MANUAL – INSTALLATION + SERVICE Fan Filter Unit - High Efficiency FFU-HE Series v300 Issue Date: 06/21/17 © 2017 Price Industries Limited. All rights reserved.

Upload: voxuyen

Post on 28-Mar-2019

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

MANUAL – INSTALLATION + SERVICE

Fan Filter Unit - High EfficiencyFFU-HE Series

v300 – Issue Date: 06/21/17© 2017 Price Industries Limited. All rights reserved.

Page 2: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYTABLE OF CONTENTS

Product Overview

Read & save these instructions ....................................1

Before you start ............................................................2

introduction ..................................................................3

Installation & Service Instructions

Diffuser Module Installation ...........................................4

Speed Controllers .........................................................7

PSCSC Speed Controller Installation & Operation ......7

ECMSC/WK Speed Controller Installation & Operation ..9

ECMDx/WK Speed Controller Installation & Operation..13

BACnet Flow Controller (BFC) Installation & Operation ..16

Optional Accessories

ATS .........................................................................19

Unit Filter Installation ...................................................21

Room Side Replaceable Filter (RSR .........................21

Bench Top Replaceable Filter (BTR ..........................23

Filter/Motor Indicator LED (ML/FL) - RSR ...................25

Filter/Motor Indicator LED (FL/ML) - BTR ...................27

Motor/Filter Indicator BAS (MBAS/FBAS .....................31

Service: Cleaning of Pre-Filter .....................................32

Service: Removal and Replacement of RSR Filter .......33

Service: Removal and Replacement of BTR Filters ......34

Service: Changing Motors in the Field .........................35

Top Access Motor/Blower Assembly .......................35

Room Side accessible Motor/Blower Assembly .......37

Technical Note: Static Pressure Ports .........................41

Room Side Replaceable (RSR) Port .........................41

Bench Top Replaceable (BTR) Port ..........................42

Technical Note: Design with VAV/Constant Flow Boxes

and Ducted Applications .............................................43

Technical Note: Balancing Ducted Units ......................44

Troubleshooting Tips ...................................................45

BTR ............................................................................46

RSR ............................................................................47

FFU-HE Ordering Procedure .......................................49

Warranty .....................................................................61

Page 3: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYPRODUCT OVERVIEW

Read and Save These InstructionsWarning! To reduce the risk of fire, electrical shock, or injury to persons, observe the following:

A. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.

B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

C. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer:

In the United States2975 Shawnee Ridge CourtSuwanee, Georgia USA 30024Ph: 770.623.8050 Fax: 770.623.6404

In Canada / International Export Sales Office638 Raleigh StreetWinnipeg, Manitoba Canada R2K 3Z9Ph: 204.669.4220 Fax: 204.663.2715

D. Before servicing or cleaning unit, switch power off at service panel and lock service panel to prevent power from being switched on accidentally.

E. To reduce the risk of injury to persons, install the unit at least 7ft above grade or in ceiling.

1

Page 4: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYPRODUCT OVERVIEW

Before You StartInspect all cartons and boxes for flaws and shipping damage.

If anything is discovered to be damaged, contact the shipping company and file a freight claim.

Ensure that all HEPA/ULPA filters are stored in a clean, dry location in a vertical position, as labeled on the carton.

NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty.

If units are to be ducted, read Technical Note: Design with VAV/Constant Flow Boxes and Ducted Applications, and Technical Note: Balancing Ducted Units prior to starting installation.

A minimum of two (2) people will be required to install the filters.

priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual2 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 5: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

IntroductionPrice Fan Filter Units (FFU-HE) are ceiling module diffusers consisting of a fan/motor assembly and room-side (RSR), or bench-top (BTR) removable filters. The module is designed to provide unidirectional vertical airflow of filtered, clean air over a cleanroom space.

Fan Filter Units (FFU-HE) models will have a total of three (3) stickers located on the back of the plenum. For ease of troubleshooting assistance, replacement parts, and general factory assistance, it is recommended that the order number, and model line string be available for reference. This information can be found on the Factory Label.

Eng

inee

ring

Req

uest

No:

(yyyy/mm/dd)

InitialsCompletion dateFactory order no OperatorSch datePart qty

Sheet

of

Revision

Description

Drawing no.DateStatus

Drawn by Scale

Comment/TagIssued date Blank qty

LABELFFU

ETL LABEL

045451 C 1 3

Solid Edge

C

Revised ETL Logo and manufacturing addresses. Added sheets 2 and 3. 140596 2014/12/04 GH

B 082870 2008/12/24 LPA 071119 2007/06/19 LP

Rev Description ECN Date (y/m/d) By

002 UL 1995001 UL 507

DASH # DESCRIPTION

Winnipeg, MB CANADA9801655

CONFORMS TO UL STD. 507CERTIFIED TO CSA STD. C22.2 NO.113

SERIALMODEL

H.P. VOLTS/PH/CYC

x

Manufactured By

®

AMPS

MAX OVERCURRENT PROT. (MOP)

MIN CIRCUIT AMPACITY (MCA)

045451-001 REV C

R.P.M.

MOTOR THERMALLYPROTECTED

TESTED TO 1.2" w.g. MAXOPERATING STATIC PRESSURE

INSTALL FAN AT LEAST 7 FT. ABOVE THE FLOOR

AVERTISSEMENT: COUPER LES SOURCES

POWER SUPPLIES BEFORE SERVICING.WARNING: DISCONNECT ALL REMOTE ELECTRIC

D'ALIMENTATION À DISTANCE AVANT LE DÉPANNAGE.

CONFORMS TO UL STD. 1995CERTIFIED TO CSA STD. C22.2 NO.236

SERIALMODEL

H.P. VOLTS/PH/CYC

x

Manufactured By

®

AMPS

MAX OVERCURRENT PROT. (MOP)

MIN CIRCUIT AMPACITY (MCA)

Winnipeg, MB CANADA9801655

045451-002 REV C

R.P.M.

MOTOR THERMALLYPROTECTED

TESTED TO 1.2" w.g. MAXOPERATING STATIC PRESSURE

INSTALL FAN AT LEAST 7 FT. ABOVE THE FLOOR

AVERTISSEMENT: COUPER LES SOURCES

POWER SUPPLIES BEFORE SERVICING.WARNING: DISCONNECT ALL REMOTE ELECTRIC

D'ALIMENTATION À DISTANCE AVANT LE DÉPANNAGE.

NOTES:1. MATERIAL: 3M #7883 FOIL ROLL STOCK FOR COMPUTER FEED.2. COLOR: MATTE SILVER WITH BLACK LETTERING.3. ADHESIVE: PRESSURE SENSITIVE TYPE "300".4. VENDOR: BY CERTIFIED LABEL MANUFACTURER.5. DATA PRINTED IN BY PRICE.

6. UL STD. 507: ELECTRIC FANS LISTING REPORT #: 3116139COQ-002

UL STD. 1995: HEATING AND COOLING EQUIPMENT LISTING REPORT #: 3090127COQ-001

*ALL LABEL INFORMATION MUST BE TYPED OR PRINTED.

