ENERBATT 3GWireless Battery Monitoring System

WIRELESSRadio

FrequencyMonitoring

NO MOREMESSY

CABLES

ENERBATT 3G

The Enerbatt 3G Battery MonitoringSystem is a complete solut ion forcaptur ing important parameters ofbatteries at real time. The BMS is able,communicate wirelessly, measure up to512 nodes per system and record data inexternal memory cards to enable easydata access and backup securi ty.

Battery Cell Short or Open

Battery Cell Reversal

Battery Cell Impedance

- determine impedance value of

the internal battery cell

Communication & protocol

- R.F 2.4G for wireless connection

- wired communication via

Ethernet TCP/IP, RS 485

The new BMS is able to detect various battery problems to ensurethe batteries are in working conditions.

Short point

Battery voltagedecrease

Open point

Battery voltageincrease

4V dropped

1 cell voltage reverse

The Data collector comes with a large 6.4” LCD Screen with GraphicTouch function offering access and viewing of various batteriesparameters.

Functions of the Data Collector:Real-time Monitoring Information and Battery Test

- Battery Voltage, Battery Impedance, String Voltage, StringCurrent and Environment Temperature

Charts & Curves- Curve, Bar graph, AverageEvents Log

- Alarms via email & dry contactSensor Network Manage

- Battery Configuration settings- Networks Parameters settings

ENERBATT 3G

Impedance curve

Temperature curve

Voltage curve

History curve

Battery voltage

Event logs

Batteries readings

ENERBATT 3GTechnical Specification

18 Watts, maximumPower Consumption

RF 2.4G for wirelessRadio Frequency

Ethernet TCP/IP, RS 485,

Input / Output Dry contact signal

Available Communication Port

100 ~ 240Vac, 35 ~ 60VdcSupply Voltage

440 × 262 × 75Enclosure Dimension (W × H × D) mm

95% without condensingRelative Humidity

0°C~40°COperating Temperature

GENERAL

1M

10mV

1mV

1.5~4V

2V

BATTERY BLOCK VOLTAGE MEASUREMENT

Input Impedance

Accuracy

Resolution

9~16V4.5~8VBlock Voltage Measuring Range

12V6VBlock Rated Voltage

1MInput Impedance

0.3VAccuracy

0.1VResolution

620VMaximum Measurement Voltage

BATTERY STRING VOLTAGE MEASUREMENT

Designed and Engineered by

0.3%Accuracy

0.1AResolution

3,000AMaximum Measurement Voltage

BATTERY STRING CURRENT MEASUREMENT