98 79 - 0 Fax + 49 (0) 71 81 / 98 79 - 179 [email protected] www.di-soric.com

TECHNICAL INFORMATION (typ.) +20°C, 24V DC

Operating principle   Inductive

Evaluation   digital

Size   80 x 80 x 40 mm (Dimensions)

Design   cuboid design

Mounting   non-flush

Operating distance   50 mm

Standardized measuring plate   150 x 150 x 1 mm

Service voltage   10 ... 30 V DC

Internal power consumption   < 10 mA

Switching output   pnp, 200 mA, NO/NC, exclusive OR

Switching hysteresis   < 15 %

LED indicator   yes

Voltage drop   < 2,4 V

Operating frequency   100 Hz

Ambient temperature   -25 … +70 °C

Insulation voltage endurance   500 V

Protection class   IP 67

Casing material   plastics (polycarbonate - PC)

Connection   Connection compartment for 4 x 1,5 mm²

80

80

65

65

5

PG 13,5

11

BN = brown

BK = black

WH = white

BU = blue

BN

BK

BU

1

4

3pnp

WH 2S

S

pnp

Safety instructionsThe Instruments are not to be used for safety applications, in particularapplications in which safety of persons depends on proper operation of theinstruments.These instruments shall exclusively be used by qualified personnel.

Connection clamps

Protection against short-circuit and reverse polarity

LED indicatior for output state

High protection class IP 67