VIESMANN VITODENS 200-WGas condensing boiler

17.0 to 105.0 kWas a multi-boiler system up to 420.0 kW

VITODENS 200-W Type WB2B

Wall mounted gas condensing boiler,with modulating MatriX cylinder burnerfor open or balanced flue operation

5822 432 GB 6/2009

Technical guide

Page 2: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Index

1. Vitodens 200-W 1.1 Product description ....................................................................................................... 41.2 Specification ................................................................................................................. 6

■ Vitodens 200-W, 45 and 60 kW ................................................................................ 7■ Vitodens 200-W, 80 and 105 kW .............................................................................. 11

2. Installation accessories 2.1 Product description ....................................................................................................... 14■ Installation accessories for the Vitodens 200-W, 45 and 60 kW ............................... 14■ Installation accessories for the Vitodens 200-W, 80 and 105 kW ............................. 19■ Installation accessories for multi-boiler systems ....................................................... 20

3. DHW cylinder 3.1 Product description ....................................................................................................... 21

4. Design information 4.1 Positioning, installation ................................................................................................. 21■ Installation conditions for open flue operation (appliance type B) ............................. 21■ Installation conditions for balanced flue operation (appliance type C) ...................... 21■ Operation of the Vitodens in wet areas ..................................................................... 22■ Electrical connection ................................................................................................. 22■ Gas connection ......................................................................................................... 23■ Minimum clearances ................................................................................................. 23■ Pre-installation for installing the Vitodens 200-W directly onto a wall ....................... 24■ Pre-installation, multi-boiler system .......................................................................... 24

4.2 Condensate connection ................................................................................................ 29■ Condensate drain and neutralisation ........................................................................ 29

4.3 Hydraulic connection .................................................................................................... 31■ General ..................................................................................................................... 31■ Expansion vessels .................................................................................................... 31■ Low loss header ........................................................................................................ 31

5. Control units 5.1 Vitotronic 100, type HC1, for constant temperature operation ...................................... 33■ Structure and functions ............................................................................................. 33■ Specification, Vitotronic 100 ...................................................................................... 33

5.2 Vitotronic 200, type HO1, for weather-compensated operation .................................... 33■ Specification, Vitotronic 200 ...................................................................................... 35

5.3 Vitotronic 300-K, type MW2 for multi-boiler systems .................................................... 35■ Cascade control unit for the Vitodens 200-W with a Vitotronic 100 .......................... 35■ Construction and function ......................................................................................... 35■ Specification, Vitotronic 300-K .................................................................................. 37■ Delivered condition Vitotronic 300-K ......................................................................... 38

5.4 Accessories for the Vitotronic ....................................................................................... 38■ Allocation to control unit types .................................................................................. 38■ Vitotrol 100, type UTA ............................................................................................... 39■ Vitotrol 100, type UTD ............................................................................................... 39■ External extension H4 ............................................................................................... 40■ Vitotrol 100, type UTD-RF ......................................................................................... 40■ Notes regarding room temperature hook-up (RS function) for remote control units . 40■ Information regarding the Vitotrol 200 and 300 ......................................................... 41■ Vitotrol 200 ................................................................................................................ 41■ Vitotrol 300 ................................................................................................................ 41■ Room temperature sensor ........................................................................................ 42■ Radio clock receiver .................................................................................................. 42■ Function extension 0 to 10 V .................................................................................... 42■ Vitocom 100, type GSM ............................................................................................ 43■ Extension kit for one heating circuit with mixer with integral mixer motor ................. 43■ Extension kit for one heating circuit with mixer for separate mixer motor ................. 44■ Extension kit for one heating circuit with mixer for the Vitotronic 300-K ................... 44■ Immersion thermostat ............................................................................................... 45■ Contact thermostat .................................................................................................... 45■ Immersion temperature sensor ................................................................................. 46■ LON communication module ..................................................................................... 46■ LON connecting cable for data exchange between control units .............................. 46■ Extension of the connecting cable ............................................................................ 47■ Terminator (2 pce.) ................................................................................................... 47■ KM BUS distributor ................................................................................................... 47■ Internal extension H1 ................................................................................................ 47■ Internal extension H2 ................................................................................................ 47■ External extension H1 ............................................................................................... 48■ External extension H2 ............................................................................................... 48

Index

2 VIESMANN VITODENS 200-W

5822

432

GB

Page 3: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

6. Appendix 6.1 Regulations / Directives ................................................................................................ 49■ Regulations and Directives ....................................................................................... 49

7. Keyword index .............................................................................................................................................. 50

Index (cont.)

VITODENS 200-W VIESMANN 3

5822

432

GB

Page 4: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

1.1 Product descriptionA Inox-Radial heat exchanger made from stainless steel - for high

operational reliability and a long service life. Large output in thesmallest of spaces

B Modulating MatriX cylinder burner for extremely clean combustionand quiet operation

C Variable speed combustion fan for quiet and economical opera-tion

D Gas and water connectionsE Digital boiler control unit

Vitodens 200-W wall mounted condensing boilers up to 105 kW areespecially suitable for installation in apartment buildings and commer-cial or public buildings. For these, the Vitodens 200-W offers an afford-able, space-saving solution – either as a single unit up to 105 kW oras a cascade with up to four boilers and an output up to 420 kW.The Inox-Radial heat exchanger made from stainless steel offers highoutput in the tightest of spaces. This enables particularly efficient oper-ation with standard efficiency up to 98 % (Hs)/109 % (Hi).The Vitotronic 300-K cascade control unit regulates up to four Vitodens200-W as a single heating centre. In this way, the boiler output is auto-matically matched to the heat demand. This means subject to the pre-vailing demand, either one boiler modulates or all four boilers operateconcurrently.For the construction of cascade systems, we offer perfectly matchingsystem design, e.g. control units with up to four appliances, fully insu-lated hydraulic cascades or flue gas headers.

Recommended applicationsHigh output from a compact, user-friendly wall mounted boiler, suitablefor the following applications:■ Systems with few, large-demand consumers, e.g. fan heaters in

supermarkets/markets, workshops and industrial premises, nurser-ies, garages and DHW heating systems

■ Systems with several heating circuits for underfloor and/or staticradiators in multi-occupancy dwellings, central heating plants for ter-raced houses, office buildings and administration premises - partic-ularly suitable for attic heating centres

■ Heating of public buildings, such as sports and multi-purpose halls,schools, kindergartens

■ Suitable for installation in basement boiler rooms, on single floors orin the attic.

Benefits at a glance■ Wall mounted gas condensing boiler as central heating boiler, 17 to

105 kW■ As multi-boiler system with cascade control and up to 4 Vitodens

200-W (up to 420 kW)■ Seasonal efficiency [to DIN]: up to 98 % (Hs)/109 % (Hi)■ Stainless steel Inox-Radial heat exchanger

– Self-cleaning of the smooth stainless steel surfaces through theflue gas and the condensate flowing in the same direction

– Excellent corrosion resistance through high-grade stainless steel1.4571

■ Modulating MatriX cylinder burner – in-house development andmanufacture– Low emissions– Long service life through stainless steel MatriX mesh– Optimised match between the heat exchanger and the burner

■ Intelligent Lambda Pro Control combustion controller– A change in the gas type requires no change of nozzle– Consistently high efficiency, even in case of fluctuating gas com-

position– Consistently low emissions– Low combustion noise through low fan speed

Delivered condition

Wall mounted gas condensing boiler with Inox-Radial heat exchanger,modulating MatriX cylinder burner for natural gas and LPG (45 and60 kW) or natural gas (80 and 105 kW) to DVGW Code of PracticeG260 [Germany], and wall retainer.Fully plumbed and wired. Colour of the epoxy-coated casing: white.Packed separately:Vitotronic 100 for constant temperature modeorVitotronic 200 for weather-compensated operation.

Vitodens 200-W

4 VIESMANN VITODENS 200-W

1

5822

432

GB

Page 5: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Set up for operation with natural gas. A conversion within the gas groupE/LL is not required. The conversion to LPG (up to 60 kW only) is madeat the gas valve (conversion kit not required).

Multi-boiler systemsMulti-boiler systems for open flue operation with 2, 3 or 4 boilers.

Installation on a wall in series

Comprising:■ Hydraulic cascade with low loss header and thermal insulation■ Connection set for every boiler with:

– Interconnecting pipes formed to suit– Circulation pump (3-stage)– Ball valves– Fill & drain valve– Check valve– Gas shut-off valve– Safety valve

■ Thermal insulation■ Sensor well for flow temperature sensor■ Weather-compensated, digital cascade and heating circuit control

unit Vitotronic 300-K■ Cascade communication module for each boiler

Installation with a self-supporting mounting frame in series andas a single block

Comprising:■ Hydraulic cascade with low loss header and thermal insulation■ Connection set for every boiler with:

– Interconnecting pipes formed to suit– Circulation pump (3-stage)– Ball valves– Fill & drain valve– Check valve– Gas shut-off valve– Safety valve

■ Thermal insulation■ Sensor well for flow temperature sensor■ Weather-compensated, digital cascade and heating circuit control

unit Vitotronic 300-K■ Cascade communication module for each boiler■ Mounting frame

– Ceiling mounting

NoteOrder circulation pumps for heating circuits and cylinder heating sep-arately.

Approved qualityVDE designation approval applied for

CE designation according to current EC Directives

Meets the requirements for the "Blue Angel" certificate of environmen-tal excellence to RAL UZ 61.

Vitodens 200-W (cont.)

VITODENS 200-W VIESMANN 5

5822

432

GB

1

Page 6: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

1.2 Specification

Gas boiler, series B and C, category II2N3P II2N3P I2N I2N

Gas condensing boilerRated output range45 and 60 kW: Specification to EN 677. 80 and 105 kW: Specification to EN 15417.

TV/TR = 50/30 °C kW 17.0-45.0 17.0-60.0 30.0-80.0 30.0-105.0TV/TR = 80/60 °C kW 15.4-40.7 15.4-54.4 27.0-72.6 27.0-95.6Rated thermal load kW 16.1-42.2 16.1-56.2 28.1-75.0 28.1-98.5Type WB2B WB2B WB2B WB2BProduct ID CE-0085 BR 0432IP rating IP X4D to EN 60529Gas supply pressure Natural gas mbar 20 20 20 20LPG mbar 50 50 — —Max. permissible gas supply pressure*1 Natural gas mbar 25.0 25.0 25.0 25.0LPG mbar 57.5 57.5 — —Max. power consumption W 30 50 105 150Weight kg 65 65 83 83Heat exchanger capacity l 7.0 7.0 12.8 12.8Max. flow rateLimit for the use of hydraulic separation

l/h 3500 3500 5700 5700

Rated circulation water volume at TV/TR = 80/60 °C l/h 1748 2336 3118 4106Permiss. operating pressure bar 4 4 4 4Dimensions Length mm 380 380 530 530Width mm 480 480 480 480Height mm 850 850 850 850Gas connection R ¾" ¾" 1" 1"Connection valuesin relation to the max. load

with gas Natural gas E m3/h 4.47 5.95 7.94 10.42Natural gas LL m3/h 5.19 6.91 9.23 12.12LPG kg/h 3.30 4.39 — —Flue gas parameters*2 Flue gas value group to G 635/G 636 G52/G51 G52/G51 G52/G51 G52/G51

Temperature (at 30 °C return temperature) – at rated output °C 35 40 35 40– at partial load °C 33 35 33 35Temperature (at return temperature 60 °C) °C 65 70 65 70Mass flow rate Natural gas – at rated output kg/h 81.2 110.6 147.5 193.3– at partial load kg/h 31.1 31.1 55.8 55.8LPG – at rated output kg/h 78.2 106.7 — —– at partial load kg/h 26.6 26.6 — —Available draught Pa 250 250 250 250 mbar 2.5 2.5 2.5 2.5Standard efficiency at TV/TR = 40/30 °C % up to 98 (Hs)/109 (Hi)Average condensate volume with natural gas and TV/TR = 50/30 °C l/day 14-19 23-28 25-30 35-40Internal pipe diameter to expansion vessel DN 22 22 28 28safety valve DN 22 22 22 22Condensate connection (hose nozzle) Ø mm 20-24 20-24 20-24 20-24

*1 If the gas supply pressure is higher than the maximum permitted value, install a separate gas pressure governor upstream of the system.*2 Calculation values for sizing the flue gas system to EN 13384.

Flue gas temperatures measured as gross values at 20 °C combustion air temperature.

The flue gas temperature at a return temperature of 30 °C is significant for the sizing of the flue system.The flue gas temperature at a return temperature of 60 °C is used to determine the application range of flue pipes with maximum permissibleoperating temperatures.

Vitodens 200-W (cont.)

6 VIESMANN VITODENS 200-W

1

5822

432

GB

Page 7: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Gas boiler, series B and C, category II2N3P II2N3P I2N I2N

Gas condensing boilerRated output range45 and 60 kW: Specification to EN 677. 80 and 105 kW: Specification to EN 15417.