-001 UL 507 LABEL -002 UL 1995 LABEL

MB

2002/04/29

1:1

FAN FILTER UNIT - HIGH EFFICIENCYPRODUCT OVERVIEW

ETL LABEL

FACTORY LABEL

FACTORY PERFORMANCE LABEL

SPEED CONTROLLER

EYEBOLT

OPTIONAL PRE-FILTER

OPTIONAL DUCT COLLAR

MOTOR/BLOWER ASSEMBLY

3priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manualpriceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 6: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Diffuser Module InstallationThe Price FFU-HE will come completely assembled from the factory with the exception of the HEPA/ULPA filters, will ship in its own carton, and the speed controller wall kits (if selected).

NOTE: Do not open and/or install the HEPA/ULPA filters (RSR models only) prior to the full installation of the FFU-HE units. All construction in the space should be complete, and the site and upstream air should be clean so as not to unnecessarily load the filter.

Sample line string for Room Side Replaceable filter: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB//ML/FL/WPF/PL-AL///PL-MILL//

STEP 1: Remove FFU from shipping carton and inspect for any damage.

NOTE: Ensure the HEPA/ULPA filter has been safely stored in a vertical position, per carton label, until ready for use.

STEP 2: If unit is Bench Top Replaceable (BTR) refer to page 23 for filter installation prior to proceeding. If unit is Room Side Replaceable (RSR), proceed directly to next step.

Sample line string for Bench Top Replaceable filter: FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//

Unit Unpacking

4 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 7: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 3: Raise the unit through ceiling grid at an angle until entire unit is above the ceiling grid

STEP 4: Lower unit onto the backside of the tees.

STEP 5: Secure the unit to the overhead structure using the eyebolts located on the back of the unit.

STEP 6: Adjust and level the unit so that it rests on the tees and there is adequate compression on the gasket to warrant a tight seal.

Ensure that ceiling grid is properly gasketed/sealed to prevent infiltration of unfiltered air from the ceiling plenum into the room side.

Above steps are manufacturer's suggested hanging techniques, always make sure to follow all local building codes, including seismic, where applicable.

Unit Eyebolts for Mounting

5priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 8: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 7: Refer to Factory Label to determine which speed controller is on the unit and use the following table for appropriate reference page for the particular speed controller on your unit.

Sample line string for speed controller: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB//ML/FL/WPF/PL-AL///PL-MILL//

Speed Controller Page Reference

PSCSC/WK 7

ECMSC/WK 9

ECMDX/WK 13

BFC 16

NOTE: Depending on unit ordered, speed controller will be mounted on the unit itself, or, if a wall-kit option was selected, shipped loose for field installation.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

6 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 9: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Speed ControllersPSCSC/WK Speed Controller Installation and Operation

Sample line string below:

FFU-HE/24/48/RSR/BC/PSC/115/10//NP//HEPA//PSCSC//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

If unit does not have the wall kit (WK) option, proceed to step 13a.

Sample line string below:

FFU-HE/24/48/RSR/BC/PSC/115/10//NP//HEPA//PSCSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 8A: Locate pre-installed electric box for wall-mounted speed controller.

STEP 9A: Wire speed controller according to wiring diagram found on page 57. Wall-mounted speed controller will be wired in series with the motor.

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 10A: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.

STEP 11A: Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.

Sample line string below: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 12A: If using RSR filter, refer to page 21 for installation instructions.

NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter.

STEP 13A: Ensure proper Voltage is hooked up, and turn unit on.

STEP 14A: Using a flow hood to determine airflow, adjust speed control switch until desired airflow is achieved.

NOTE: Clockwise rotation will increase airflow, counter-clockwise rotation will decrease airflow.

PSC Speed Controller with Wall Kit Option

7priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 10: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

NOTE: If unit is ducted, refer to Technical Note: Balancing Ducted Units on page 44 of this manual.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Speed Controller Adjustment

8 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 11: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

ECMSC/WK Speed Controller Installation and Operation

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC// WK /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

If unit does not have the wall kit (WK) option, proceed to step 13b.

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC// /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 8B: Locate pre-installed electrical box for wall-mounted speed controller.

STEP 9B: Wire speed controller according to wiring diagram found on page 58 and 59. Motor speed controller will have color coded wires and must be wired to the matching colors on the wall-mounted portion.

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 10B: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.

STEP 11B: Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.

Sample line string below: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 12B: If using RSR filter, refer to page 21 for installation instructions.

NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter

NOTE: Prior to turning on unit, ensure that the proper voltage is hooked up to the unit.

STEP 13B: Ensure proper Voltage is hooked up, and turn unit on.

STEP 14B: Attach a standard multimeter on a DC voltage setting to the positive and negative terminals (measurement tabs) on speed controller, located on the back of the unit (see arrows below for connection points).

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

ECMSC/WK

9priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 12: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 13B: Determine test point voltage (VDC) from the formula based on the desired airflow using the appropriate chart below.

BTR Filters with FC Wheel

24"x24" FFU-HE

Voltage Equation

115 VDC = (CFM+170)/169

240 VDC = (CFM+157)/159

277 VDC = (CFM+146)/166

24"x36" FFU-HE

Voltage Equation

115 VDC = (CFM+292)/244

240 VDC = (CFM+229)/231

277 VDC = (CFM+200)/222

24"x48" FFU-HE

Voltage Equation

115 VDC = (CFM+201)/250

240 VDC = (CFM+204)/252

277 VDC = (CFM+238)/262

RSR Filters with FC Wheel

24"x24" FFU-HE

Voltage Equation

115 VDC = (CFM+104)/100

240 VDC = CFM+104)/100

277 VDC = (CFM+74)/98

24"x36" FFU-HE

Voltage Equation

115 VDC = (CFM+179)/178

240 VDC = (CFM+179)/179

277 VDC = (CFM+172)/172

24"x48" FFU-HE

Voltage Equation

115 VDC = (CFM+235)/237

240 VDC = (CFM+255)/241

277 VDC = (CFM+219)/234

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

POTENTIOMETER(POT)

MEASURE (+) VDC MEASURE (-) VDC

ECMSC Speed Controller

VDC Equations

10 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 13: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Example: 24”x48”, FC Wheel, 115V @ 450cfm

VDC = (CFM + 201)/250

VDC = (450+201)/250

VDC = 2.60V

The potentiometer (POT/DIAL) would need to be turned up until the voltage measured 2.60 at the Measurement Tabs

NOTE: The calculated VDC value is intended as a starting point; actual VDC value may differ slightly depending on field variables.

NOTE: ECM Speed Controllers have 2 modes: manual adjust and BAS (Building Automation System). Standard manual control outputs are shown below:

Measurement Tab Voltage Motor Control

0 - 1 VDC Off

1 - 4.5 VDC 0-100%

4.5 - 5 VDC 100%

The speed controller will automatically ignore the potentiometer (POT/DIAL)/DIAL when a BAS signal is detected (BAS Input Signal >1). VDC equations are for potentiometer (POT/DIAL) manual adjustment only (0-1 BAS input signal). The VDC equations are based on a 1-5 Volt scale. The BAS input voltage is a 2-10 VDC scale, and therefore VDC calculated for a given CFM using the equation must be doubled to achieve that CFM using the BAS input.

BAS Voltage Response Notes

0 - 1 VDC Local control mode using push buttons Local setpoint can be adjusted from 0 - 100% using push buttons

1 - 2 VDC Motor Off Recommended sending a 1.5 VDC signal to command motor off

2 - 9 VDC Modulating Control 2 - 9 VDC modulates motor from 0 - 100%

9 - 10 VDC Maximum Speed Motor is running at maximum speed (100%)

STEP 14B: If using potentiometer/manual adjustment, rotate the potentiometer (POT/DIAL) dial on the outside of the box with a screwdriver until the test point voltage is achieved.

