Page 1: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

ELECTRIC UTILITY

ELECTRIC UTILITY

ENERGY WIRE AND CABLE FOR POWER GENERATION,TRANSMISSION AND DISTRIBUTION

m a r c h 2 0 12

Page 2: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

Electric UtilityThis catalog contains in-depth information on the most comprehensive line of utility products available today for the electric utility marketplace.

The product and technical sections have been developed with an easy-to-use “spec-on-a-page” format. They feature the latest information on electric utility products, from applications and construction to detailed technical and specification data. There’s also a user-friendly index.

For low-, medium-, high-, and extra-high-voltage wire and cable for power generation, distribution and transmission, both overhead and underground, General Cable offers a broad spectrum of BICC® Brand and Silec® Brand cables for electric utilities, rural electric co-ops and independent power producers.

all information in this catalog is presented solely as a guide to product selection and is believed to be reliable. all printing errors are subject to correction in subsequent releases of this catalog. although General Cable has taken precautions to ensure the accuracy of the product specifications at the time of publication, the specifications of all products contained herein are subject to change without notice.

GeNeraL CabLe, SILeC braND, bICC braND, bIfILL, CDC, eMPOWr, POWrMaX, POWrNeT, POWrPaK, POWrSerV, STraNDfILL, TraNSPOWr, TrIfILL and uLTraPOWr are trademarks of General Cable Technologies Corporation.

emPowr® fill and PowrPak cables with General Cable’s semi-conducting shields are protected by u.S. patents 6,274,066; 5,556,697 and other patents pending.

emPowr® Link cables with General Cable’s semi-conducting shields are protected by u.S. patents 6,274,066; 6,291,772; 6,491,849 and other patents pending.

© 2012. General Cable Technologies Corporation.Highland Heights, Ky 41076all rights reserved. Printed in uSa.

What’s New?

S I L EC ® B R A N D H I G H - & E X T R A- H I G H -VO LTAG E CA B L E SYST EM S

The Silec Brand name has been synonymous with solid-dielectric

extruded cable solutions for nearly fifty years. General Cable offers

a fully integrated approach to providing a comprehensive range

of quality Silec high- and extra-high-voltage cable systems. They

are designed, engineered and manufactured to ensure maximum

service life and best-in-class performance while maintaining cost

effectiveness.

D EL I V ER I N G T H E R EN E WA B L E P OW ER O F W I N D EN ER GY

General Cable has the offering to comprise a complete cable solution

for wind power applications. From optical fiber and grounding

wires for SCADA systems, low-voltage DC and AC connections and

medium-voltage distribution to high-voltage overhead, underground

and submarine transmission lines, General Cable has the range of

products engineered to withstand the demands of entire wind power

generation, transmission and distribution systems — from the wind

to the outlet.

H A R N ES S I N G T H E R EN E WA B L E P OW ER O F T H E S U N

General Cable has the offering to comprise a complete cable

solution for solar power applications. From low-voltage DC and

AC connections and medium-voltage distribution to high-voltage

overhead and underground transmission lines, General Cable’s range

of products is engineered to withstand the demands of entire solar

power generation, transmission and distribution systems — from the

sun to the outlet.

G EN ER AT I N G R ES U LTS T H R O U G H I N N OVAT I O N

EmPowr® Link CL™, the next generation in renewable energy

collection systems, is the only medium-voltage cable that costs

less now and pays more later.

• Reduced upfront cost • Environmentally friendly

• Better long-term efficiency • Greater return on investment

When it comes to ensuring system reliability to satisfy the

demand for uninterrupted power, you can rely on the validated

performance of EmPowr® Link CL™.