TV/TR = 50/30 °C kW 17.0-45.0 17.0-60.0 30.0-80.0 30.0-105.0TV/TR = 80/60 °C kW 15.4-40.7 15.4-54.4 27.0-72.6 27.0-95.6Flue gas connection Ø mm 80 80 100 100Ventilation air connection Ø mm 125 125 150 150

Vitodens 200-W, 45 and 60 kW

Multi-boiler systemsFor further details regarding multi-boiler systems, see page 24.

40

100

200

752

1975

1700

850

380

875

1166

176GCB DF

EA

L

M

O

H

RK

N

240305

400

B

902 98

2

S

80

160480

P

A Expansion vessel connection G 1"B Safety valveC Heating flow G 1½"D Cylinder flow G 1½"E Gas connection R ¾"F Cylinder return G 1½"G Heating return G 1½"

H Cable entry area at the backK Connection sets (accessory)

Shown without thermal insulation (standard delivery, connectionsets)

L Without connection setsM With connection setsN Recommended dimension for a single boiler system

Vitodens 200-W (cont.)

VITODENS 200-W VIESMANN 7

5822

432

GB

1

Page 8: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

O Recommended dimension for a multi-boiler systemP Flue gas/ventilation air connection with bend (accessory)

R Condensate drainS Top edge finished floor

NoteRoute all required supply cables on site and lead them into the boilerat the point indicated (see page 22).

Variable speed heating circuit pump in the heating circuit connection set (accessory)The pump speed and consequently the pump rate is relayed to thepump and adjusted by the control unit subject to outside temperatureand switching times for central heating or reduced mode via a dataBUS.Individually match the minimum and maximum speed plus the speedfor reduced mode to the existing heating system using the control unitcodes.Using the diagram, the pump rate can be adjusted to the respectivesystem conditions.Matching the pump rate of the circulation pump to the individual systemconditions reduces the power consumption of the heating system.

Circulation pump VIRS 7 BUSRated voltage V~ 230Rated current A max. 0.55 min. 0.37Condenser µF 3.5Power consumption W max. 126 min. 42 in the delivered condition 93

Variable speed, fully wired, ready to plug in.

Vitodens 200-W (cont.)

8 VIESMANN VITODENS 200-W

1

5822

432

GB

Page 9: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Residual head of the circulation pump

00 200 400 600 800 1000Flow rate in l/h

1200 1400 1600 1800 2000 2200 2400 2600

Res

idua

l hea

d in

mba

r

0kPa

10010

20020

30030

40040

50050

60060

70070

A DB C E F G H

Curve Circulation pump rate Setting code address "E6"A 30 % E6:030B 40 % E6:040C 50 % E6:050D 60 % E6:060E 70 % E6:070F 80 % E6:080G 90 % E6:090H 100 % E6:100

3-speed heating circuit pump in the heating circuit connection set (accessory)

Circulation pump VIRS 25/7-3Rated voltage V~ 230Rated current A max. 0.58 min. 0.30Condenser µF 3.5Power consumption W Stage 1 62 Stage 2 92 Stage 3 132

3-stage, fully wired ready, to plug in.

Vitodens 200-W (cont.)

VITODENS 200-W VIESMANN 9

5822

432

GB

1

Page 10: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Residual head of the circulation pump

A B C

00 200 400 600 800 1000Flow rate in l/h

1200 1400 1600 1800 2000 2200 2400 2600

Res

idua

l hea

d in

mba

r

0kPa

10010

20020

30030

40040

50050

60060

70070

A Stage 1B Stage 2C Stage 3

Pressure drop (on the heating water side)For sizing an on-site circulation pump

0 500 1000 15000

100

200

300

400

500

600

Pres

sure

dro

p in

mba

r

0

10

20

30

40

50

60

kPa

2000 2500 3000 3500Flow rate in l/h

Circulation pump in the connection set for DHW cylinders

Pump type VI RS 25/6-3Voltage V~ 230Power consumption W max. 93

min. 46

Vitodens 200-W (cont.)

10 VIESMANN VITODENS 200-W

1

5822

432

GB

Page 11: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Residual head of the circulation pump

0 0,5 1 1,50

100

200

300

400

500

600

Hea

d in

mba

r

0

10

20

30

40

50

60

kPa

2 2,5 3 3,5Pump rate in m³/h

A B C

A Stage 1B Stage 2C Stage 3

Vitodens 200-W, 80 and 105 kW

Multi-boiler systemsFor further details regarding multi-boiler systems, see page 24.

100

850

530

P

40

160 160

200

752

1975

1700

480

875

1300

E

L

M

O

C G

K

H

N

236

A

B

D F

A Safety valveB Expansion vessel connection G 1"C Boiler flow 7 42 mmD Cylinder flow 7 35 mmE Gas connection R 1"

F Cylinder return 7 35 mmG Boiler return 7 42 mmH Connection sets (accessory)

Shown without thermal insulation (standard delivery, connectionsets)

Vitodens 200-W (cont.)

VITODENS 200-W VIESMANN 11

5822

432

GB

1

Page 12: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

K Cable entry area at the backL Without connection set (accessories)M With connection set (accessories)

N Recommended dimension (single boiler system)O Recommended dimension (multi-boiler system)P Condensate drain

NoteThe heating circuit connection set must be ordered separately.

NoteRoute all required supply cables on site and lead them into the boilerat the point indicated (see page 22).

3-speed heating circuit pump in the heating circuit connection set (accessory)

Circulation pump VI TOP-S25/10-3Rated voltage V~ 230Rated current A max. 2.08 min. 1.75Power consumption W Stage 1 340 Stage 2 395 Stage 3 410

3-stage, fully wired ready, to plug in.

Residual head of the circulation pump

100

Res

idua

l hea

d in

mba

r

00 1000Flow rate in l/h

200

600

800

1000

A

300400500

700

900

11001200

2000 3000 4000 5000

BC

100

20

60

80

100

304050

90

110120

70

kPa

A Stage 1B Stage 2C Stage 3

NoteObserve further details regarding the use of a low loss header (seepage 31).If the residual head of the circulation pump available as an accessoryis insufficient to overcome the following system pressure drop values,install an additional, external circulation pump on site.In such cases, use a low loss header.

Pressure drop (on the heating water side)For sizing a circulation pump on site (when connecting to DHW cylinderfrom connection set)

Vitodens 200-W (cont.)

12 VIESMANN VITODENS 200-W

1

5822

432

GB

Page 13: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

0 1000 2000 30000

100

200

300

400

500

600

Pres

sure

dro

p in

mba

r

0

10

20

30

40

50

60

kPa

4000 5000 6000 7000Flow rate in l/h

Vitodens 200-W (cont.)

VITODENS 200-W VIESMANN 13

5822

432

GB

1

Page 14: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

2.1 Product description

Installation accessories for the Vitodens 200-W, 45 and 60 kW

Heating circuit connection set without circulation pump

Part no. 7245 738Connections G 1½"Comprising:■ Tee with ball valve■ BDF valve■ Safety valve■ Gas shut-off valve with integral thermal safety shut-off valve■ Connection G 1" for expansion vessel

Heating circuit connection set with variable speed circulationpump

Part no. 7247 374Connections G 1½"Comprising:■ Circulation pump, variable speed, Wilo type VIRS-25/7 BUS■ 2 tees with ball valve■ Check valve■ 2 BDF valves■ Safety valve■ Gas shut-off valve with integral thermal safety shut-off valve■ Thermal insulation■ Connection G 1" for expansion vessel

Heating circuit connection set with 3-stage circulation pump

Part no. 7247 341Connections G 1½"

Comprising:■ Circulation pump, 3-stage, Wilo type VIRS-25/7-3■ 2 tees with ball valve■ Check valve■ 2 BDF valves■ Safety valve■ Gas shut-off valve with integral thermal safety shut-off valve■ Thermal insulation■ Connection G 1" for expansion vessel

Connection set for DHW cylinders

Part no. Z006 183Connections G 1½"Comprising:■ Circulation pump, Wilo type VIRS-25/6-3■ 2 ball shut-off valves■ Check valve■ Cylinder temperature sensor

Ball valve

Part no. 7247 3731 pce. G 1¼" with gasket and union nut.

Modular Divicon heating circuit distributor

For part no. in conjunction with the different circulation pumps, see Viessmann pricelist.

Installation accessories

14 VIESMANN VITODENS 200-W

2

5822

432

GB

Page 15: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

89

501

120

120

A

B

C

D

E

HV HR

HV HR

Diagram without thermal insulation, wall mounted

HR Heating returnHV Heating flowA Ball valves with thermometer (as programming unit)

B Connection for overflow valveC Circulation pumpD Connection for bypass valve (only for versions with mixer)E Mixer-3

Heating circuit distributor with or without mixer. Incl. thermal insula-tion.The dimensions of the heating circuit distributor are the same, with orwithout mixer.

Heating circuit connection R ¾ 1Flow rate (max.) m3/h 1.0 1.5

Installation example: Modular-Divicon with triple distributionmanifold

HRHV

120 120697

635

132

120

G1"¼"

HR Heating returnHV Heating flow

Determining the required internal diameter

B

A

C

ΔT= 15K

ΔT= 20K

ΔT= 30K

ΔT= 5K

ΔT= 10K

2,0

20050100

806040

30201086543210,1

0,2

0,5

1,0

1,5

5,0

Pressure drop in mbar

Thro

ughp

ut in

m³/h

10 20 30 405310,1

0,2

0,5

1,0

1,52,0

5,0

Heating circuit outputin kW

A Modular-Divicon with mixer-3The identified operating ranges F and G provide optimum con-trol characteristics with the Modular-Divicon mixer:

B Modular-Divicon with mixer-3 (R ¾")Application range: 0 to 1.0 m 3/h

C Modular-Divicon with mixer-3 (R 1")Application range: 0 to 1.5 m 3/h

Installation accessories (cont.)

VITODENS 200-W VIESMANN 15

5822

432

GB

2

Page 16: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Example:Heating circuit for radiators with an output of Q = 11.6 kWHeating system temperature 75/60 °C (ΔT = 15 K)Flow rate ´

² = µ · c · ΔT c = 1.163Wh

kg · K µ

²

c · ΔT=

kgh

´ =11600 W · kg · K

1.163 Wh · (75-60) K= 665

m³h

0.665

´ (1 kg ≈ 1 dm³)

Select the smallest possible mixer within the application range withvalue ´.

Result of this example: Modular-Divicon with mixer-3 (R ¾")

Bypass valve

Part no. 9557 011To hydraulically balance the heating circuit. Is inserted into the Mod-ular-Divicon.

Overflow valve

Part no. 9557 010Only with manually controlled heating circuit pump. Is inserted into theModular-Divicon.

ManifoldWith thermal insulationThe connection between boiler and manifold must be made on site. ■ For 2 Modular-Divicon

Part no. 7147 860

G 1½"

120 120

130

Rp ¾"120

HV HR

HV HR HV HR457

A C B

A Heating flow drainB Heating return drainC Connection option for expansion vesselHV Heating water flowHR Heating water return

■ For 3 Modular-Divicon

Part no. 7147 861

HV HR

HV HR HV HR HV HR120

697

120 120

130

120

G 1 Rp

A Heating flow drainB Heating return drainC Connection option for expansion vesselHV Heating water flowHR Heating water return

Installation accessories (cont.)

16 VIESMANN VITODENS 200-W

2

5822

432

GB

Page 17: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Pressure drop

AB

Pres

sure

drop

kP

a

00 0.5 1 1.5 2Flow rate in m³/h

0.51

1.52

32.5

A opposite connectionB remote connection

Wall mounting – manifold

Part no. 7147 887

101-123

Modular-Divicon wall mounting

Part no. 7147 886Comprising screws, rawl plugs and spacers.

Low loss header

Part no. 7148 100Flow rate max. 4.5 m3/hWith thermal insulation and integral sensor well (50 mm long)The connection between boiler and low loss header must be made onsite.

HV HR

HV HR

360

450

120

275

G 1

A Sensor wellB Optional blow-downHV Heating water flowHR Heating water return

Pressure drop

Pres

sure

drop

kP

a

00 1 2 3 4 5Flow rate in m³/h

2468

1012

Circulation pump curves and pressure drop on the heating water sideThe residual pump head results from the difference between the selec-ted pump curve and the pressure drop curve of the respective heatingcircuit distributor or further components (pipe assembly, distributoretc.).The pressure drop curve of a Modular-Divicon is shown in the pumpdiagrams.The pressure drop curve is almost equal for all Modular-Diviconunits.Maximum flow rate for Modular-Divicon:■ with R ¾" = 1.0 m3/h■ with R 1" = 1.5 m3/h

Example:Flow rate V = 0,665 m3/h

Selected:Modular-Divicon with mixer R ¾" and circulation pump Wilo 4-3 Ku,pump curve 2, pump rate 0.7 m 3/h

Head of the relevant pumpcurve: 28 kPaPressure drop – Modular-Divi-con: 2 kPaResidual head: 28 kPa –2 kPa = 26 kPa.

NoteFor further components (pipe assembly, distributor, etc.) determine thepressure drop and deduct it from the residual head.