EXAMPLE: If using a BAS signal, to calculate appropriate starting voltage, first calculate the VDC (as shown in above example)

VDC = 2.60 V

Then double this value

BAS Input Voltage = VDC*2

BAS Input Voltage = 2.60*2

BAS Input Voltage = 5.20

11priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 14: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 15B: Wait a few seconds for the ECM motor to adjust its speed and then verify fan airflow with measurements at the unit face using a flow hood. Adjust the POT/DIAL, or BAS input signal to reach desired airflow as required.

NOTE: If unit is ducted, please refer to Technical Note: Balancing Ducted Units on page 44 of this manual.

POTENTIOMETER/DIAL ADJUST

GREEN STATUS LED MUST BE BLINKING. (CODE 1 THRU 4)

Speed Controller Adjustment

12 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 15: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

ECMDX/WK Speed Controller Installation and Operation

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX// WK /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

If unit does not have the wall kit (WK) option, proceed to step 11c.

NOTE: Sample line string below:

1//FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX// /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 8C: Locate pre-existing electrical box for wall-mounted speed controller.

NOTE: Wall kit must be mounted horizontally, as shown above.

STEP 9C: Wire unit according to wiring diagram found on page 58 and 60. Motor speed controller will have color coded wires and must be wired to the matching colors on the wall-mounted portion.

NOTE: 24VAC and COMMON will need to be run from the terminal block in the control box to the terminals listed 24VAC HOT, and COMMON on the wall-mounted portion.

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

ECMDX Wall Kit Speed Controller

ECMDX Speed Controller

13priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 16: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 10C: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.

STEP 11C: Wire the unit according to appropriate wiring diagram. Refer to table below for reference page number. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.

Sample line string below: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 12C: If using RSR filter, refer to page 21 for installation instructions.

NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter

STEP 13C: Wire unit according to wiring diagram found on page 58 and 60.

STEP 14C: Ensure proper Voltage is hooked up, and turn unit on.

NOTE: ECMDX Speed Controllers have multiple modes, which are listed below:

Display Mode Range

L.SEt Local Setpoint – Manual speed adjust mode (use UP / DOWN to adjust) 0 - 100%

rPnRPM – Shows current RPM of motor 1

If E001 – no RPM pulses are being read, check 6 position cable If E002 – RPM reading is above 2000 RPM, check primary air

0 - 2500 RPM

bAS.r BAS Remote – BAS Mode – Voltage signal (Max reading is 9.99 VDC) 0 - 9.99 VDC

bAS.S BAS Setpoint – Current BAS setpoint 0 - 100%

STEP 15C: Determine Local Setpoint from the formula based on the desired airflow using the appropriate chart below.

14 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 17: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

BTR Filters with FC Wheel

24"x24" FFU-HE

Voltage Equation

115 L. Set = (CFM/5.90)

240 L. Set = (CFM/5.58)

277 L. Set = (CFM/5.81) - 4

24"x36" FFU-HE

Voltage Equation

115 L. Set = (CFM/8.54) + 6

240 L. Set = (CFM/8.07)

277 L. Set = (CFM/7.75) - 3

24"x48" FFU-HE

Voltage Equation

115 L. Set = (CFM/8.77) - 6

240 L. Set = (CFM/8.82) - 5

277 L. Set = (CFM/9.16) - 1

RSR Filters with FC Wheel

24"x24" FFU-HE

Voltage Equation

115 L. Set =(CFM/3.52) + 1

240 L. Set = (CFM/3.49) + 1

277 L. Set = (CFM/3.41) - 7

24"x36" FFU-HE

Voltage Equation

115 L. Set = (CFM/6.23)

240 L. Set = (CFM/6.27)

277 L. Set = (CFM/6.03)

24"x48" FFU-HE

Voltage Equation

115 L. Set = (CFM/8.30)

240 L. Set = (CFM/8.43) + 2

277 L. Set = (CFM/8.20) - 2

STEP 16C: If manually adjusting at the speed controller ensure controller is in Local Setpoint mode (L.SEt). To change modes, press the up and down arrows simultaneously until you reach L.SEt.

STEP 17C: Enter the Local Setpoint value (L. Set) you have found from the chart by using the up/down buttons.

NOTE: The L.Set calculated above is a starting point; actual value may differ slightly depending on field variables.

NOTE: The BAS signal will override the local setpoint using a remote 0 – 10 VDC signal. If the BAS signal drops below 1 VDC local control (via the up/down buttons) is restored.

The ECMDX speed controller can be controlled using multiple strategies; these are outlined in the chart below.

BAS Voltage Response Notes

0 - 1 VDC Local control mode using push buttons Local setpoint can be adjusted from 0 - 100% using push buttons

1 - 2 VDC Motor Off Recommended sending a 1.5 VDC signal to command motor off

2 - 9 VDC Modulating Control 2 - 9 VDC modulates motor from 0 - 100%

9 - 10 VDC Maximum Speed Motor is running at maximum speed (100%)

The VDC equations are based on a 1-5 Volt scale. The BAS input voltage is a 2-10 VDC scale, and therefore VDC calculated for a given CFM using the equations (refer to ECM speed controller on page 10) must be doubled to achieve that CFM using the BAS input.

STEP 18C: Wait a few seconds for the ECM motor to adjust its speed and then verify fan airflow with measurements at the supply outlets using a flow hood. Adjust voltage to reach desired airflow as required.

NOTE: If unit is ducted, please refer to Technical Note: Balancing Ducted Units on page 44 of this manual.

15priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 18: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

BACnet Flow Controller (BFC) Installation and Operation

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//BFC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 8D: Wire unit according to wiring diagram found on page 59 and 60.

NOTE: Polarity is important and must be observed. It is also vital that the 24 VAC common side of the transformer be Earth grounded.

STEP 9D: Hook up applicable BACnet, and/or local Building Automation System (BAS) according to wiring diagram found on page 59 and 60. 'For multiple units, use provided able to daisy chain units together. If using BAS or Local Setpoint, skip to step 14D (formerly 12G) for applicable reference instructions.

Create render of FFU-HE's daisy chained together and insert after this step

NOTE: For additional information on BACnet, and the BFC controller, refer to the BACnet Wiring Guidelines, and BFC Manual which are available on the Price website (priceindustries.com).

STEP 10D: Wire the unit according to appropriate wiring diagram. Refer to table below for reference page number. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.

Sample line string below: FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

STEP 11D: If using RSR filter, refer to page 21 for installation instructions.

NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter

STEP 12D: Ensure proper Voltage is hooked up, and turn unit on.

STEP 13D: Configure BACnet addressing (if applicable).

STEP 14D: Using the desired method of control (local, BAS, or BACnet) set unit airflow.

• Local Setpoint:

- Refer to page 15 for the ECMDX Speed Controller instructions for calculating Local Setpoint value.

- Hold down ‘Enter/Menu’ button for 5 seconds, display will show ‘Passcode”. Use the ‘Up’ and ‘Down’ arrow keys to enter this sequence: Down, Up, Up, Down.

- Use ‘Up’ and ‘Down’ arrow keys to manually enter Local Setpoint value; numbers will be displayed on LCD screen.