Page 3: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

PRODUCT SELECTION LOCATORSection PageS

1 Low-Voltage Power cable 1-13

2 Medium-Voltage Power cable 14-41

5 Bicc® Brand Stock Program 132

6 Handling Recommendations and Packaging information 133-135

3 High- and extra-High-Voltage transmission cable 42-47

7 code Word classifications and index 136-139

4 overhead conductors 48-131

Page 4: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

EmPowr® Description ...........................................................................................................................................14-16

Concentric Neutral Underground Distribution Cable

• 15kVCUorALConductor ...........................................................................................................................17-20

• 25kVCUorALConductor ...........................................................................................................................21-22

• 28kVCUorALConductor ...........................................................................................................................23-24

• 35kVCUorALConductor ...........................................................................................................................25-26

FlatStrap–PILCReplacementCable

• 15kV&25kVCUConductor .......................................................................................................................27-28

Copper Wire Shielded Power Cable

• 5kV&15kVCUConductor .............................................................................................................................. 29

• 5kV&15kVALConductor ............................................................................................................................... 30

• 25kV,35kV&46kVCUConductor ................................................................................................................. 31

• 25kV,35kV&46kVALConductor .................................................................................................................. 32

Copper Tape Shielded Power Cable

• 5kV&15kVCUConductor .............................................................................................................................. 33

• 5kV&15kVALConductor ............................................................................................................................... 34

• 25kV,35kV&46kVCUConductor ................................................................................................................. 35

• 25kV,35kV&46kVALConductor .................................................................................................................. 36

LongitudinallyAppliedCorrugatedTape(LACT)ShieldedPowerCable

• 15kVCUConductor ......................................................................................................................................... 37

• 15kVALConductor .......................................................................................................................................... 38

• 25kV&35kVCUConductor ............................................................................................................................ 39

• 25kV&35kVALConductor ............................................................................................................................. 40

SECTioN PAgeS

Table of Contents

1 Low-Voltage Power Cable 1-13

2 Medium-Voltage Power Cable 14-41

3 High- and Extra-High-Voltage Transmission Cable 42-47

PowrServ® Description ................................................................................................................................................ 1

Underground Distribution Cable

• USeI-75 ............................................................................................................................................................2-3

• USeI-90 ............................................................................................................................................................4-5

• USeB-90 ...........................................................................................................................................................6-7

Service Drop Cable Neutral-Supported

• DuplexTypeNS75 ............................................................................................................................................... 8

• TriplexTypeNS75 ................................................................................................................................................ 9

• QuadruplexTypeNS75 ..................................................................................................................................... 10

• DuplexTypeNS75/NS90 ................................................................................................................................... 11

• TriplexTypeNS75/NS90 .................................................................................................................................... 12

• QuadruplexTypeNS75/NS90 ........................................................................................................................... 13

Page 5: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

Section pageS

Table of Contents

transpowr® Description .......................................................................................................................................48-50

Bare overhead

• A1(ASC)AluminumStrandedConductor ....................................................................................................51-58

• Compact(SmoothBody)ASCAluminumStrandedConductor...................................................................59-62

• AAC/TWTrapezoidalAluminumStrandedConductor .................................................................................63-68

• A2(AASC)AluminumAlloyStrandedConductor .........................................................................................69-72

• ACSRAluminumConductorSteel-Reinforced .............................................................................................73-90

• Compact(SmoothBody)ACSRAluminumConductorSteel-Reinforced ....................................................91-94

• ACSR/TWTrapezoidalAluminumConductorSteel-Reinforced .................................................................95-102

• ACSSAluminumConductorSteel-Supported .........................................................................................103-112

• ACSS/TWTrapezoidalAluminumConductorSteel-Supported ...............................................................113-120

• ACSR/SDSelf-DampingAluminumConductorSteel-Reinforced ............................................................121-126

WeatherproofOverheadLineWire

• WeatherproofOverheadLineWire ...........................................................................................................127-130

AluminumTieWire

• AluminumTieWire........................................................................................................................................... 131

4 Overhead Conductors 48-131

5 BICC® Brand Stock Program 132

7 Code Word Classifications and Index 136-139

• RecommendedReelHandlingProcedures ..............................................................................................133-134

• StandardPackageandShippingInformation ................................................................................................. 135

6 Handling Recommendations and Packaging Information 133-135

Product Warning NoticeCommencing in the mid 1980s, the Electrical and Electronic Manufacturers Association of Canada (EEMAC) promoted that the following product warning notice be provided to the users of electrical wire and cable.