Installation accessories (cont.)

VITODENS 200-W VIESMANN 17

5822

432

GB

2

Page 18: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Manually controlled heating circuit pumps

Wilo 4-3 Ku

A

Min.1

Max. head 3

40

0

10

20

30

0

1

2

3

4

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

505

2

A Modular-Divicon

Wilo 6-3 Ku

A

Min. head 1

Max. head 3

40

0

10

20

30

0

1

2

3

4

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

505

606

2

A Modular-Divicon

Grundfos UPS-40

Min. head

Max. head

A

0

10

20

30

40

0

1

2

3

40404

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

A Modular-Divicon

Grundfos UPS-60

Max. head

AMin. head

606

40

0

10

20

30

0

1

2

3

4

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

505

A Modular-Divicon

Heating circuit pumps regulated by differential pressureAccording to the [German] Energy Savings Order (EnEV), circulationpumps in central heating systems must be sized in accordance withcurrent technical rules. Circulation pumps in central heating systemswith rated output higher than 25 kW should be equipped and designedin such a way that the power consumption will be automaticallymatched to the operational (capacity) requirements in at least 3 stages,if no safety concerns relating to the boiler make demands to the con-trary.

In addition to the EnEV regulations, the use of regulated pumps is alsorecommended for smaller capacities.

Design informationThe use of differential pressure regulated heating circuit pumpsrequires heating circuits with variable flow rate, e.g. single line andtwin-line systems with thermostatic valves, underfloor heating withthermostatic or zone valves.

Installation accessories (cont.)

18 VIESMANN VITODENS 200-W

2

5822

432

GB

Page 19: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Grundfos Alpha 2LGrundfos Alpha 2L is the simpler version of the standard pump Grund-fos Alpha 2.■ Very economical HE DC pump (in accordance with Energy Label A)■ without power consumption indication■ without Autoadapt function (automatic matching to the pipework)■ without night setback function

Grundfos Alpha 2■ Very economical HE DC pump (in accordance with Energy Label A)■ with power consumption indication■ with Autoadapt function (automatic matching to the pipework)■ with night setback function

Grundfos Alpha 2L-40/Alpha 2-40

40

0

10

20

30

0

1

2

3

4

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

505

606

A Modular-DiviconB Stage 1

C Stage 2D Stage 3E Min. proportional pressureF Max. proportional pressureG Min. constant pressureH Max. constant pressure

Grundfos Alpha 2L-60/Alpha 2-60

40

0

10

20

30

0

1

2

3

4

0 0.5 1.0 1.5 2.0 2.5Pump rate in m³/h

Pres

sure

dro

p/he

adm

WS

kPa

505

606

A Modular-DiviconB Stage 1C Stage 2D Stage 3E Min. proportional pressureF Max. proportional pressureG Min. constant pressureH Max. constant pressure

Installation accessories for the Vitodens 200-W, 80 and 105 kW

Heating circuit connection set with 3-stage circulation pump

Part no. 7345 107Comprising:■ Circulation pump, 3-stage, Wilo type VIRS-25/10-3■ 2 ball valves with adaptors Ø 42 mm (locking ring fitting)■ Tee with ball valve■ Check valve■ BDF valve■ Safety valve■ Gas shut-off valve with integral thermal safety shut-off valve■ Thermal insulation■ Connection G 1" for expansion vessel

Low loss headerFor flow rate up to 8 m3/hPart no. Z007 743Comprising:■ Low loss header with integral sensor well (50 mm long)■ Thermal insulation■ Immersion temperature sensor for the low loss header

Installation accessories (cont.)

VITODENS 200-W VIESMANN 19

5822

432

GB

2

Page 20: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

■ Quick-acting air vent valve■ 2 adaptors Ø 42 mm (locking ring fitting)

364

160204

413

963

313

1078

863

Bracket for low loss header■ For floorstanding installation

Part no. 7346 787■ For wall mounting

Part no. 7346 788

Connection set for DHW cylinders

Part no. 7348 934Connections: Ø 35 mm (locking ring fitting)Comprising:■ Connecting lines for flow and return■ Cylinder temperature sensor

Installation accessories for multi-boiler systems

Hydraulic cascadesSee page 24.

Flue gas cascade (positive pressure)Comprising:■ Flue gas non-return device for each boiler■ Flue gas header■ Terminal with condensate drain and siphon■ Boiler coding card

A

C

B

B BB

A Flue gas headerB Flue gas non-return deviceC Terminal with siphon

■ 2-boiler system installed in series– For the Vitodens 200-W, 17 to 45 kW: Part no. Z005 380– For the Vitodens 200-W, 17 to 60 kW: Part no. Z005 381– For the Vitodens 200-W, 30 to 80 kW: Part no. Z006 139– For the Vitodens 200-W, 30 to 105 kW: Part no. Z006 140

■ 3-boiler system installed in series– For the Vitodens 200-W, 17 to 45 kW: Part no. Z005 382– For the Vitodens 200-W, 17 to 60 kW: Part no. Z005 383– For the Vitodens 200-W, 30 to 80 kW: Part no. Z006 141– For the Vitodens 200-W, 30 to 105 kW: Part no. Z006 142

■ 4-boiler system installed in series– For the Vitodens 200-W, 30 to 105 kW: Part no. Z006 143

■ 4-boiler system installed as single block– For the Vitodens 200-W, 17 to 45 kW: Part no. Z005 386– For the Vitodens 200-W, 17 to 60 kW: Part no. Z005 387– For the Vitodens 200-W, 30 to 80 kW: Part no. Z006 145– For the Vitodens 200-W, 30 to 105 kW: Part no. Z006 146

For further technical details regarding the flue gas cascades, see thetechnical guide to Vitodens flue systems.

Installation accessories (cont.)

20 VIESMANN VITODENS 200-W

2

5822

432

GB

Page 21: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

3.1 Product descriptionFor details regarding DHW cylinders, see the technical guide to theVitodens up to 35 kW, or separate datasheets.

Design information

4.1 Positioning, installation

Installation conditions for open flue operation (appliance type B)(Type B23 and B33)

In rooms where air contamination through halogenated hydrocar-bons can occur, such as hairdressing salons, printing shops, chemicalcleaners, laboratories, etc., install the Vitodens only as balanced fluesystem.If in doubt, please contact us.Wall mounted boilers should not be installed in areas subject to verydusty conditions.The installation location must be kept free from frost and must be ade-quately ventilated.Provide a condensate drain and a blow-off line for the safety valve inthe installation room.The maximum ambient temperature of the system should not exceed35 ºC.If these instructions are not observed, any consequential loss directlyrelated to any of these causes is excluded from our warranty.

Vitodens 200-W from 60 kW and multi-boiler systemsInstall boilers from 50 kW in accordance with the Combustion Order(FeuVo) [Germany] [or local regulations] in a separate installationroom. Fit the main isolator outside the installation room.

Combustion air aperturesGas equipment with a total rated output in excess of 50 kW must beprovided with combustion air apertures leading to the outside. Thecross-section should be at least 150 cm2 and should be 2 cm2 largerfor each kW above 50 kW rated output. This cross-section may not besplit over more than 2 apertures (observe FeuVo and TRGI 2008 point5.5.4 [or local regulations]).

Example:Vitodens 200-W, 4 × 60 kW Total rated output 240 kW 150 cm2 + 190 × 2 cm2 = 530 cm2 or 2 × 265 cm2.The combustion air apertures should be at least 530 cm2 or 2 ×265 cm2.

Multi-boiler systems with pressurised flue gas systemsThe Vitodens 200-W multi-boiler systems with common pressurisedflue gas systems are designed for open flue operation (type B).For further details, see the technical guide on flue gas systems for theVitodens.

Installation room (up to 50 kW)

Permissible:■ Boiler installation on the same floor■ Adjacent rooms with interconnected room ventilation (larders, base-

ment, utility rooms, etc.)■ Attic rooms, but only with adequate minimum chimney height to DIN

18160 – 4 m above inlet (negative pressure operation).

Not permissible:■ Stair wells and common hallways; exception: Detached and two-

family homes of low height (top edge of the floor in the top storey <7 m above ground level)

■ Bathrooms and toilets without outside windows with duct ventilation■ Rooms where explosive or flammable materials are stored■ Rooms ventilated mechanically or via individual duct systems to DIN

18117-1.

Observe all local fire regulations.

Connection on the flue gas side(for further details, see the technical guide "Flue gas systems for theVitodens")The connecting piece to the chimney should be as short as possible.Therefore position the Vitodens as closely to the chimney as possi-ble.No special protective measures or clearances towards combustibleobjects, e.g. furniture, cartons or similar, need to be taken/observed.The surface temperatures of the Vitodens and the flue system neverexceeds 85 ºC anywhere.

ExtractorsWhen installing devices with extraction to the outside (cooker hoods,extractors, etc.), ensure that air extraction will not create negativepressure inside the installation room. A return flow of flue gases couldresult, if the ventilation system and the Vitodens were to operate simul-taneously. In such cases, install an interlocking circuit.For this, the internal extension H2 (accessories) can be used. Thisswitches the extractors OFF when the burner is started.

Installation conditions for balanced flue operation (appliance type C)The Vitodens can be installed as appliance type C13x, C33x, C43x, C53x

or C63x to TRGl 2008, for balanced flue operation independent of thesize and ventilation of the installation room.It may, for example, be installed in recreation rooms, in other livingspace, in ancillary rooms without ventilation, in cupboards (open at thetop) and recesses without maintaining minimum clearances to com-bustible parts as well as in attic rooms (pitched attics and ancillaryrooms) where the balanced flue pipe can be directly routed throughthe roof. Since the flue pipe connecting piece for balanced flue oper-ation is surrounded by combustion air (coaxial pipe), no clearancestowards combustible parts need to be maintained (for further details,see the technical guide "Flue gas systems for the Vitodens").

The installation location must be safe from the risk of frost.Provide a condensate drain and a blow-off line for the safety valve inthe installation room.Electrical interlocks for extractors (extractor hoods, etc.) are notrequired with balanced flue operation.

Vitodens 200-W from 60 kWInstall boilers from 50 kW in a separate room in accordance with theCombustion Order (FeuVo) [Germany] [or local regulations]. Fit themain isolator outside the installation room.Appropriate ventilation air and extract air apertures are required inaccordance with TRGI (see the technical guide on flue gas systemsfor the Vitodens).

DHW cylinder

VITODENS 200-W VIESMANN 21

5822

432

GB

3

Page 22: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Installation in a garageTests carried out by the Gaswärme-Institut e.V., Essen, have con-firmed that the Vitodens is suitable for installation in garages.

When installing this boiler in garages, maintain a clearance betweenthe floor and the burner of at least 500 mm. Protect the boiler on sitewith a bracket or deflector against mechanical damage.

Operation of the Vitodens in wet areasThe Vitodens is approved for installation in wet areas (protectionIP X4 D, splash-proof)

When installing the Vitodens in wet areas, observe the safety zonesand minimum wall clearances according to VDE 0100 [or local regu-lations]. The Vitodens 200-W may be installed in safety zone 1.

Electrical connectionEnsure the power supply complies with the requirements of your localpower supply utility and current VDE [or local] regulations.Protect the power cable with a fuse with a max. rating of 16 A.Make the power supply (230 V~, 50 Hz) via a permanent connection.Connect the supply cables and accessories at the terminals inside theboiler.Allow cables/leads in the shaded area to protrude at least 800 mm fromthe wall (see diagram):

40

200

752

B

A

A Reference point Vitodens top edgeB Area for electrical supply cables

Recommended leads/cables

NYM-J 3 × 1.5 mm2 2-core min. 0.75 mm2 4-core 1.5 mm2

or3-core 1.5 mm2 without green/yellow core

NYM-O 3 x 1.5 mm2

– Power cables (also for accesso-ries)

– DHW circulation pump– Central fault message

– External extension H1 or H2– Outside temperature sensor– Vitotronic 200-H (LON)– Extension kit for heating circuit

with mixer (KM BUS)– Vitotrol 100, type UTD – Vitotrol 200– Vitotrol 300– Boiler control Vitohome 300– Radio clock receiver

– Vitotrol 100, type UTD-RF – Vitotrol 100, type UTA

Interlock switchInstall an interlock for open flue operation if an extractor (e.g. cookerhood) is fitted in the room providing the boiler ventilation.For this, the internal extension H2 (accessories) can be used. Thisswitches the extractors OFF when the burner is started.

Power supply of accessoriesThe power supply of accessories can be connected directly to thecontrol unit.This connection is controlled with the system ON/OFF switch (max.4 A).Where the boiler is installed in a wet area, the power supply connectionof accessories must not be made at the control unit.

Additional requirements when installing boilers with LPG opera-tion in rooms below ground levelAccording to TRF 1996 Vol. 2 – valid as of 1 September 1997 – anexternal safety solenoid valve is no longer required when installing theVitodens below ground level.However, the high safety standard derived from the use of an externalsafety solenoid valve has proved to be valuable. We therefore recom-mend the installation of an external safety solenoid valve when instal-ling the boiler in rooms below ground level. This requires the internalextension H1.