• BAS:

- Refer to page 10 for the ECM Speed Controller instructions for calculating VDC.

• BACnet:

- Log into Building Management System, or Price supplied BFC-FE front end.

- Calculate Local Setpoint value using the equations on page 15 from the ECMDX instructions.

- Write this value into ECM Setpoint BACnet point.

16 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 19: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 15D: Check airflow using flow hood and adjust ECM Setpoint as required until desired airflow is reached.

NOTE: Before proceeding to next step, ensure unit is operating at desired airflow. Any changes to the airflow will require the filter status to be reset.

STEP 16D: To calibrate clean filter pressure drop, scroll, scroll through the ‘Service Menus’ until reaching ‘Filter’, select this menu by pressing the ‘Enter/Menu’ button (far right).

STEP 17D: Scroll through the ‘Filter’ menu until reaching ‘Reset Filter’ select by pressing the ‘Enter/Menu’ button.

Price FFU-HE-FE Points List

17priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 20: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

NOTE: Make sure the area directly beneath and around the unit is clear of any personnel or equipment as this can affect the reading of the clean filter static pressure.

STEP 18D: Press the ‘Enter/Menu’ button to confirm reset of filter; this will begin calibration. This will take approximately 2 minutes

After filter calibration is complete, LCD will display: ‘RESET COMPLETED’.

NOTE: If unit is ducted, please refer to Technical Note: Balancing Ducted Units on page 44 of this manual.

Calibration Screen

Filter Reset Screen

18 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 21: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

ATS PORT

KNIFE EDGE

STATIC PRESSURE PORT DIFFUSER FACE

FRAME

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Optional AccessoriesATS

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 1: If unit has room side removable filter (RSR), remove diffusers perforated face by turning quarter turn fasteners holding face in place.

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.

If unit is bench top removable (BTR), proceed to next step.

STEP 2: Remove threaded plug covering ATS port using a 5/16” hex screw driver.

Unit Port Locations

19priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 22: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 3: Insert aerosol test fitting or adaptor (the aerosol injection port has a 3/8” NPT internal thread) into ATS test port.

NOTE: An adaptor/test fitting that is longer than 1.5” and/or wider than 1” will not fit.

STEP 4: Inject aerosol test agent and measure particulate counts according to local codes.

NOTE: Static pressure port can be used to measure upstream particle counts. Refer to page 41 for static pressure port details.

STEP 5: Disconnect test equipment, and reinstall plugs in the static pressure (if applicable) and aerosol injection ports. Reinstall diffuser face (if applicable).

If the safety cables were also disconnected when removing the face, they must be reattached. When reinstalling the face, care should be taken to tuck safety cables in place without damaging the filter.

NOTE: Airflow and aerosol challenge concentration should be kept uniform during the test. Static pressure and concentration may be sampled through the static pressure port during the test, if required, to verify flow and concentration.

The following table outlines a few possible problems that may be encountered during leakage testing. This chart is intended as a quick troubleshooting guide, and is not exhaustive. All local and applicable codes should be followed.

Problem Possible Cause Solution

Leakage at the perimeter of the filter

Improper filter installationGently remove the filter, verify that the gel seal is intact and undam-aged, and carefully reseat the filter in the knife edge frame and latch in place.

Pinhole leaks detected in filterImproper handling of filter/dam-age during installation

Filter may be repaired by a trained technician.

Leakage at the perimeter of the fan filter unit

Improper seal between unit and ceiling plenum

Check seal between unit and ceiling plenum and seal as required.

Particle Counter is beeping at multiple locations, even away from filter face

Possible leakage through ad-jacent lights, diffusers, and/or ceiling panels

Isolate unit by placing cardboard or sheet metal to create vertical 'walls' extending 2ft below the ceiling plane. If filter passes, sealing of adjacent lights, diffusers, and/or ceiling panels may be required.

priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual20 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 23: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Unit Filter Installation Room Side Replaceable Filter (RSR)

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty.

STEP 2

STEP 4

STEP 1

STEP 3

Remove filter from box using handles Place unit on flat surface or table.

Cut plastic bag and remove filter with care. To handle the filter, grasp by the frame only.

21priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manualpriceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 24: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 7

STEP 5

STEP 6

STEP 8

Loosen cam locks on diffuser to prepare filter for installation. Be sure latches are turned inwards so as not to interfere with filter frame.

NOTE: Note location of filter alignment guides (minimum one per side, dependent on size).

Raise the filter in place using two people and being careful not to contact the filter media.

Secure filter in place using the cam locks. Tighten until no further rotations can be made. No tools are required to tighten, and using one may cause damage to filter gel seal.

Ensure HEPA filter outer frame is in contact with horizontal knife edge of frame. Note that diffuser knife edge cannot bottom out in HEPA filter gel seal.

Using the alignment guides, raise the filter into place, ensuring filter gel seal channel seat into knife edge of plenum.

NOTE: Do not bottom out gel seal in plenum knife edge. The gel seal needs to ‘float’ in gel seal to ensure proper seal.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

FILTER MEDIA

GEL SEAL

CONTACT POINT

CAM LOCK

HEPA FILTER OUTER FRAME

KNIFE EDGE

22 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 25: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Unit Filter Installation Bench Top Replaceable Filter (BTR)

Sample line string below:

FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//

NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty.

NOTE: If ordered with Filter, or Motor LED Indicator (ML/FL), refer to LED installation instructions which must be done at same time as filter installation.

FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//

STEP 2 STEP 1

Place filter box on floor, careful to set box in correct orientation, as per the arrow.

Remove filter from box being careful not to touch filter media.

STEP 4 STEP 3

Place the filter gently on the floor, remove the tape, and take the filter out of the bag.

Place filter on a flat, clean, protecting surface with the expanded face screen on the bottom. Make sure to protect face LED if this has been selected as an option.

23priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 26: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 6 STEP 5

Place FFU-HE top cap assembly onto filter’s gasketed flange/frame, being careful to not damage the filter media.

Attach filter to top cap assembly by hooking and securing latches. Gasket may need to be compressed to grab channel with latch.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

24 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 27: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Filter/Motor Indicator LED (ML/FL) – RSRSample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

LED Operation

Option CodeLED

ColorAction Notes

Filter LED FLGreen None Indicates normal operation until filter pressure drop exceeds calibrat-

ed pressure drop (factory set at 1.5x clean filter pressure).

Yellow Change FilterIndicates filter pressure drop has exceeded calbirated setting (factory set at 1.5x clean filter pressure.

Motor LED

MLGreen None

Indicates normal motor operation when the static pressure is above 0.2" w.g.

Red Troubleshoot Motor Indicates motor is not in operation, and that unit static pressure is below 0.2" w.g.

Calibration

Filter LED will come factory set to activate at the pressure drops listed in the Table below.

Filter Pressure @ 90fpm [in w.g.] 1.5x Clean Filter [in w.g.]

HEPA 0.4 0.6

ULPA 0.6 0.9

If different set points are desired, they can be adjusted as follows:

STEP 1: Remove Loctite from adjustment screw hole.

Filter Indicator Set Points

Pressure Switch Adjustment

25priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 28: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

Set P

oint

in In

ches

w.g

.

Turns of Set Point Adjustment Screw(from starting point at 0.25” w.g.)