WARNING

Risk Description

FLAMMABLE – Cables will burn and may transmit fire.

TOXIC – Toxic gas may be formed from burning cables. – DO NOT breathe fumes or enter area until well ventilated.

CORROSIVE– Burning cables may form acid gases. – DO NOT enter area until well ventilated. – Metals in the vicinity of burning cables may corrode.

SMOKE – Burning cables may release dense smoke that may impede fire supression.

– Burning cables may cause loss of life, personal injury, damage to property and may impede fire supression efforts. – Risks increase when a) cables are grouped, and b) cables are installed in facilities which fail to comply with good engineering practices relating to fire protection, electrical systems, operating and maintenance practices (the “Engineering Practices”). – Expert advice must be sought in relation to the Engineering Practices to minimize all risks.

This notice supercedes all references to the characteristics of this cable and must be brought to the attention of those involved with the use of cables.

3/2013

Page 6: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

Our Green Initiative symbol recognizes our role

and responsibility in promoting sustainability.

The symbol also reflects our commitment to achieving

industry-leading standards and responding

proactively to environmental global issues.

Visit www.generalcable.comSelect “COMPANY”, then select “Corporate Social Responsibility”

Look for our products with the RoHS symbol for your green building initiatives.

Page 7: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

general cable is a leader in the

development, design, manufacture,

marketing and distribution of copper,

aluminum and fiber optic wire and cable

for the energy, industrial, specialty and

communications markets.

our products inspire progress worldwide …

customers use our value-added products

to create global infrastructure that

improves the standard of living for

people everywhere.

each day we’re building business

momentum — developing ideas into

innovative solutions and industry-leading

products, expanding geographic access and

furthering our investment in highly capable

associates, Lean Manufacturing, material

science and technology resources.

as one of the largest wire and cable manufacturers with more than

14,000 associates, 57 manufacturing facilities in 26 countries and

sales representation and distribution worldwide, we are truly

One Company Connecting the World.

Energy Cables our cables carry energy across the world — through the air,

underground and under the sea. increasing demand for energy is

accelerating investment in exploration, extraction, power generation,

transmission and distribution — whether based on coal, natural gas,

oil, nuclear, wind, solar or water.

Industrial & Specialty Cables our cables channel the power and signals that make equipment hum

and engines run. From oil rigs and broadcast studios to cars and

trains, and in commercial buildings, public venues, factory floors and

special applications such as military, nuclear, marine and mining —

we serve an extensive range of markets.

Communications Cables our cables keep information flowing — facilitating a non-stop stream

of words and images around the world. We meet the high-speed

bandwidth needs of global communications networks from fiber

optic submarine communications cables, copper and fiber aerial and

underground cables to copper and fiber optic enterprise cables and

system solutions.

World Headquarters General Cable 4 tesseneer Drive

Highland Heights, KY

41076-9753 U.S.a.