Design information (cont.)

22 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 23: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Gas connectionGas installations must only be carried out by an approved gas fitter[CORGI] who has been authorised by the relevant gas supply utility.Connect and size the mains gas according to TRGI 2008 or TRF 1996[or local regulations].a Connect the mains gas according to ÖVGW-TR Gas (G1) and

the regionally applicable Building Regulations.Max. test pressure 150 mbar.We recommend the installation of a gas filter compliant with DIN 3386into the gas supply line.

Thermally activated safety shut-off valveAccording to paragraph 4, sect. 5 of the FeuVo '96 [Germany], ther-mally activated shut-off equipment, that isolates the gas supply ifexternal temperatures exceed 100 ºC, must be installed in gas com-bustion equipment or in gas supply lines. These valves must isolatethe gas supply for at least 30 minutes up to a temperature of 650 ºC.This should prevent the formation of explosive gas mixtures in theevent of a fire.

The gas taps supplied with the Vitodens are equipped with integralthermally activated safety shut-off valves.

Sizing the gas flow limiter

Rated output range of theVitodens

Gas flow limiter for gas type

kW Natural gas E Natural gasLL

17.0-45.0 GS 10 GS 1017.0-60.0 GS 16 GS 1630.0-80.0 GS 16 GS 1630.0-105.0 GS 16 GS 16

Minimum clearancesMaintain a clearance of 700 mm in front of the Vitodens or the DHWcylinder for maintenance purposes.

Maintenance clearances to the l.h. or r.h. side of the Vitodens arenot required.

Design information (cont.)

VITODENS 200-W VIESMANN 23

5822

432

GB

4

Page 24: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Pre-installation for installing the Vitodens 200-W directly onto a wallAn installation template is supplied with the Vitodens 200-W for thelocation of fixing holes for the wall mounting bracket and the locationof the flue pipe on the wall.Order connection sets separately for the connection of the heating cir-cuits and one DHW cylinder.

40422

480

Ø 10

752

200

A

D

B

F

E

C

A Reference point Vitodens top edgeB Installation template Vitodens C Area for electrical supply cables.

Allow all cables/leads to protrude approx. 1200 mm from thewall.

D Recommended dimension■ Single boiler system: 1975 mm■ Multi-boiler system: 1700 mm

E Wall retainerF Top edge finished floor

Installation in front of a wall with a self-supporting mountingframe (single boiler)The Vitodens can be mounted on the self-supporting mountingframe.

The panel supplied with the boiler cannot then be used.

Pre-installation, multi-boiler system

Hydraulic cascade for wall mounting and installation on self-sup-porting frames.Flow and return collectors with low loss header for multi-boiler systemsof 2 to 4 Vitodens boilers in series or 4 boilers arranged as a block.Heating circuit connections either on the right or left.

Design information (cont.)

24 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 25: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

HV

HRC

f

100

h

e

g

g

c

834

A B

ba

d

HV

HR

C

HVHR

Rp ½"

Rp ½"

k

l

Shown without the thermal insulation supplied

A Sensor well for flow temperature sensorB Air vent valveC Connection accessories with circulation pump

HR Heating returnHV Heating flow

Boiler Quantity 2x45 kW 2x80 kW 3x45 kW 3x80 kW 4x105 kW (2x2) 45 kW*3 (2x2) 80 kW*3

2x60 kW 2x105 kW 3x60 kW 3x105 kW (2x2) 60 kW*3 (2x2) 105 kW*3

Heating circuitconnection

R 2" — — — — — —PN6/DN — 65 65 100 100 65 100

Boiler connec-tion

G 1¼" 2" 1¼" 2" 2" 1¼" 2"

Max. flow rate m3/h 6.9 12.1 10.3 18.1 24.1 13.8 24.1Dimen-sions

a mm 970 1320 1320 1340 1340 1302 1340

b mm 845 1250 1250 1260 1260 1250 1260 c mm 295 250 250 260 260 250 260 d mm 100 150 150 150 150 150 150 e mm 160 200 200 280 280 200 280 f mm 230 210 210 190 190 210 190 g mm 1560 1640 2220 2335 2900 1585 1765 h mm 120 160 160 200 200 160 200 k mm 350 370 370 390 390 370 390 l mm 80 80 80 120 120 80 120

*3 Arranged as a block

Design information (cont.)

VITODENS 200-W VIESMANN 25

5822

432

GB

4

Page 26: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Installation in series, directly against the wall

cd

≥ 20

0

ab

HV

HR

1700

A

B C

D

e

100

Shown without the thermal insulation supplied

A Flue gas cascadeB VitodensC Vitotronic 300-K (to be fitted to the wall either to the left or the

right)The total length of all BUS cables (on site) should not exceed50 m.

D Hydraulic cascadeHR Heating returnHV Heating flow

For details regarding the flue gas cascade, see page 20 and the tech-nical guide on flue gas systems.

For further details regarding the hydraulic cascade, see page 24.

Number of boilers 2x45 kW 2x80 kW 3x45 kW 3x80 kW 4x105 kW 2x60 kW 2x105 kW 3x60 kW 3x105 kW

a mm 1060 1060 1640 1640 2220b mm 1660 1640 2220 2335 2900c mm 176 176 205 205 234d mm 155 241 155 241 241e mm 388 443 388 443 443

Multi-boiler system standard delivery■ Vitodens 200-W (2 to 4 boilers)■ Cascade control unit Vitotronic 300-K■ Cascade communication module for each boiler

■ Immersion temperature sensor for the low loss header■ Hydraulic cascade with low loss header and thermal insulation■ Connection accessory with circulation pumps (3-stage) and thermal

insulation

Design information (cont.)

26 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 27: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Installation in series with self-supporting mounting frames

cd

≥ 20

0

ab

HV

HR

618

618

1700

AB

D

D

F

E

580

552

675

C

Shown without the thermal insulation supplied

A Flue gas cascadeB Ceiling mountingC VitodensD Vitotronic 300-K (to be fitted to the wall either to the left or the

right)The total length of all BUS cables (on site) should not exceed50 m.

E Self-supporting mounting frameF Hydraulic cascadeHR Heating returnHV Heating flow

For details regarding the flue gas cascade, see page 20 and the tech-nical guide on flue gas systems.

For further details regarding the hydraulic cascade, see page 24.

Number of boilers 2x45 kW 2x80 kW 3x45 kW 3x80 kW 4x105 kW 2x60 kW 2x105 kW 3x60 kW 3x105 kW

a mm 1160 1160 1740 1740 2320b mm 1610 1700 2270 2395 2960c mm 176 176 205 205 234d mm 325 404 325 404 404

Multi-boiler system standard delivery■ Vitodens 200-W (2 to 4 boilers)■ Cascade control unit Vitotronic 300-K■ Cascade communication module for each boiler■ Immersion temperature sensor for the low loss header

■ Self-supporting mounting frame with ceiling mounting■ Hydraulic cascade with low loss header and thermal insulation■ Connection accessory with circulation pumps (3-stage) and thermal

insulation

Design information (cont.)

VITODENS 200-W VIESMANN 27

5822

432

GB

4

Page 28: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Block installation, floorstanding in a room

≥ 2

00

HR

618

1700

B

C D

F

E

1160

A

HV

ab c

176

Shown without the thermal insulation supplied

A Flue gas cascadeB Ceiling mountingC VitodensD Vitotronic 300-K (to be fitted to the wall either to the left or the

right)The total length of all BUS cables (on site) should not exceed50 m.

E Mounting frameF Hydraulic cascadeHR Heating returnHV Heating flow

For details regarding the flue gas cascade, see page 20 and the tech-nical guide on flue gas systems.For further details regarding the hydraulic cascade, see page 24.

Boiler 4x45 kW 4x80 kW 4x60 kW 4x105 kW

a mm 1585 1765b mm 403 703c mm 843 1280

Multi-boiler system standard delivery■ Vitodens 200-W (4 boilers)■ Cascade control unit Vitotronic 300-K

■ Cascade communication module for each boiler■ Immersion temperature sensor for the low loss header■ Hydraulic cascade with low loss header

– Thermal insulation– Mounting frame– Ceiling mounting

■ Connection accessory with circulation pumps (3-stage) and thermalinsulation

Design information (cont.)

28 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 29: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

4.2 Condensate connectionRoute the condensate drain with a constant slope.Route the condensate from the flue gas system (if equipped with adrain), together with the boiler condensate directly or (if installed) viaa neutralising system to the public sewer.

NoteA pipe vent valve must be installed between the siphon and the neu-tralising system.

A

B

Vitodens 200-W, 45 and 60 kW

A Drain hose (standard delivery for the Vitodens)B Drain outlet kit (accessories)

A

B

Vitodens 200-W, 80 and 105 kW

A Drain hose (standard delivery for the Vitodens)B Drain outlet kit (accessories)

Condensate drain and neutralisationDrain the condensate created during the heating operation in the con-densing boiler and in the flue pipe in accordance with appropriate reg-ulations. During gas combustion, the condensate will have a pHbetween 4 and 5.The Code of Practice ATV-DVWK-A 251 "Condensate from condens-ing boilers", that is generally based on the local waste water regula-tions [in Germany], determines conditions for draining condensatefrom condensing boilers into the public sewer system.The consistency of condensate drained from Vitodens condensingboilers meets the requirements specified in the Code of Practice ATV-DVWK-A 251.The condensate drain to the sewer connection must be able to beinspected.It must be installed with a continuous gradient and must contain astench trap. Also provide a suitable facility for extracting samples.Condensate drains must only be made from corrosion-resistant mate-rials (e.g. reinforced hoses).Never use any galvanised materials or those containing copperfor pipes, connectors, etc. A siphon is installed in the condensate drain to prevent flue gasesescaping.Local waste water regulations and/or specific technical circumstancesmay specify designs that vary from those described in the aboveCodes of Practice.It is advisable to contact your local authority responsible for wastewater management prior to installation, to find out about local regula-tions.

Condensate from gas combustion equipment up to 200 kW com-bustion outputUp to a rated output of 200 kW, the condensate from a gas condensingboiler can generally be introduced into the public sewer system withoutprior neutralisation.Also ensure that your domestic drainage system is made from mate-rials that are resistant to acidic condensate.

According to the Code of Practice ATV DVWK A 251, these materialsinclude:■ Clay pipes■ Hard PVC pipes■ PVC pipes■ PE HD pipes■ PP pipes■ ABS/ASA pipes■ Stainless steel pipes■ Borosilicate pipes

Neutralising system

A

C

B

A Condensate drainB Neutralising systemC Venting via the roof

Design information (cont.)

VITODENS 200-W VIESMANN 29

5822

432

GB

4

Page 30: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

The Vitodens can (if required) be supplied with a separate neutralisingsystem (accessories). Any condensate is piped to and treated in theneutralising system.The condensate drain to the sewer connection must be able to beinspected. It must be installed with a slope and stench trap on thesewer side, and must provide a suitable facility for extracting sam-ples.Install a condensate lifting pump if the Vitodens has been installedbelow the waste water antiflooding level.Condensate lift pumps are available as accessories (see the Vitosetpricelist).Since the consumption of neutralisation granulate depends on theoperating mode of the system, determine the required top-up amountduring the first year of operation by regular checks. It is feasible thatone fill may last longer than 12 months.

Neutralising system for single boiler systems with 45 and 60 kWPart no. 9535 742

400 DN 40

145

Neutralising system for single boiler systems with 80 and 105 kW, and multi-boiler systemsPart no. 7226 141

A

B

B

A

145

6019

2

420520

346

118118

A Inlet (DN 20)B Outlet (DN 20)

Condensate lifting system

part no. 7374 796Automatic condensate lifting system for condensate with a pH value≥ 2.7 from oil and gas condensing boilers.Components:■ Condensate container 0.5 l■ Shaftless permanent magnet ball motor pump■ Control unit for pump operation, display of operating conditions and

fault messages■ 2 m long power cable with plug■ 2 m long connecting cable for fault messaging■ Two 7 24 mm connection apertures for condensate inletThe standard delivery comprises:■ 6 m long drain hose 7 14 x 2 mm■ Non-return valve

2000

90

168

148

118

A B C

A Condensate inletB Condensate inlet with drain plugC Condensate drain

SpecificationRated voltage 230 V~Rated frequency 50 HzPower consumption 20 W

Design information (cont.)

30 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 31: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

IP rating IP 44 Protection class F

Permissible medium temperature +60 °CMax. head 45 kPaMax. capacity 450 l/hZero volt contact N/C, breaking capacity

230 VA

4.3 Hydraulic connection

General

System designViessmann condensing boilers can generally be installed in any pum-ped hot water heating system (sealed system). Connection sets with integral circulation pump are available as acces-sories.Minimum system pressure 1.0 bar.The boiler water temperature is limited to 82 ºC.To minimise distribution losses, we recommend that you size the heatdistribution system to a max. flow temperature of 70 ºC.