1.00

0.90

0.80

0.70

0.60

0.50

0.40

0.30

0.20

0.10

0.00

Table 3. Set Point Adjustment

Turns of Set Point Adjustment Screw(from starting point at 0.25” w.g.)

Set P

oin

t in

in

ch

es w

.g.

0 1 2 3 4 5

1.000.900.800.700.600.500.400.300.200.100.00

0 1 2 3 4 5

STEP 2: Calculate number of turns required based on difference between factory set point and desired set point using the following chart.

Example:

HEPA filter with desired set point of 0.9 in w.g.

Number of turns at 0.9 in w.g. = 4

Number of turns at factory set point of 0.6 in w.g. = 2.2

Number of turns to field set = 4 – 2.2 = 1.8 (approximately)

NOTE: Maximum available pressure setting is 1.0” w.g. Do not exceed 4 ½ turns (total). – Necessary

STEP 3: Turn screw clockwise the number of turns calculated above. You will need a 1.5mm hex Allen wrench

STEP 4: To check filter pressure set point and/or to fine tune, insert Magnehelic gauge into the static pressure port (located along knife edge of diffuser – diffuser face must be removed to access).

STEP 5: Using an obstruction (piece of cardboard or equivalent), slowly increasing pressure on the unit by blocking off more and more of the diffuser face until the LED turns from green to yellow.

STEP 6: Take pressure measurement at point the LED changed color and rotate the adjustment screw until desired pressure set point is reached.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

26 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 29: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Filter/Motor Indicator LED (FL/ML) – BTRSample line string below:

FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//

LED Operation

Option CodeLED

ColorAction Notes

Filter LED FLGreen None Indicates normal operation until filter pressure drop exceeds calibrat-

ed pressure drop (factory set at 1.5x clean filter pressure).

Yellow Change FilterIndicates filter pressure drop has exceeded calbirated setting (factory set at 1.5x clean filter pressure.

Motor LED

MLGreen None

Indicates normal motor operation when the static pressure is above 0.2" w.g.

Red Troubleshoot Motor Indicates motor is not in operation, and that unit static pressure is below 0.2" w.g.

Installation

STEP 1: Remove BTR filter from box by following the instructions found on page 23 of this installation manual.

STEP 2: Take LED cable assembly out of FFU-HE Plenum

Cable Assembly

27priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 30: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Remove Well Nut on Static Presure Port

Remove Threaded Standoff

STEP 3: Remove well nut in center port of BTR filter.

STEP 4: Remove threaded standoff and lock washer from LED cable assembly

THREADED STANDOFF

LOCK WASHER

RUBBER WASHER

METAL WASHER

LED

28 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 31: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 5: Thread cable through static pressure port on face of BTR filter

NOTE: It is recommended to rest the filter frame on 2x4 lumber to protect the LED light from breaking

STEP 6: Put lock washer and threaded standoff back on cable and tighten to LED.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Installed LED on Filter Face

Filter Resting on Lumber

Threaded Standoff through Filter Channel

29priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 32: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

Cable Assembly

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 7: With two (2) people holding the unit, pull cable back through plenum until plenum can rest on top of filter.

STEP 8: Refer to BTR Filter Instructions found on page 23 for proper filter installation.

STEP 9: Refer to wiring diagram (located in control box) to connect LED leads to terminal block.

NOTE: If unit has BFC speed controller, LED leads will need to be connected to the BFC controller instead of the terminal block.

Calibration

Refer to page 18 for filter calibration.

30 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 33: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

MBAS/FBAS Pressure Switch Diagram

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Motor/Filter Indicator BAS (MBAS/FBAS)Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/MBAS/FBAS/WPF/PL-AL/F-AL/PL-B12/F-B12

Operation

Option Code Action Notes

Motor BAS MBASTroubleshoot

MotorCloses a dry contact to let the BAS signal pass through when the static pressure is less than 0.2" w.g. indicating the motor is not operating.

Filter BAS FBASChange

Filter

Closes a dry contact to let the BAS signal pass through when the static pressure is greater than the calibrated pressure drop (factory set at 1.5x clean filter).

Unit will come factory calibrated; no additional field modifications are required.

Wire unit terminal block according to wiring diagrams found starting on page 51 of this manual.

NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.

FFU-HE

Pressure switch(es) completes signal when failure is reached (as per chart above)

BAS Signal In

31priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 34: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Service: Cleaning of Pre-filterNOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.

NOTE: When performing any type of maintenance on the FFU be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt, dust, and debris that may be present in the unit’s external environment.

STEP 1: Gain access to the top of the unit by removing adjacent ceiling, or access panel.

STEP 2: Bend up pre-filter retaining clips and remove the pre-filter (non-ducted), or remove filter access door (ducted). Reference the below figures for further details.

Non-Ducted Unit

Removal of Pre-filter

Ducted Unit

STEP 3: Clean pre-filter by hand washing in water with a mild detergent or by using a vacuum cleaner. Allow pre-filter to dry completely before replacing.

STEP 4: Reverse above steps to install the pre-filter.

32 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 35: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Service: Removal and Replacement of RSR FiltersReplacement filters can be ordered through your local Sales Representative. Visit the Price Ind. Website to find yours (http://www.priceindustries.com/contact/reps-dealers).

STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.

NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.

STEP 2: Remove filter by loosening cam latch bolts (filter retainer clips) by turning counter clockwise using your hands.

STEP 3: Turn all cam latch filter retainers to the open position

STEP 4: Remove filter by handling frame; do not touch filter media if re-using filter.

NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.

STEP 5: Follow the step on page 21, Installation of RSR Filters to install new filter.

Remove Diffuser Face with Quarter Turn Fasteners

Loosen Cam Latch Bolts

33priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 36: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Service: Removal and Replacement of BTR FiltersReplacement filters can be ordered through your local Sales Representative. Visit the Price Ind. Website to find yours (http://www.priceindustries.com/contact/reps-dealers).

STEP 1: Remove unit from ceiling, gently placing FFU-HE on a clean, dry surface.

NOTE: If the FL or ML filter option has been selected, It is recommended to rest the filter frame on 2x4 lumber to protect the LED light.

STEP 2: Unhook latches attaching bench top replaceable filter to fan filter body.

STEP 3: Remove filter by handling frame; do not touch filter media if re-using filter.

NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.

STEP 4: For installation of new filter, follow steps on page 23.

Unhook Latches

34 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 37: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Service: Changing Motors in the FieldTop Access Motor/Blower Assembly

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/MBAS/FBAS/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.

NOTE: When performing any type of maintenance on the FFU-HE, be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt, dust, and debris that may be present in the unit’s external environment.

STEP 1: Gain access to the top of the unit by removing adjacent ceiling, or access panel.

STEP 2: Bend up pre-filter retaining clips and remove the pre-filter (non-ducted), or remove the duct collar/pre-filter housing and pre-filter (if applicable) via screws (ducted) to expose motor assembly. Reference the below figures for further detail.

Pre-filter Retaining Clips – Non-Ducted

Remove Duct Collar Remove Pre-Filter

35priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 38: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Remove Diffuser Face with Quarter Turn Fasteners

STEP 3: Make note of all wire locations for re-installation later. It is recommended to take a picture of all applicable wires.

STEP 4: Open control box and disconnect wires at the terminal block, referencing applicable wiring diagram.

STEP 5: Remove the 6 bolts to free the motor/blower assembly, using a 7/16” socket wrench (or equivalent).