Chemical anti-corrosion agentsCorrosion is generally avoided in correctly installed and operatedsealed heating systems.Never use chemical anti-corrosion agents.Some manufacturers of plastic pipes recommend the use of chemicaladditives. In such cases, only use anti-corrosion agents offered by theheating trade that have been approved for boilers with DHW heatingvia single-walled heat exchangers (instantaneous water heater orDHW cylinder).For this, observe the VDI guideline 2035 [or local regulations].

Heating circuitsFor heating systems with plastic pipes, we recommend the use ofimpermeable pipes to prevent the infusion of oxygen through the pipewalls.Provide system separation in heating systems with plastic pipes to DIN4726 that are permeable to oxygen. We supply a separate heatexchanger for this.Install a sludge separator in underfloor heating systems and systemswith a large water content; see the Viessmann Vitoset pricelist.Connect underfloor heating systems with very large water content(>15 l/kW), even with condensing boilers, to heating circuits via a 3-way mixer; see technical guide "Control of underfloor heating sys-tems" or the relevant sample applications.Install a temperature limiter into the flow of the underfloor heating cir-cuit to limit the maximum temperature. Observe the requirements ofDIN 18560-2 [or local regulations].

Plastic pipework for radiatorsWe also recommend the installation of a temperature limiter to restrictthe maximum temperature of plastic pipes in heating circuits with radi-ators.

Safety valveA safety valve in accordance with TRD 721 is part of the heating circuitconnection set (accessory) (opening pressure 4 bar).

Route the blow-off line in accordance with EN 12828 into a drain outlet(drain outlet kit available as an accessory). The drain outlet incorpo-rates a siphon as a stench trap.

Low water indicatorAccording to EN 12828, a low water level indicator can be omitted forboilers up to 300 kW, as long as heating can be reliably preventedwhen the water level is too low.Viessmann Vitodens boilers are equipped with a low water indicator(boil-dry protection). Tests have verified that the burner will be auto-matically switched OFF in the event of water shortage due to a leak inthe heating system and simultaneous burner operation, before theboiler or the flue system reach unacceptably high temperatures.

Attic heating centreThe installation of a low water indicator specified as compulsory byDVGW is not required when installing the Vitodens in an attic.The Vitodens condensing boilers are protected against low water lev-els in accordance with EN 12828.

Water quality/Frost protectionUnsuitable fill and top-up water increases the level of deposits andcorrosion and may lead to boiler damage.Regarding the quality and volume of heating water, incl. fill and top-upwater, observe VDI 2035.■ Thoroughly flush the entire heating system prior to filling it with water.■ Only use fill water of potable quality.■ Fill water with a water hardness in excess of the following values

must be softened, e.g. with the small softening system for heatingwater (see the Viessmann Vitoset pricelist):– Vitodens up to 45 kW: 16.8 °dH (3.0 mol/m3)– Vitodens from 60 kW and multi-boiler systems up to 200 kW:

11.2 °dH (2.0 mol/m3)– Multi-boiler systems above 200 kW: 8.4 °dH (1.5 mol/m3)

■ An antifreeze additive suitable for heating systems can be mixed withthe fill water. The antifreeze manufacturer must verify its suitability,since otherwise damage to gaskets and diaphragms can occur aswell as noise during heating operation. Viessmann accepts no lia-bility for damage or consequential damage as a result.

■ For commissioning or systems with a volume that is in excess of20 litres/kW, observe VDI 2035.

Installation examplesFor installation examples for the Vitodens 200-W, see "System exam-ples".

Expansion vesselsIn accordance with EN 12828, water heating systems must be equip-ped with an expansion vessel.

The size of the expansion vessel is subject to the heating systemspecification and should be checked in each case.

Low loss header

Application

Design rules for system hydraulics:

Design information (cont.)

VITODENS 200-W VIESMANN 31

5822

432

GB

4

Page 32: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

■ Generally install a low loss header with the Vitodens 200-W in multi-boiler systems.

■ When balancing the low loss header, adjust the flow rate on theequipment side approx. 10 to 30 % lower than the flow rate on thesystem side (reducing the return temperature).

■ The low loss header should be sized for the max. volume flow thatmay occur in the overall system.

The low loss header separates the heat source (boiler circuit) from thedownstream heating circuits.Install a low loss header if the maximum flow rate of an individualdesign is greater than the values shown in the table below.

Boiler Max. flow rate l/h

Vitodens 200-W, 17 - 45 kW 3500Vitodens 200-W, 17 - 60 kW 3500Vitodens 200-W, 30 - 80 kW 5700Vitodens 200-W, 30 - 105 kW 5700

We recommend installing a low loss header if the minimum flow rateslisted in the table below cannot be guaranteed.

Boiler Min. flow rate l/h

Vitodens 200-W, 17 - 45 kW 450Vitodens 200-W, 17 - 60 kW 450Vitodens 200-W, 30 - 80 kW 1300Vitodens 200-W, 30 - 105 kW 1300

For installation designs in conjunction with low loss headers, see therelevant sample application in the "System examples" document.

Boiler circuitThe circulation pump in the Vitodens must be able to supply therequired water volume against the (mostly low) pressure drop of theboiler circuit; the pressure drop of the low loss header is negligible.Subject to the water volume circulating in the generator circuit, therespective residual head may be determined for sizing the internal pipediameters using the pump diagram; alternatively the variable speedpump can be adjusted accordingly.

Heating circuitThe central heating pumps to be installed on site must be able todeliver the water volume in the heating circuits against their pressuredrop; size the pumps accordingly.

Principle of operation

T1 T3

T2 T4

VsecondaryVprimary

Vprimary Heating water volume in the heat source circuit (approx.10 - 30 % less than Vsecondary)

Vsecondary Heating water volume heating circuit

T1 Flow temperature boiler circuitT2 Return temperature boiler circuitT3 Heating circuit flow temperatureT4 Return temperature heating circuitQprimary Amount of heat supplied by the boilerQsecondary Amount of heat transferred by the heating circuit

Vprimary < Vsecondary T1 > T3 T2 ≃ T4 Qprimary = Qsecondary

NoteSuitable thermometers in the flow and return of the low loss headermake adjustments easier.

Low loss header in conjunction with Modular-DiviconFor description and specification, see page 14.

Low loss header for the Vitodens 200-W with 45 and 60 kW fromthe Vitoset rangeSee the "Vitoset" pricelist.

ed

c

ba

HV

HR

KV

KR

HR Heating returnHV Heating flowKR Boiler returnKV Boiler flow

Flow rate max.

m3/h 4 4 8 10 18

Connections - Female thread Rp 1 - Male thread R 1¼" 2" - Flange DN 65 80Dimensions

a mm 500 500 800 1400 1450

b mm 360 360 650 1000 1000 c mm 270 270 550 1000 1000 d mm 80 80 120 160 200 e mm 50 50 80 80 120

Low loss header for the Vitodens 200-W with 80 and 105 kWSee page 19.

Low loss header with distributor/manifold for multi-boiler sys-tems with 2 to 4 Vitodens 200-WFor description and specification, see page 24.

Design information (cont.)

32 VIESMANN VITODENS 200-W

4

5822

432

GB

Page 33: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

5.1 Vitotronic 100, type HC1, for constant temperature operation

Structure and functions

Modular designThe control unit is integrated into the boiler.The control unit is comprised of a basic unit, electronic modules anda programming unit.

Basic unit:■ ON/OFF switch■ Optolink laptop interface■ Operating and fault display■ Reset button■ Fuses

Programming unit:■ Display■ Adjustment and display of temperatures and codes■ Fault message display■ Keys:

– Program selection– Boiler water temperature– DHW temperature– Emissions test function

Functions■ Electronic boiler control unit for operation at a constant boiler water

temperature■ Room temperature-dependent operation requires a Vitotrol 100,

type UTA, UTD or UTD-RF (according to EnEV [Germany])■ Heating system frost protection■ Integral diagnostic system■ Integral cylinder thermostat

Control characteristicsPI characteristics with modulating output.

Setting the heating programsThe heating system frost protection (see frost protection function)applies to all heating programs.You can select the following heating programs with the programkeys:

■ Heating and DHW■ DHW only■ Standby mode

Frost protection functionThe frost protection function is active in all heating programs.The burner is switched ON at a boiler water temperature of 5 ºC andwill be switched OFF again at a boiler water temperature of 20 ºC.The circulation pump will be switched ON simultaneously with theburner and switched OFF after a delay.The DHW cylinder will be heated to approx. 20 ºC.To protect the system against frost, the circulation pump may be star-ted at certain intervals (up to 24 times per day) for periods of approx.10 minutes.

Summer modeHeating program "w" The burner starts only when the DHW cylinder needs to be heated upagain.

Boiler water temperature sensorThe boiler water temperature sensor is connected to the control unitand built into the boiler.

SpecificationPermissible ambient temperature – during operation 0 to +130 °C– during storage and transport -20 to +70 °C

Cylinder temperature sensorStandard delivery contains the DHW cylinder connection set.

SpecificationLead length 3.75 m, fully wiredIP rating IP 32Permissible ambient temperature – during operation 0 to +90 °C– during storage and transport –20 to +70 °C

Specification, Vitotronic 100

Rated voltage 230 V~Rated frequency 50 HzRated current 6 AProtection class IFunction Type 1 B to EN 60730-1Permissible ambi-ent temperature

– during operation 0 to +40 °CInstallation in living spaces or boiler rooms(standard ambient conditions)

– during storageand transport –20 to +65 °C

Electronic tempera-ture limiter setting(heating mode) 82 °C (change not possible)Setting range forthe DHW tempera-ture

10 to 68 °C

5.2 Vitotronic 200, type HO1, for weather-compensated operationStructure and functions

Modular structureThe control unit is integrated into the boiler.The control unit comprises a standard unit, electronic modules and aprogramming unit.

Standard unit:■ ON/OFF switch■ Optolink laptop interface

■ Operating and fault display■ Reset button■ Fuses

Programming unit:■ With digital time switch■ Illuminated display with plain text support■ Adjustment and display of temperatures and codes■ Fault message display

Control units

VITODENS 200-W VIESMANN 33

5822

432

GB

5

Page 34: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

■ Rotary selector for the temperature in standard mode■ Keys:

– Program selection– Holiday program– Party and economy mode– Temperature for reduced mode– DHW temperature– Emissions test function– Time/date

Functions■ Weather-compensated control of the boiler water and/or flow tem-

perature■ Electronic maximum and minimum temperature limit■ Demand-dependent heating circuit pump and burner OFF control■ Adjustment of a variable heating limit■ Anti-seizing pump protection■ Heating system frost protection■ Integral diagnostic system■ Maintenance display■ Cylinder temperature control with priority■ Auxiliary function for DHW heating (short-term heating to a higher

temperature)■ Screed drying program■ External starting and blocking (accessories)

The requirements of DIN EN 12831 for the heating load calculation aremet. To reduce the heat-up load, the reduced room temperature willbe raised in case of low outside temperatures. The flow temperaturewill be raised for a limited time to reduce the heat-up time after a set-back period.According to the Energy Savings Order [Germany], the temperature ineach room must be individually controlled, e.g. through thermostaticradiator valves.

Control characteristicsPI characteristics with modulating output.

Time switchDigital time switch■ Individual and 7-day program■ Automatic summer/winter time changeover■ Automatic function for DHW heating and DHW circulation pump■ Time, day and standard switching times for central heating, DHW

heating and the DHW circulation pump are factory-set■ Switching times are individually programmable, i.e. up to four switch-

ing periods per dayShortest switching interval: 10 minutesPower backup: 14 days

Setting the heating programsThe heating system frost protection (see frost protection function)applies to all heating programs.You can select the following heating programs with the programkeys:■ Heating and DHW■ DHW only■ Standby modeExternal heating program changeover in conjunction with an externalextension H1 or H2.

Frost protection function■ The frost protection function will be started when the outside tem-

perature drops below approx. +1 °C.With frost protection, the heating circuit pump is switched ON andthe boiler water is maintained at a lower temperature of approx.20 °C.The DHW cylinder will be heated to approx. 20°C.

■ The frost protection function will be stopped when the outside tem-perature rises above approx. +3 °C.

Summer modeHeating program "w"The burner starts only when the DHW cylinder needs to be heated upagain.

Adjusting the heating curves (slope and level)The Vitotronic 200 controls the boiler water temperature (= flow tem-perature of the heating circuit without mixer) and the flow temperatureof the heating circuit with mixer (in conjunction with the extension kitfor one heating circuit with mixer) subject to outside temperature. Theboiler water temperature is automatically boosted by between 0 and40 K higher than the currently required set flow temperature (deliveredcondition 8 K).The flow temperature required to reach a specific room temperaturedepends on the heating system and the thermal insulation of the build-ing to be heated.Adjusting both heating curves matches the boiler water temperatureand the flow temperature to these operating conditions.Heating curves:The upper boiler water temperature is limited by the temperature limiterand the temperature set at the electronic maximum thermostat.The flow temperature cannot exceed the boiler water temperature.

3.2

3.4

Boile

r wat

er o

rflo

w te

mpe

ratu

re in

°C

Outside temperature in °C

Heating curve slope

3.0

2.8

2.2

2.4

2.0

1.6

1.41.21.00.80.60.40.2

9080706050403020

-20-15-10-5051015201.

8

2.6

-30-25

Heating systems with low loss headerWhen using a hydraulic separation (low loss header), connect a tem-perature sensor for use in the low loss header.

Boiler water temperature sensorThe boiler water temperature sensor is connected to the control unitand built into the boiler.

SpecificationPermissible ambient temperature – during operation 0 to +130 °C– during storage and transport -20 to +70 °C

Cylinder temperature sensorStandard delivery contains the DHW cylinder connection set.

SpecificationLead length 3.75 m, fully wiredIP rating IP 32Permissible ambient temperature – during operation 0 to +90 °C– during storage and transport –20 to +70 °C

Outside temperature sensorInstallation location:■ North or north-western wall of the building■ 2 to 2.5 m above the ground, for multi-storey buildings in the upper

half of the second floorConnection:

Control units (cont.)

34 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 35: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

■ 2-core lead, length up to 35 m with a cross-section of 1.5 mm2 (cop-per)

■ Never route this lead immediately next to 230/400 V cables

41 66

80

SpecificationProtection IP 43 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature duringoperation, storage and transport -40 to +70 °C

Specification, Vitotronic 200

Rated voltage 230 V~Rated frequency 50 HzRated current 6 AProtection class IPermissible ambienttemperature

– during operation 0 to +40 °CInstallation in living spaces or boiler rooms(standard ambient conditions)

– during storage andtransport –20 to +65 °C

Electronic temperaturelimiter setting (heatingmode) 82 °C (change not possible)Setting range for theDHW temperature

10 to 68 °C

Heating curve settingrange

Slope 0.2 to 3.5Level –13 to 40 K

5.3 Vitotronic 300-K, type MW2 for multi-boiler systems

Cascade control unit for the Vitodens 200-W with a Vitotronic 100Weather-compensated, digital cascade and heating circuit controlunit■ for multi-boiler systems up to 4 Vitodens 200-W■ with sequential boiler strategy■ for one system circuit and up to two heating circuits with mixer. Up

to a further 32 Vitotronic 200-H heating circuit control units can beconnected via the LON BUS (LON module required; accessory)

■ for modulating operation in conjunction with the Vitotronic 100, typeHC1

■ with cylinder temperature control unit or control unit of a primarystore system with mixer assembly

■ capable of communicating via the LON BUS (LON communicationmodule and terminators are available as accessories)

■ with integral diagnostic system.

NoteFor higher interference protection, connect all boilers with theVitotronic 100 and the Vitotronic 300-K cascade control unit to thesame phase.

Construction and function

Modular structureThe control unit comprises a standard unit, electronic modules and aprogramming unit.Standard unit:■ ON/OFF switch■ Emissions test switch■ Optolink laptop interface■ Operation and fault displays■ Plug connection chamber

– Connection of external equipment via a system plug– Plug the connectors directly into the front of the open control unit– Connection of three-phase consumers via additional contactors

Programming unit:■ The same user interface as the Vitotronic boiler control units■ With digital time switch■ Backlit display with plain text support■ Adjustment and display of temperatures and codes■ Fault message display

■ Rotary selector for the temperature in standard mode■ Keys:

– Temperature for reduced mode– Program selection– Holiday program– Party and economy mode– DHW temperature– Heating circuit curves for system flow temperature and heating

circuit flow temperature– Heating circuit selection

Functions■ Weather-compensated regulation of system/boiler water tempera-

ture of a multi-boiler system with up to 4 Vitodens 200-W withVitotronic 100, type HC1 (modulating temperature) and the flow tem-perature of the heating circuits with mixer

■ Control of the Vitotronic 100, type HC1 of the boilers in accordancewith a boiler sequence strategy (can be freely selected)

■ Electronic maximum temperature limiter■ Demand-dependent heating circuit pump shutdown■ Adjustment of a variable heating limit

Control units (cont.)

VITODENS 200-W VIESMANN 35

5822

432

GB

5

Page 36: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

■ Anti-seizing pump protection■ Central fault message■ Integral diagnostic system■ Adaptive cylinder thermostat with priority (heating circuit pump OFF,

mixer closed)■ Auxiliary function for DHW heating (short-term heating to a higher

temperature)■ Control unit of a primary store system with a regulated 3-way mixing

valve■ Screed drying, for underfloor heating systems

The requirements of DIN EN 12831 for the heating load calculation aremet. To reduce the heat-up load, the reduced room temperature willbe raised in case of low outside temperatures. The flow temperaturewill be raised for a limited time to reduce the heat-up time after a set-back period.According to the Energy Savings Order [Germany], the temperature ineach room must be individually controlled, e.g. through thermostaticradiator valves.

DHW heating in a multi-boiler system

A

M M

A Vitotronic 300-K

Control characteristics■ PI characteristics with three-point output■ Setting range for heating curves:

– Slope: 0.2 to 3.5– Level: –13 to 40 K– Max. limit: 1 to 127 °C– Min. limit: 1 to 127 °C– Differential temperature for a heating circuit with mixer: 0 to 40 K

■ Set DHW temperature range:10 to 60 °C, adjustable to 10 to 95 °C (available temperature limitedby the max. boiler flow temperature).

Time switchDigital time switch■ Day and week program, annual calendar■ Automatic summer/winter time changeover■ Automatic function for DHW heating and DHW circulation pump■ Time, day and standard switching times for central heating, DHW

heating and the DHW circulation pump are factory-set■ Switching times are individually programmable, i.e. up to four switch-

ing periods per dayShortest switching interval: 10 minutesPower backup: 5 years

Setting heating programsThe heating system frost protection (see frost protection function)applies to all heating programs.You can select the following heating programs with the programkeys:■ Heating and DHW■ Only DHW■ Standby modeOptional external changeover of heating program for all heating cir-cuits together or for selected heating circuits only.

Frost protection function■ The frost protection function will be started when the outside tem-

perature drops below approx. +1 °C.With frost protection, the heating circuit pump is switched ON andthe boiler water is maintained at a lower temperature of approx.20 °C.The DHW cylinder will be heated to approx. 20°C.

■ The frost protection function will be stopped when the outside tem-perature rises above approx. +3 °C.

Summer mode("DHW only")One or several burner(s) start(s), when the DHW cylinder needs to beheated up (controlled by the cylinder temperature control unit).

Adjusting the heating curves (slope and level)Subject to heating system:■ The Vitotronic controls the flow temperature of up to 2 heating cir-

cuits with mixer in weather-compensated mode■ The Vitotronic controls the system/flow temperature automatically 0

to 40 K (delivered condition 8 K) higher than the current maximumset flow temperature

The flow temperature required to reach a specific room temperaturedepends on the heating system and the thermal insulation of the build-ing to be heated.Adjusting the heating curves matches the system flow temperatureand the heating circuit flow temperature to these conditions.

Control units (cont.)

36 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 37: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

3.2

3.4

Boile

r wat

er o

rflo

w te

mpe

ratu

re in

°C

Outside temperature in °C

Heating curve slope

3.0

2.8

2.2

2.4

2.0

1.6

1.41.21.00.80.60.40.2

9080706050403020

-20-15-10-505101520

1.8

2.6

-30-25

The upper flow temperature is limited by temperature controller "R"and the electronically set maximum temperature of the Vitotronic 100boiler control units, type HC1.

Outside temperature sensorInstallation location:■ North or north-western wall of the building■ 2 to 2.5 m above the ground, for multi-storey buildings in the upper

half of the second floorConnection:■ 2-core lead, length up to 35 m with a cross-section of 1.5 mm2 (cop-

per)■ Never route this lead immediately next to 230/400 V cables

41 66

80

SpecificationProtection IP 43 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature duringoperation, storage and transport -40 to +70 °C

Immersion temperature sensorTo capture the common flow temperature of the multi-boiler system.This sensor is inserted into the sensor well of the low loss header or itis secured with a tie.

SpecificationLead length 3.75 m, fully wiredIP rating IP 32 to EN 60529;Permissible ambient temperature – during operation 0 to +90 °C– during storage and transport –20 to +70 °C

Cylinder temperature sensor

SpecificationLead length 5.8 m, fully wiredIP rating IP 32 to EN 60529;Permissible ambient temperature – during operation 0 to +90 °C– during storage and transport –20 to +70 °C

Specification, Vitotronic 300-K

Rated voltage: 230 V~Rated frequency: 50 HzRated current: 6 APower consumption: 10 WSafety class: IProtection: IP 20 D to EN 60529,

ensure through design/installation

Function: Type 1B to EN 60730-1Permissible ambient temperature – during operation: 0 to +40 °C use in the living

space or in boiler rooms(standard ambient condi-tions)

– during storage and transport: –20 to +65 °C

Rated breaking capacity of the relay out-puts:

– Heating circuit pumps or heatexchanger set sÖ: 4(2) A 230 V~

– Circulation pump for cylinder heatingsA:

4(2) A 230 V~

– DHW circulation pump sK: 4(2) A 230 V~– Distribution pump sL: 4(2) A 230 V~– Central fault message gÖ: 4(2) A 230 V~– Motor, 3-way mixing valve, primary

store systemorMixer motor gS: 0.2(0.1) A 230 V~

– Overall max. 6 A 230 V~

Control units (cont.)

VITODENS 200-W VIESMANN 37

5822

432

GB

5

Page 38: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Dimensions

297

584

108

172

B

A

A

B

A Vitotronic 300-KB Mounting panel

Delivered condition Vitotronic 300-K

■ Programming unit with backlit plain text prompts■ Cascade communication module (corresponding to no. Vitodens)■ Outside temperature sensor■ Flow temperature sensor■ Cylinder temperature sensor■ Mounting panel

The control unit is fitted to the wall with a mounting panel.

An extension kit (accessories) is required for each heating circuit withmixer.The LON communication module and BUS terminators are availableas accessories to enable communication.

Heating system with DHW cylinderOrder the circulation pump with check valve or the Vitotrans 222 pri-mary store system separately.

5.4 Accessories for the Vitotronic

Allocation to control unit types

Vitotronic 100 200 300-KType HC1 HO1 MW2AccessoriesVitotrol 100, type UTA x Vitotrol 100, type UTD x External extension H4 x Vitotrol 100, type UTD-RF x Vitotrol 200 x xVitotrol 300 x xRoom temperature sensor x xRadio clock receiver x xFunction extension 0–10 V xImmersion temperature sensor x Cylinder temperature sensor x x Vitocom 100 x x xExtension kit for one heating circuit with mixer xExtension kit for one heating circuit with mixer with integral mixermotor

x

Extension kit for one heating circuit with mixer with separate mixermotor

x

Mixer motor for flanged mixers x xImmersion thermostat x xContact thermostat x xLON communication module x xLON connecting cable x xLON coupling x xLON plug-in connector x xLON socket x xTerminator x xKM BUS distributor x x xInternal extension H1 x x Internal extension H2 x x External extension H1 x x External extension H2 x x

Control units (cont.)

38 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 39: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Vitotrol 100, type UTA

Part no. 7170 149

Room thermostat■ With switching output (two-point output)■ With analog time switch■ With adjustable individual day program■ Standard switching times are factory-set (individually programma-

ble)■ Shortest switching interval 15 minutes

Install the Vitotrol 100 in the main living room on an internal wall oppo-site radiators, but not inside shelf units, recesses, immediately by adoor or a heat source (e.g. direct sunlight, fireplace, TV set, etc.).Control unit connection:3-core cable with a cross-section of 1.5 mm2 (without green/yellow) for230 V~.

150

34

90

SpecificationRated voltage 230 V/50 HzRated breaking capacity of the con-tact 6(1) A 250 V~Protection IP 20 to EN 60529

safeguard through appropriatedesign and installation

Permissible ambient temperature – during operation 0 to +40 °C– during storage and transport -20 to +60 °CSet value range for standard andreduced mode 10 to 30 °CSet room temperature in standbymode 6 °C

Vitotrol 100, type UTD

Part no. 7179 059

Room thermostat■ With switching output (two-point output)■ With digital time switch■ With individual day and 7-day programs■ With rotary selector for the following settings:

– Standard room temperature "Permanent comfort"– Reduced room temperature "Permanent setback"– Frost protection temperature "Frost"– 2 fixed time programs– 1 individually adjustable time program– Holiday program

■ With selector keys for party and economy mode

Install the Vitotrol 100 in the main living room on an internal wall oppo-site radiators, but not inside shelf units, recesses, immediately by adoor or a heat source (e.g. direct sunlight, fireplace, TV set, etc.).Operation without power supply (two 1.5 V round alkaline cells,type LR6 (AA), which run for approx. 18 months)Control unit connection:2-core cable with a cross-section of 1.5 mm2 for 230 V~Connection via a LV cable is possible in conjunction with the externalextension H4 (accessories).