STEP 6: Remove motor/blower assembly.

STEP 7: Inspect and/or replace parts.

STEP 8: Replace with the new motor/blower assembly and reassemble by reversing the above steps.

NOTE: For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price’s website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.

STEP 9: Double check airflow to ensure that set point hasn’t changed. applicable speed controller found on pages X-X

36 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 39: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Room Side Accessible Motor/Blower Assembly

NOTE: Sample line string below:

1//FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/RMB/ATS/MBAS/FBAS/WPF/PL-AL/F-AL/PL-B12/F-B12

NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.

NOTE: When performing any type of maintenance on the FFU be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt, dust, and debris that may be present in the unit’s external environment.

STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.

NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.

STEP 2: Remove filter by loosening cam latch bolts (filter retainer clips) by turning counter clockwise using your hands, or hex key as required to fully tighten latches.

Remove Diffuser Face with Quarter Turn Fasteners

Loosen Cam Latch Bolts

37priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 40: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 3: Turn all cam latch filter retainers to the open position

STEP 4: Remove filter by handling frame; do not touch filter media.

NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.

STEP 5: Remove the nuts securing the blower housing using a 7/16” socket wrench (or equivalent).

NOTE: A 7/16” ratchet with extension is recommended for ease of access for unfastening.

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

2x2 FC Blower Housing

BC Wheel Housing

2x3 and 2x4 FC Blower Housing

NUTS LOCATED ON TOP OF BLOWER HOUSING

NUTS LOCATED ON SIDE OF BLOWER HOUSING

38 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 41: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

STEP 6: Remove the housing exposing the motor/blower assembly.

STEP 7: Remove 7/16” nuts holding motor/blower assembly in place.

STEP 8: Drop motor/blower assembly out of unit. Be careful as wire connection are still in place.

STEP 9: Disconnect plug and play connection connecting wires from motor to control box.

Removal of 2x2 Motor/Blower Housing

Removal of Motor/Blower Housing

39priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 42: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

STEP 10: Full remove motor/blower assembly.

STEP 11: Inspect and/or replace parts.

STEP 12: Replace with the new motor/blower assembly and reassemble by reversing the above steps.

STEP 13: Double check airflow to ensure that set point hasn’t changed. applicable speed controller found on pages X-X

NOTE: For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price’s website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.

Plug and Play Connections

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

40 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 43: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Technical Note: Static Pressure PortsRoom Side Replaceable (RSR) Port

Sample line string below:

FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12

STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.

NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.

Step 2: Remove gasketed bolt

STEP 3: Insert pressure measuring gauge (eg. Magnehelic) to read pressure drop across filter. Hole size is 5/16”.

NOTE: Static Pressure Port can also be used as a test port for sample aerosol concentrations upstream of the filter.

Remove Diffuser Face with Quarter Turn Fasteners

Static Pressure Port

41priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 44: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Static Pressure Port

Bench Top Replaceable (BTR) Port

NOTE: Sample line string below:

1//FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//

NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.

STEP 1: Remove gasketed bolt located along center channel of BTR filter. There are two ports located on the face; either can be used.

STEP 3: Insert pressure measuring gauge (eg. Magnehelic) to read pressure drop across filter. Hole size is 5/16”.

NOTE: Static Pressure Port can also be used as a test port for sample aerosol concentrations upstream of the filter.

42 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 45: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Technical Note: Design with VAV/Constant Flow Boxes and Ducted ApplicationsIn applications where the fan filter unit will be ducted with upstream VAV, constant flow boxes, valves, or other airflow devices that may have varying airflows, or modes, caution must be taken with balancing and proper selection of fan filter unit.

A constant flow program is not recommended for this type of application. In systems where two controllers are trying to compensate to adjust to a constant airflow, the system will be unable to stabilize. This results in constant adjustment of both controllers until the FFU-HE motor shuts off. The ECM with constant torque motor program or PSC motor is suggested for this type of application.

The FFU-HE is designed to overcome the pressure drop of the filter only. The motor is not intended to pull air down supply ductwork, nor to experience a positive static pressure at the inlet forcing air through the fan. These scenarios will cause starving, or overfeeding of the fan which can damage the fan motor. Fan filter units should be installed in a system where the inlet static will be 0.0” w.g., or slightly negative.

In ducted applications, it is critical that primary air be balanced prior to installing the FFU-HE. The primary air controls should be locked in position post balancing, and the FFU-HE is installed and running. Similarly, the FFU-HE should be bench-set by using a flow hood and adjusting the speed controller, as required, to the same balanced, primary airflow rate before the FFU-HE is mated with the duct. Alternatively, the Balancing Ducted Units Technical Note can also be followed on page 44 of this manual.

To prevent a high static pressure build up at the FFU-HE during start up, the FFU-HE’s should be energized prior to the system. This helps to prevent the possibility of backwards rotations of the blower wheel, which will eventually lead to the motor shutting off.

Excessive negative static air pressure at the inlet is also not an intended use for fan filter units. Negative static at the inlet will cause the motor to be overworked and will lead to decreased motor life. Additionally, inconsistent motor running modes may result, depending on the magnitude of the negative pressure. Positive static inlet pressure will eventually lead to ECM motors shutting off entirely, and PSC motors running inconsistently. The discharge static pressure of the VAV, constant flow boxes, valves, other airflow devices, or balancing damper feeding the FFU-HE should be as close to 0.0” w.g. as possible.

For any additional information, or troubleshooting assistance on systems and design with fan filter units used in sequence with a variable upstream air source, contact Price Industries Fan Filter help at [email protected], or dial (204) 654-5613 option 5.

43priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 46: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Technical Note: Balancing Ducted UnitsSTEP 1: Set FFU on benchtop and balance to desired flow using appropriate speed controller set up (Pages X-X).

STEP 2: Confirm airflow using flow hood and adjust speed controller as required.

STEP 3: Lock primary air control

STEP 4: Install FFU into ceiling grid

STEP 5: Turn FFU’s on – ensuring all FFUs on the same system are turned on at the same time.

STEP 5: Unlock primary air control

STEP 6: Measure discharge static pressure at VAV discharge or FFU inlet.

STEP 7: If measured pressure is greater than 0.0” w.g., turn up the FFU in small increments while monitoring the measured pressure. Increment until pressure approaches 0.0” w.g. Similarly, if measured pressure is negative, turn down the FFU in small increments, monitoring the measured pressure until it approaches 0.0” w.g.

NOTE: A slightly negative static pressure is also acceptable.

NOTE: Not recommended for FFU-HE units with ECM units with constant airflow program.

If removing the FFU-HE from the duct is not possible, follow the below instructions for balancing:

STEP 1: Install an air pressure measurement device (i.e. Pitot tube) in the inlet of the FFU-HE.

STEP 2: Power up FFU-HE and set the speed controller to approximately 75% of maximum set point.

STEP 3: Power upstream airflow control device, and set airflow to the FFU-HE to 25% less than design flow.

STEP 4: Read the inlet pressure.

STEP 5: Measure airflow using flow hood

STEP 6: Using the table below, adjust FFU-HE controller, or upstream airflow device as required

FFU Airflow FFU Inlet Static Action

Above Set point Above 0'' W.G. Lower airflow on airflow control device

Above Set point Below 0'' W.G. Lower FFU control setting

Above Set point 0'' W.G. Lower Both FFU and airflow control device

Below Set point 0'' W.G. Raise Both FFU and airflow control device

Below Set point Below 0'' W.G. Raise airflow on airflow control device

Below Set point Above 0'' W.G. Raise FFU control setting

STEP 7: Repeat steps 4-6 unit design airflow is achieved and inlet pressure is neutral (0.0” w.g.).