144

30

98

SpecificationRated voltage 3 V–Rated breaking capacity of the zerovolt contact

– max. 6(1) A 230 V~– min. 1 mA 5 V–Protection IP 20 to EN 60529

safeguard through appropriatedesign and installation

Function RS type 1B to EN 60730-1Permissible ambient temperature – during operation 0 to +50 °C– during storage and transport -10 to +60 °CSetting range – Comfort temperature 10 to 30 °C– Setback temperature 10 to 30 °C– Frost temperature 6 to 10 °CPower reserve during batterychange 10 min

Control units (cont.)

VITODENS 200-W VIESMANN 39

5822

432

GB

5

Page 40: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

External extension H4

Part no. 7197 227Connection extension for connecting the Vitotrol 100, type UTD or24 V clock thermostats via a LV cable.With cable (0.5 m long) and plug for the connection to theVitotronic 100.

72 130

45

SpecificationRated voltage 230 V~Output voltage 24 V~Rated frequency 50 HzPower consumption 2.5 WLoad 24 V~ (max.) 10 WProtection class IProtection IP 41Permissible ambient temperature – during operation 0 to +40 °C

Installation in living spaces orboiler rooms (standard ambi-ent conditions)

– during storage and transport -20 to +65 °C

Vitotrol 100, type UTD-RF

Part no. 7160 432

Room thermostat with integral wireless transmitter and one receiver■ With digital time switch■ With individual and seven-day programs■ With rotary selector for the following settings:

– Standard room temperature "Permanent Comfort"– Reduced room temperature "Permanent Setback"– Frost protection temperature "Frost"– 2 fixed time programs– One individually adjustable time program– Holiday program

■ With selector keys for party and economy mode

Install the Vitotrol 100 in the main living room on an internal wall oppo-site radiators, but not inside shelf units, recesses, immediately by adoor or a heat source (e.g. direct sunlight, fireplace, TV set, etc.).Operation of the room thermostat without power supply (two 1.5 Vround alkaline cells, type LR6 (AA) that last for approx. 18 months)Receiver with reception strength indicator and indication of the relaystate.

Connection of the receiver to the control unit:■ 4-core cable with a cross-section of 1.5 mm2 for 230 V~

or■ 3-core cable without green/yellow core

144

30

98

80

120

31

Specification, room thermostatRated voltage 3 V–Transmission frequency 868 MHzTransmission < 10 mWRange approx. 25 - 30 m inside build-

ings, subject to constructionProtection IP 20 to EN 60529;

ensure through appropriatedesign/installation

Function RS Type 1B to EN 60730-1Permissible ambient temperature – during operation 0 to +50 °C– during storage and transport –10 to +60 °CSetting range – Comfort temperature 10 to 30 °C– Setback temperature 10 to 30 °C– Frost temperature 6 to 10 °CPower reserve during batterychange 10 min

Specification, receiverOperating voltage 230 V~ +/– 10% 50 HzRated breaking capacity of the zerovolt contact

1 A, 250 V~

Protection IP 20 to EN 60529;ensure through appropriatedesign/installation

Protection class II to EN 60730-1 subject to cor-rect installation

Permissible ambient temperature 0 to +55 °C

Notes regarding room temperature hook-up (RS function) for remote control unitsNever activate the RS function for underfloor heating circuits (iner-tia).

Control units (cont.)

40 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 41: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

In heating systems with a heating circuit without mixer and heatingcircuits with mixer, the RS function must only affect the heating circuitwith mixer.

Information regarding the Vitotrol 200 and 300For every heating circuit in a heating system, one Vitotrol 200 or oneVitotrol 300 can be deployed.

Vitotrol 200

Part no. 7450 017KM BUS subscriberThe Vitotrol 200 remote control regulates the heating program for oneheating circuit and the required set room temperature in standardmode, from any room in the house.The Vitotrol 200 is equipped with backlit heating program selectionkeys as well as a party and economy key.The fault display shows faults on the control unit.WS function:Installation anywhere in the building.RS function:Installation in the main living room on an internal wall opposite radia-tors. Never install inside shelf units, recesses, immediately by a dooror heat source (e.g. direct sunlight, fireplace, TV set, etc.).The integral room temperature sensor captures the actual room tem-perature and effects any necessary correction of the flow temperatureas well as a rapid heat-up at the start of the heating operation (ifappropriately programmed).Connection:■ 2-core lead, length max. 50 m (even if connecting several remote

control units)■ Never route this lead immediately next to 230/400 V cables■ LV plug part of the standard delivery

3075

115

SpecificationPower supply via KM BUSPower consumption 0.2 WProtection class IIIProtection level IP 30 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature– during operation 0 to +40 °C– during storage and transport −20 to +65 °CSet room temperature range 10 to 30 °C

adjustable from3 to 23 °C or17 to 37 °C

The set room temperature for reduced mode is adjusted at the controlunit.

Vitotrol 300

Part no. 7248 907KM BUS subscriberThe Vitotrol 300 remote control regulates the required set room tem-perature for one heating circuit in standard and reduced mode, theheating program and the switching times for central heating, DHWheating and the DHW circulation pump.The Vitotrol 300 provides a backlit display as well as backlit heatingprogram keys, a party and economy key, automatic summer/wintertime changeover, keys for holiday program, day and time.WS function:Installation at any point in the building.RS function:Installation in the main living room on an internal wall opposite radia-tors. Never install inside shelf units, niches, immediately by a door orheat source (e.g. direct sunlight, fireplace, TV set, etc.).The integral room temperature sensor captures the actual room tem-perature and effects any necessary correction of the flow temperatureas well as a rapid heat-up at the start of the heating operation (if suit-ably encoded).Connection:

■ 2-core lead, length max. 50 m (even if connecting several remotecontrol units)

■ Never route this lead immediately next to 230/400 V cables■ LV plug as standard delivery

30

194

115

SpecificationPower supply via KM BUSPower consumption 0.5 W

Control units (cont.)

VITODENS 200-W VIESMANN 41

5822

432

GB

5

Page 42: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Protection class IIIProtection IP 30 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature– during operation 0 to +40 °C– during storage and transport -20 to +65 °C

Set room temperature range – for standard mode 10 to 30 °C

adjustable to3 to 23 °C or17 to 37 °C

– for reduced mode 3 to 37 °C

Room temperature sensor

Part no. 7408 012Separate room temperature sensor as supplement to the Vitotrol 200and 300; to be used if the Vitotrol 200 or 300 cannot be installed insidethe main living room or in a suitable position where the unit can captureand adjust the temperature.Installation in the main living room on an internal wall opposite radia-tors. Never install inside shelf units, recesses, immediately by a dooror heat source (e.g. direct sunlight, fireplace, TV set, etc.).Connect the room temperature sensor to the Vitotrol 200 or 300.Connection:■ 2-core lead with a cross-section of 1.5 mm2 (copper)■ Lead length from the remote control up to 30 m■ Never route this lead immediately next to 230/400 V cables

20

80□

SpecificationProtection class IIIProtection level IP 30 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature– during operation 0 to +40 °C– during storage and transport −20 to +65 °C

Radio clock receiver

Part no. 7450 563For receiving the DCF 77 time signal (location: Mainflingen near Frank-furt/Main).Radio controlled setting of time and date.Install on an outside wall, facing the transmitter. The reception may bereduced by metallic elements in the building structure, e.g. steel rein-forced concrete, neighbouring buildings and sources of electro-mag-netic interference, e.g. HV and public transport lines.Connection:■ 2-core lead, length up to 35 m with a cross-section of 1.5 mm2(cop-

per)■ Never route this lead immediately next to 230/400 V cables.

41 66

80

Function extension 0 to 10 V

Part no. 7174 718KM BUS subscriberIncluding cables with plug fÖ and aVG.■ To specify a set boiler water temperature via a 0-10 V input for a

temperature range of 10 to 100 °C (0 to 1 °V≙boiler OFF)■ To control a feed pump connected to a Vitotronic 200-H, e.g. in a

substation.■ To signal reduced mode and to regulate the heating circuit pump to

a lower speed.

217130

84

SpecificationRated voltage 230 V~Rated frequency 50 Hz

Control units (cont.)

42 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 43: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Power consumption 1 WRated breaking capacity of the relay out-put

4(2) A 230 V

IP rating IP 42 to EN 60529; ensurethrough design/installation

Permissible ambient temperature – during operation 0 to +40 °C– during storage and transport –20 to +65 °C

Vitocom 100, type GSM■ Without SIM card

Part no. Z004594■ With contract SIM card for the operation of the Vitocom 100 via

mobile phonePart no. Z004615

NoteFor further information regarding the conditions of contract, see theViessmann pricelist.

Functions:■ Remote switching via GSM mobile phone networks■ Remote scanning via GSM mobile phone networks■ Remote monitoring via SMS to 1 or 2 mobile phones■ Remote monitoring of additional systems via digital input (230 V)

Configuration:Mobile phones via SMS

Standard delivery:■ Vitocom 100 (subject to order with or without SIM card)■ Power supply cable with Euro plug (2.0 m long)■ GSM aerial (3.0 m long), magnetic foot and adhesive pad■ KM BUS cable (3.0 m long)

On-site requirements:Good reception for GSM communication of the selected mobile phoneoperator.Total length of all KM BUS subscriber cables up to 50 m.

72 130

50

SpecificationRated voltage 230 V ~Rated frequency 50 HzRated current 15 mAPower consumption 4 WProtection class IIProtection IP 41 to EN 60529; safeguard

through appropriate designand installation

Function Type 1B to EN 60 730-1Permissible ambient temperature – during operation 0 to +55 °C

Installation in living spaces orboiler rooms (standard ambi-ent conditions)

– during storage and transport -20 to +85 °COn-site connectionFault input DE 1 230 V~

Extension kit for one heating circuit with mixer with integral mixer motor

Part no. 7178 995KM BUS user

Components:■ Mixer electronics with mixer motor for Viessmann mixer DN 20 to 50

and R½" to 1¼"■ Flow temperature sensor (contact temperature sensor), lead length

2.2 m, fully wired, for specification, see below■ Connecting plug for the heating circuit pump■ Power supply cable (3.0 m long)■ BUS connecting cable (3.0 m long)

The mixer motor is mounted directly onto the Viessmann mixer DN 20to 50 and R ½" to 1¼".

Mixer electronics with mixer motor

180185

182

SpecificationRated voltage 230 V~Rated frequency 50 HzPower consumption 6.5 WProtection IP 32D to EN 60529

safeguard through appropriatedesign and installation

Protection class IPermissible ambient temperature – during operation 0 to +40 °C– during storage and transport -20 to +65 °C

Control units (cont.)

VITODENS 200-W VIESMANN 43

5822

432

GB

5

Page 44: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Rated breaking capacity of the relayoutput for heating circuit pump sÖ 4(2) A 230 V~Torque 3 NmRuntime for 90 ° ∢ 120 min

Flow temperature sensor (contact sensor)

42

76

40

Secured with a tie.

SpecificationProtection IP 32 to EN 60529

safeguard through appropriatedesign and installation

Permissible ambient temperature – during operation 0 to +120 °C– during storage and transport -20 to +70 °C

Extension kit for one heating circuit with mixer for separate mixer motor

Part no. 7178 996KM BUS userFor the connection of a separate mixer motorComponents:■ Mixer electronics for the connection of a separate mixer motor■ Flow temperature sensor (contact temperature sensor), lead length

5.8 m, fully wired■ Connecting plug for the heating circuit pump■ Mixer motor terminals■ Power supply cable (3.0 m long)■ BUS connecting cable (3.0 m long)

Mixer electronics

145185

175

SpecificationRated voltage 230 V~Rated frequency 50 HzPower consumption 2.5 WProtection IP 32D to EN 60529

safeguard through appropriatedesign and installation

Protection class IPermissible ambient temperature – during operation 0 to +40 °C– during storage and transport -20 to +65 °CRated capacity of the relay outputs Heating circuit pump sÖ 4(2) A 230 V~Mixer motor 0.2(0.1) A 230 V~Required runtime of the mixer motorfor 90 ° ∢ approx. 120 s

Flow temperature sensor (contact sensor)

42

76

40

Secured with a tie.

SpecificationProtection IP 32 to EN 60529

safeguard through appropriatedesign and installation

Permissible ambient temperature – during operation 0 to +120 °C– during storage and transport -20 to +70 °C

Extension kit for one heating circuit with mixer for the Vitotronic 300-K

Part no. 7450 650Comprising:■ Mixer motor■ Flow temperature sensor (contact temperature sensor), lead length

5.8 m, fully wired■ Connecting plug for the heating circuit pump■ Mixer motor terminals■ Connecting cable (4.2 m long)

The mixer motor is mounted directly onto the mixer DN 20 to 50 orR ½" to 1¼".

Control units (cont.)

44 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 45: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Mixer motor

180

130

90

Specification, extension kitRated voltage 230 V~Rated frequency 50 HzPower consumption 2.5 WProtection class IIP rating IP 32D to EN 60529;

ensure through design/installation

Permissible ambient temperature – during operation 0 to +40 °C– during storage and transport –20 to +65 °C

Torque 3 NmRuntime for 90° ∢ 120 s

Flow temperature sensor (contact sensor)

4042

76

Secured with a tie.