44 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 47: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Troubleshooting Tips:• If FFU is turned to 75% and it shut offs after a short time, follow the below steps:

1. Power cycle the FFU-HE.

2. Measure inlet static while the FFU-HE is running.

3. If the inlet static is positive, reduce your airflow device airflow an additional 25%.

4. Return to Step 4, above and finish balancing unit.

• If the unit shuts off still at this 50% setpoint, follow the below steps:

1. Power cycle the FFU-HE

2. Measure inlet static while the FFU-HE is running

3. If the inlet static is positive, reduce your airflow device airflow 25% more.

4. Return to Step 4, above and finish balancing unit.

If experiencing further issues with unit, contact Price Industries Fan Filter help at:

By Email: [email protected]

By Phone: (204) 654-5613 option 5

Low Air Velocity

1. Check prefilter media (only with optional prefilter); replace or clean as necessary.

2. Adjust variable speed control for higher blower output.

3. Check power for proper voltage, amerage, and distribution frequency.

4. Replace HEPA/ULPA filter if the veloicty remains low.

High Air Velocity 1. Adjust variable speed control for lower blower output.

Non-Laminar Flow and/or Excessive Contamination

1. Ensure that no large obstructions are upstream of airlfow pattern.

2. Determine that no other air-moving devices are operating in or around cleanroom which could disrput the room's airlfow pattern.

3. Check air velocity and if low, conduct the 'Low Air Velocity' procedure outlined above.

4. Conduct somke and photometer test on HEPA/ULPA filter. Seal or replace.

Motor Keeps Shutting Off

1. Check if unit is ducted.

2. If no, contact Price at [email protected].

3. If yes, check inlet pressure, if postive, re-balance until inlet pressure is zero.

LED Light Turned Red 1. Refer to 'Motor Will Not Run' procedure outlined below.

LED light Turned Yellow 1. Replace filter.

Motor Will Not Run1. Check that motor has power at correct voltage.

2. Check that the speed controller has power.

45priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 48: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

BTR HEPA

Size Quantity Description Price Part Number2x2 1 Filter, HEPA, 99.99% FFU-HE 24 x 24 x 3.06" 042299-0112x3 1 Filter, HEPA, 99.99% FFU-HE 24 x 36 x 3.06" 042299-0122x4 1 Filter, HEPA, 99.99% FFU-HE 24x 48 x 3.06" 042299-013

ULPA

Size Quantity Description Price Part Number2x2 1 Filter, HEPA, 99.99% FFU-HE 24 x 24 x 2.5" 042299-0142x3 1 Filter, ULPA, 99.99% FFU-HE 24 x 36 x 2.5" 042299-0152x4 1 Filter, ULPA, 99.99% FFU-HE 24 x 48 x 2.5" 042299-016

Parts Quantity Description Price Part NumberPrefilter 1 Foam Filter 16x20x.437 045964-001Prefilter 1 Foam Filter 20x20x.437 045964-002

Speed Controller 1 USC 8A speed control 232953-100ECM Speed Controller Cable 1 Cable ECM Speed Control 2ft 019186-001ECM WK Speed Controller 1 Wall Mounted Speed Controller 232953-300

ECM WK Remote Speed Controller 1 Wall Mounted Remote for ECM Speed Controller 232953-350

ECMDX WK Speed Controller 1Deluxe Wall Mounted Speed Control for ECM Motor

232953-400

ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186-006ECMDX Wall Cable 1 ECMDX/BFC Speed Control, 2 ft 019186-004ECM Power Cable 1 Power Cable Harness 115V - 0191487-003

240V/277V - 019187-004

Transformer Quantity Description Price Part Number115V 1 Transformer 120/24 50VA FT-MT 019436-001

208-240V 1 Transformer (208/240V)/24V 50VA FT-MT 019436-011277V 1 Transformer 277/24V 50VA FT-MT 019439-001

Blower Wheel Quantity Description Price Part Number2x2 1 WHL 1/2 Bore w/ REV Hub 100080-001

2x3, 2x4 1 WHL 1/2 (FC) 100090-0022x3, 2x4 1 WHL 1/2 (BC) 100090-003

Disconnect Switch Disconnect Switch 15A 019903-001

PSC MotorSize Wheel Type 115 208-240 2772x2 FC 019584-001 019584-002 019584-003

2x3FC 019584-008 019584-007 019584-003BC 019584-001 019584-002 019584-003

2x4FC 019584-008 019584-007 019584-003BC 019584-001 019584-002 019584-003

ECM Motor

Size Quantity Description Price Part Number2x4, 2x3, 2x2 1 277V - ECM Eon Motor 1/3 HP 019173-0082x4, 2x3, 2x2 1 115V/240V - ECM Eon Motor 1/3 HP 019173-007

46 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 49: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

RSR HEPA

Size Quantity Description Price Part Number2x2 1 Filter, HEPA, 99.99% FFU-HE 24 x 24 x 3.5" 042299-0052x3 1 Filter, HEPA, 99.99% FFU-HE 24 x 36 x 3.5" 042299-0062x4 1 Filter, HEPA, 99.99% FFU-HE 24 x 48 x 3.5" 042299-007

ULPA

Size Quantity Description Price Part Number2x2 1 Filter, ULPA, 99.99% FFU-HE 24 x 24 x 3.5" 042299-0082x3 1 Filter, ULPA, 99.99% FFU-HE 24 x 36 x 3.5" 042299-0092x4 1 Filter, ULPA, 99.99% FFU-HE 24 x 48 x 3.5" 042299-010

Parts Quantity Description Price Part NumberPrefilter 1 Foam Filter 16x20x.437 045964-001Prefilter 1 Foam Filter 20x20x.437 045964-002

Speed Controller 1 USC 8A speed control 232953-100ECM Speed Controller Cable 1 Cable ECM Speed Control 2ft 019186-001ECM WK Speed Controller 1 Wall Mounted Speed Controller 232953-300

ECM WK Remote Speed Controller 1 Wall Mounted Remote for ECM Speed Controller 232953-350

ECMDX WK Speed Controller 1Deluxe Wall Mounted Speed Control for ECM Motor

232953-400

ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186-006ECMDX Wall Cable 1 ECMDX/BFC Speed Control, 2 ft 019186-004ECM Power Cable 1 Power Cable Harness 115V - 0191487-003

240V/277V - 019187-004

Transformer Quantity Description Price Part Number115V 1 Transformer 120/24 50VA FT-MT 019436-001

208-240V 1 Transformer (208/240V)/24V 50VA FT-MT 019436-011277V 1 Transformer 277/24V 50VA FT-MT 019439-001

Blower Wheel Quantity Description Price Part Number2x2 1 WHL 1/2 Bore w/ REV Hub 100080-001

2x3, 2x4 1 WHL 1/2 (FC) 100090-0022x3, 2x4 1 WHL 1/2 (BC) 100090-003

Disconnect Switch Disconnect Switch 15A 019903-001

PSC MotorSize Wheel Type 115 208-240 2772x2 FC 019584-001 019584-002 019584-003

2x3FC 019584-008 019584-007 019584-003BC 019584-001 019584-002 019584-003

2x4FC 019584-008 019584-007 019584-003BC 019584-001 019584-002 019584-003

ECM Motor

Size Quantity Description Price Part Number2x4, 2x3, 2x2 1 277V - ECM Eon Motor 1/3 HP 019173-0082x4, 2x3, 2x2 1 115V/240V - ECM Eon Motor 1/3 HP 019173-007

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

47priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 50: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

Reference ManualsBACnet Wiring Guidelines

Deluxe ECM Speed Controller

ECM Motor Troubleshooting Manual

BFC Speed Controller

NOTE: Above manuals can be found on the Price Industries website at priceindustries.com.

priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual48 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 51: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

FFU-HE Ordering Procedure1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 // 12 // 14 // 16 // 18 // 20 // 22 // 24 // 26 // 28 / 29 // 31 / 32 / 33 // 35 / 36

Qua

ntity

Type

FFU

-HE

Nom

inal

Wid

th

Nom

inal

Len

gth

Filte

r S

tyle

Whe

el T

ype

Mot

or T

ype

Mot

or V

olta

ge

Inle

t Siz

e

Mot

or P

rogr

am

Filte

r Ty

pe

Spe

ed C

ontr

ol

Wal

l Kit

Dis

conn

ect

Pow

er C

ord

Mot

or/B

low

er A

cces

sA

eros

ol T

est S

yste

m

Mot

or S

tatu

s

Filte

r S

tatu

s

Pre

filte

r

Ple

num

Con

stru

ctio

n

Face

Con

stru

ctio

n

Ple

num

Fin

ish

Face

Fin

ish

Type (2)= Standard Unit

S = Special Unit

Nominal Width (4)24"

Nominal Length (5)24"36"48"

Filter Style (6)

BTR =Bench Top Replaceable Filter

RSR =Room Side Replaceable Filter

Wheel Type (7)FC = Forward Curved WheelBC = Backward Curved Wheel

Motor Type (8)ECM = ECM MotorPSC = PSC Motor

Motor Voltage (9)115 = 115V Motor208 = 208V Motor240 = 240V Motor277 = 277V Motor

Inlet Size (10)10 = 10" Round Duct Collar12 = 12" Round Duct Collar

16x20 = 16"x20" Rectangular Collar

Motor Program (12)NP = Not Programmable

CF =Constant Flow ECM Pro-gram

CT =Constant Torque ECM Program

Filter Type (14)

HEPA =High Efficiency (99.99% 0.30 Microns) Particulate Air

ULPA =Ultra Low (99.9995% 0.12 Microns Penetration Air

Speed Control (16)PSCSC = PSC Speed Controller

ECMSC =ECM Standard Speed Controller

ECMDX =ECM Deluxe Speed Control-ler

BFC = BACnet Flow Controller

Wall Kit (18)= None

WK =Wall Mounted Speed Controller

Disonnect (20)= None

DSW = Disconnect Switch

Power Cord (22)= None

PC = Power Cord

Power Cord (22)= None

PC = Power Cord

Motor/Blower Access (24)

TMB =Top Access Motor/Blower Assembly

RMB =Room Side Accessible Mo-tor/Blower Assembly

Aerosol Test System (26)= None

ATS = Aerosol Test System

Motor Status (28)= None

ML = Motor Status LEDMBAS = Motor Status BAS SignalML+

MBAS =Motor Status LED and Motor Status BAS Signal

MBAC = Motor Status over BACnetML+

MBAC =Motor Status LED and Motor Status over BACnet

Filter Status (30)= None

FL = Filter Status LEDFBAS = Filter Status BAS Signal

FL+ FBAS =Filter Status LED and Filter Status BAS Signal

FBAC = Filter Status over BACnet

FL+ FBAC =Filter Status LED and Filter Status over BACnet

Prefilter (31)= None

WPF = Washable Prefilter

WPFH =Washable Prefilter with Side Acces Filter Housing

Plenum Construction (32)PL-AL = Aluminum PlenumPL-SS = Stainless Steel Plenum

WPFH =Washable Prefilter with Side Acces Filter Housing

Face Construction (33)

=Expanded Metal Grille, Painted

F-AL = Aluminum FaceF-SS = Stainless Steel Face

Plenum Finish (35)PL-MILL = Aluminum MILL finishPL-B12 = White Powder CoatPL-B25 = Baked Enamel to MatchPL-2B = 2B Stainless Steel

Face Finish (36)

=Expanded Metal Grille, Painted

F-MILL = Aluminum MILL FinishF-B12 = White Powder CoatF-B25 = Baked Enamel to MatchF-#4 = #4 Stainless Steel

49priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manualpriceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 52: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - FILTER LOADING

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING

50 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 53: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE - FILTER BAS

WIRING DIAGRAM - FFU-HE - MOTOR BAS

51priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 54: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING / FILTER LOADING

WIRING DIAGRAM - FFU-HE LED - FILTER LOADING + FILTER BAS

52 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 55: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - MOTOR BAS + FILTER LOADING

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING + FILTER BAS

53priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 56: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING + MOTOR BAS

WIRING DIAGRAM - FFU-HE - MOTOR BAS / FILTER BAS

54 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 57: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING / FILTER LOADING + FILTER BAS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING / FILTER LOADING + MOTOR BAS

55priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 58: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING / FILTER LOADING + MOTOR BAS / FILTER BAS

WIRING DIAGRAM - FFU-HE LED - MOTOR LOADING / FILTER LOADING + MOTOR BAC / FILTER BAC

56 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 59: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU - 115/277V, 1ø PSC/STANDARD MOTOR

WIRING DIAGRAM - FFU - 208/240V, 1ø MOTOR/STANDARD/PSC

57priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 60: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE - 115/277V 1ø ECM MOTOR STANDARD ECM SPEED CONTROL ECMSC

WIRING DIAGRAM - FFU-HE - 115/277V 1ø ECM MOTOR DELUXE ECM SPEED CONTROL ECMDX

58 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 61: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE - 115/277V 1ø ECM MOTOR BACNET FLOW CONTROL BFC

WIRING DIAGRAM - FFU-HE - 240VV 1ø ECM MOTOR STANDARD ECM SPEED CONTROL ECMSC

59priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual

Page 62: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WIRING DIAGRAM - FFU-HE - 240VV 1ø ECM MOTOR DELUXE ECM SPEED CONTROLLER ECMDX

WIRING DIAGRAM - FFU-HE - 240VV 1ø ECM MOTOR BACNET FLOW CONRTOLLER BFC

priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual60 priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - ManualFAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com

Page 63: Fan Filter Unit - High Efficiency - Price Industries · FAN FILTER UNIT - HIGH EFFICIENCY PRODUCT OVERVIEW Before You Start Inspect all cartons and boxes for flaws and shipping damage

FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS

WarrantyThe Company warrants and guarantees that all goods within this catalog that have been manufactured by the Company have been manufactured in accordance with the specifications published herein and will be free from defects in material and workmanship for a period of twelve (12) months from the date of Bill of Lading issued by the Company. The Company will replace defective product at its option, but will not be responsible for labour or material charges in replacing product or consequential damages. Any installation not conforming with the Company's specifications, manuals, bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty. This warranty is in lieu of all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement of such warranties, statutory or otherwise.