SpecificationIP rating IP 32 acc. to EN 60529

ensure through appropriatedesign/installation

Permissible ambient temperature – during operation 0 to +120 °C– during storage and transport –20 to +70 °C

Mixer motorsSee datasheet "Control unit accessories".

Immersion thermostat

Part no. 7151 728May be used as a maximum temperature limiter for underfloor heatingsystems.The temperature limiter is installed into the heating flow and switchesthe heating circuit pump OFF if the flow temperature is too high.

72 130

9520

0

SpecificationLead length 4.2 m, fully wiredSetting range 30 to 80 °CSwitching differential max. 11 KBreaking capacity 6(1.5) A 250 V~Setting scale inside the casingStainless steel sensor well R ½" x 200 mmDIN reg. no. DIN TR 116807

orDIN TR 96808

Contact thermostat

Part no. 7151 729May be used as a maximum temperature limiter for underfloor heatingsystems (only in conjunction with metallic pipes).The temperature limiter is installed into the heating flow and switchesthe heating circuit pump OFF if the flow temperature is too high.

Control units (cont.)

VITODENS 200-W VIESMANN 45

5822

432

GB

5

Page 46: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

72 130

95

SpecificationLead length 4.2 m, fully wiredSetting range 30 to 80 °CSwitching differential max. 14 KBreaking capacity 6(1.5) A 250V~Setting scale inside the casingDIN reg. no. DIN TR 116807

orDIN TR 96808

Immersion temperature sensor

Part no. 7179 488To capture the low loss header temperature.

SpecificationLead length 3.75 m, fully wiredIP rating IP 32Permissible ambient temperature – during operation 0 to +90 °C– during storage and transport –20 to +70 °C

LON communication module

PCB for data exchange with the Vitotronic 200-H and for connectingto a higher level building management system.

■ For installation into the Vitotronic 200Part no. 7179 113

■ For installation into the Vitotronic 300-KPart no. 7172 174

LON connecting cable for data exchange between control unitsVitotronic 300-K for the Vitotronic 200-H

Part no. 7143 495

Cable length 7 m, fully wired.

Control units (cont.)

46 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 47: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Extension of the connecting cable■ Installation spacing 7 to 14 m:

– 2 connecting cables (7.0 m long)Part no. 7143 495

– 1 LON coupling RJ45Part no. 7143 496

■ Installation distance 14 to 900 m with plug-in connectors:– 2 LON plug-in connectors

Part no. 7199 251– 2-core cable:

CAT5, screenedorSolid conductor AWG 26-22 / 0.13 mm2 - 0.32 mm2,Conductor AWG 26-22 / 0.14 mm2 - 0.36 mm2

7 4.5 mm - 8 mm

on-site■ Installation distance 14 to 900 m with junction boxes:

– 2 connecting cables (7.0 m long)Part no. 7143 495

– 2-core cable:CAT5, screenedorSolid conductor AWG 26-22 / 0.13 mm2 - 0.32 mm2,Conductor AWG 26-22 / 0.14 mm2 - 0.36 mm2

7 4.5 mm - 8 mmon-site

– 2 LON sockets RJ45, CAT6Part no. 7171 784

Terminator (2 pce.)

Part no. 7143 497To terminate the LON BUS at the first and last control unit.

KM BUS distributor

Part no. 7415 028For the connection of 2 to 9 devices to the Vitotronic KM BUS.

217130

84

SpecificationLead length 3.0 m, fully wiredProtection IP 32 to EN 60529;

safeguard through appro-priate design and installa-tion

Permissible ambient temperature– during operation 0 to +40 °C– during storage and transport -20 to +65 °C

Internal extension H1

Part no. 7179 057Electronic PCB for installation into the control unit.

Using the extension enables the following functions to be achieved:Function Rated breaking capacity of the relay output– Connection of an external safety solenoid valve (LPG) 1(0.5) A 250 V~and one of the following functions:– Connection of a heating circuit pump (stepped) for a directly connected heating circuit– Connection of a central fault message– Connection of a circulation pump for cylinder heating– Only with the Vitotronic 200, type HO1:

Connection of a DHW circulation pump

2(1) A 250 V~

SpecificationRated voltage 230 V~Rated frequency 50 Hz

Internal extension H2

Part no. 7179 144Electronic PCB for installation into the control unit.

Control units (cont.)

VITODENS 200-W VIESMANN 47

5822

432

GB

5

Page 48: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

Using the extension enables the following functions to be achieved:Function Rated breaking capacity of the relay output– External extractor interlock 6(3) A 250 V~and one of the following functions:– Connection of a heating circuit pump (stepped) for a directly connected heating circuit– Connection of a central fault message– Connection of a circulation pump for cylinder heating– Only with the Vitotronic 200, type HO1:

Connection of a DHW circulation pump

2(1) A 250 V~

SpecificationRated voltage 230 V~Rated frequency 50 Hz

External extension H1

Part no. 7179 058Function extension inside a casing for wall mounting.

Using the extension enables the following functions to be achieved:Function Rated breaking capacity of the relay output– Connection of a central fault message 0.4(0.2) A 250 V~– Connection of a heating circuit pump (stepped) for a directly connected heating circuit– Connection of a circulation pump for cylinder heating– Only with the Vitotronic 200, type HO1:

Connection of a DHW circulation pump

every 2(1) A 250 V~total max. 4 A~

– Minimum boiler water temperature demand– External blocking– Set boiler water temperature defaulted via a 0-10 V input– Only with the Vitotronic 200, type HO1:

External heating program changeover

217130

84

SpecificationRated voltage 230 V~Rated frequency 50 HzRated current 4 APower consumption 4 WProtection class IProtection IP 32Permissible ambient temperature – during operation 0 to +40 °C

Installation in living spaces orboiler rooms(standard ambient conditions)

– during storage and transport -20 to +65 °C

External extension H2

Part no. 7179 265Function extension inside a casing for wall mounting.

Using the extension enables the following functions to be achieved:Function Rated breaking capacity of the relay output– Only with the Vitotronic 200, type HO1:

Connection of a DHW circulation pump2(1) A 250 V~

– Minimum boiler water temperature demand– External blocking– Only with the Vitotronic 200, type HO1:

External heating program changeover

Control units (cont.)

48 VIESMANN VITODENS 200-W

5

5822

432

GB

Page 49: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

130 72

95

SpecificationRated voltage 230 V~Rated frequency 50 HzRated current 2 APower consumption 3 WProtection class IProtection IP 32Permissible ambient temperature – during operation 0 to +40 °C

Installation in living spaces orboiler rooms(standard ambient conditions)

– during storage and transport -20 to +65 °C

Appendix

6.1 Regulations / Directives

Regulations and DirectivesThe design and operational characteristics of the Vitodens gas con-densing boilers from Viessmann meet the requirements of EN 297.They are CE-designated.They may be installed in sealed heating systems with permissible flowtemperatures (= safety temperatures) up to 100 ºC compliant withEN 12828. The maximum flow temperature is approx. 15 K below thesafety temperature.Observe all standards and guidelines applicable to the installation andoperation of this system in your country.Only qualified contractors must carry out the installation, the mains gasand flue gas connections, the commissioning, the electrical connectionas well as general maintenance and repair work.The installation of a condensing boiler may need to be notified to andapproved by your local gas supplier.

In some regions, permits may be required for the flue system and con-densate drain into the public sewer.In some countries, the relevant flue gas inspector and water authoritiesmust be informed prior to commencing the installation.We recommend that you carry out maintenance and cleaning proce-dures annually. As part of the maintenance procedure, check the cor-rect function of the entire system. Remedy any faults.Condensing boilers must only be operated with specially designed,tested and approved flue pipes.Only recognised contractors may convert this boiler for use in countriesother than those stated on the type plate. That contractor must alsoarrange the acceptance in accordance with the statutes of that coun-try.

EnEV [Germany] Energy Savings Order1. BImSchV First order for the implementation of the Federal Immission Act (order regarding small and medium-sized

combustion equipment)FeuVo [Germany] Fire Regulations of the Federal StatesDIN 1986 Materials drain systemDIN 1988 Potable water pipe systems on propertiesDIN 4753 Water heaters and DHW systems for DHW and process waterDIN 18160 Domestic chimneysDIN 18380 Heating systems and central DHW heating systems (VOB)DIN 57116 Electrical equipment for combustion systemsEN 677 Gas condensing boilerEN 12828 Heating systems in buildings – design of hot water heating systemsEN 12831 Heating systems in buildings - process for calculating the standard heating loadEN 13384 Flue gas systems – thermal and flow technical calculationsATV DVWK A 251 Introduction of condensate from gas and oil combustion systems [into public sewers]DVGW G 260 Gas conditionDVGW G 600 Technical rules for gas installations (TRGI)DVGW G 688 Gas consumption equipment, condensing technologyDVGW/DVFG Technical rules for LPG (TRF)DVGW VP 113 Systems comprising combustion equipment and fluesVDI 2035 Guidelines for the prevention of losses through corrosion and scaling in hot water heating systemsVdTÜV 1466 Water quality datasheetVDE Regulations and special regulations of local energy supply companies.

Control units (cont.)

VITODENS 200-W VIESMANN 49

5822

432

GB

6

Page 50: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

AAccessories■ for control units.............................................................................38Adjusting the heating curves............................................................34Anti-corrosion agents.......................................................................31Antifreeze.........................................................................................31

BBalanced flue operation...................................................................21Boiler water temperature sensor................................................33, 34

CCascade control unit........................................................................35Combustion air supply......................................................................21Condensate......................................................................................29Condensate connection...................................................................29Constant temperature control unit■ Basic unit......................................................................................33■ Frost protection function...............................................................33■ Functions......................................................................................33■ Heating programs.........................................................................33■ Layout...........................................................................................33■ Programming unit..........................................................................33Contact thermostat...........................................................................45Control unit■ for constant temperature operation...............................................33■ for weather-compensated operation.............................................33

DDistributor with low loss header.......................................................32

EElectrical connection........................................................................22ENEV.........................................................................................34, 36Expansion vessel.............................................................................31Extension■ external H1....................................................................................48■ external H2....................................................................................48■ internal H1.....................................................................................47■ internal H2.....................................................................................47External extension H1......................................................................48External extension H2......................................................................48

FFill water...........................................................................................31Frost protection function.......................................................33, 34, 36

GGas connection................................................................................23

HHydraulic connection........................................................................31

IImmersion thermostat......................................................................45Initial heat-up....................................................................................31Installation conditions.......................................................................21Installation room...............................................................................21Interlocking circuit............................................................................21Interlock switch.................................................................................22Internal extension H1.......................................................................47Internal extension H2.......................................................................47

KKM BUS distributor...........................................................................47

LLeads/cables....................................................................................22Level.................................................................................................34LON communication module............................................................46Low loss header...............................................................................31Low water indicator..........................................................................31

MMixer extension■ Integral mixer motor......................................................................43■ Separate mixer motor...................................................................44Mixer extension kit■ Integral mixer motor......................................................................43■ Separate mixer motor...................................................................44

NNeutralisation...................................................................................29Neutralising system..........................................................................29

OOpen flue operation..........................................................................21Outside temperature sensor.......................................................34, 37

PProtection.........................................................................................22

RRoom temperature sensor...............................................................42Room thermostat........................................................................39, 40

SSafety equipment.............................................................................31Safety valve......................................................................................31Slope................................................................................................34Standard unit....................................................................................33System design..................................................................................31

TTemperature sensor■ Boiler water temperature.........................................................33, 34■ Outside temperature...............................................................34, 37■ Room temperature........................................................................42Thermally activated safety shut-off valve.........................................23Thermostat■ Contact temperature.....................................................................45■ Immersion temperature.................................................................45Time switch................................................................................34, 36

VVitocom■ 100, type GSM..............................................................................43Vitotrol■ 200................................................................................................41■ 300................................................................................................41■ UTA...............................................................................................39■ UTD...............................................................................................39■ UTD-RF.........................................................................................40

WWater quality....................................................................................31Weather-compensated control unit■ Frost protection function.........................................................34, 36■ Functions................................................................................33, 34■ Heating programs.........................................................................34■ Layout...........................................................................................33■ Programming unit..........................................................................33■ Standard unit.................................................................................33Wet area...........................................................................................22

Keyword index

50 VIESMANN VITODENS 200-W

5822

432

GB

Page 51: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

VITODENS 200-W VIESMANN 51

5822

432

GB

Page 52: Gas condensing boiler VIESMANN VITODENS 200-W · VIESMANN VITODENS 200-W Gas condensing boiler 17.0 to 105.0 kW as a multi-boiler system up to 420.0 kW VITODENS 200-W Type WB2B Wall

52 VIESMANN VITODENS 200-W

5822

432

GB

Prin

ted

on e

nviro

nmen

tally

frie

ndly

,ch

lorin

e-fre

e bl

each

ed p

aper

Subject to technical modifications.