Building Bridges in the Sky

Making Contact with the World

Directing Traffic without gridlock

Page 8: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

ELECTRIC UTILITy

Page 9: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

1

Electric Utility

index Page

USei-75 2-3

USei-90 4-5

USeB-90 6-7

Duplex type nS75 8

triplex type nS75 9

Quadruplex type nS75 10

Duplex type nS75/nS90 11

triplex type nS75/nS90 12

Quadruplex type nS75/nS90 13

PowrServ® Underground Secondary Distribution Cablegeneral cable manufactures a complete line of insulated underground secondary cable.general cable’s PowrServ® service cables are intended to provide power from secondary power transformers that are pad-mounted.general cable’s PowrServ® Pe USei-75 and PowrServ® XL USei-90 underground service entrance cable consists of two, three, or four class B compact 1350-H16 or -H26 aluminum conductors individually insulated with black Pe insulation (USei-75) or black RW90 XLPe insulation (USei-90), jacketed with coloured PVc and twisted together. PowrServ® Pe USei-75 cables are rated for 75ºc maximum conductor temperature under normal conditions. PowrServ® XL USei-90 cables are rated for 90ºc maximum conductor temperature under normal conditions.general cable’s PowrServ® XL USeB-90 underground service entrance cable consists of two class B compact 1350-H16 or -H26 aluminum conductors individually insulated with black RW90 XLPe insulation, laid in parallel, with a helical plain copper wire serving and an overall PVc jacket covering. PowrServ® XL USeB-90 cables are rated for 90ºc maximum conductor temperature under normal conditions.Underground secondary and service entrance cables are manufactured in accordance with cSa Standard c22.2 no. 52.general cable’s PowrServ® service cables are available in numerous insulation types, conductor alloys and numbers of conductors to meet a customer’s particular requirements. the most common styles are generally available from stock.

PowrServ® Underground Cable Options• CopperConductor– Primarily used when more ampacity is needed and/or there are limitations to the overall cable diameter.• Alloy8000AluminumConductor(ACM)– Developed to overcome mechanical connection problems associated with circuit sizes 10 to 14 aWg• ReelessPackage– Supplied in coils without the wooden reel. Provides an environmentally friendly packaging option to avoid the disposal cost and

save landfill space.• OtherPhaseIdentificationMethods– identified by coloured extruded stripes.• CDC®CombinedDuct&Cable– Designed for direct burial. the pre-installed system reduces the installation and repair cost. Various designs of wall thickness HDPe conduits are available.

PowrServ® Overhead Secondary Distribution Cablegeneral cable manufactures a complete line of insulated products for overhead secondary distribution.general cable’s PowrServ® overhead service cables are intended to provide power from secondary power transformers that are pole-mounted. the overhead service cables can also be used as pole line secondary with service splices at the pole or mid-span. general cable’s PowrServ® oH overhead products consist of a class a compact 1350-H19 aluminum conductor insulated with LLDPe (nS75) or XLPe (nS75/nS90) around a compact acSR neutral and manufactured in accordance with cSa Standard c22.2 no. 129. general cable’s PowrServ® overhead service cables are available in numerous insulation types, conductor alloys and numbers of conductors to meet a customer’s particular requirements. the most common styles are generally available from stock.

PowrServ® Overhead Cable Options• Aluminum1350–H16(¾hard)Conductor– Provides more flexibility than H19 (full hard), but yields less tensile strength.• CopperConductor– Primarily used when more ampacity is needed and/or there are environmental corrosion concerns.• FT1-RatedCross-linkedPolyethyleneInsulation– Ft1-rated flame-retardant insulation.• Colour-CodedorRibbedPVCJacket– Provides phase identification and Ft1-rated flame retardancy.• A2Messenger– concentric stranded class a, 6101-t81 aluminum alloy stranded neutral messenger conductor (a2).• A2/S3A(AACSR)Messenger– concentric stranded class a, 6101-t81 aluminum alloy – high strength steel-reinforced stranded neutral

messenger conductor.• OtherPhaseIdentificationMethods– Printed numbers on black coloured insulation or extruded coloured stripes.• CorrosionInhibitor– conductor corrosion-resistant inhibitor treatment.• ReelessPackage– Supplied in coils without the wooden reel. Provides an environmentally friendly packaging option to avoid the disposal

cost and save landfill space.

Low-Voltage Power Cable 1

3/2013

Page 10: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

2

Low-Voltage Power Cable Electric Utility

Product Construction:

Complete Cable:USei-75 Underground Service entrance cable consists of two, three, or four compact aluminum conductors individually insulated with 75°c black Pe insulation, jacketed with coloured PVc and twisted together. the neutral conductor will be white. the product meets the USei-75 cable requirements of cSa c22.2 no. 52.

Conductors: the aluminum stranded conductors are class B compact 1350-H16 (3/4 hard) aluminum.

Insulation: the insulation is a black, Linear Low-Density Polyethylene (LLDPe) meeting the requirements of cSa c22.2 no. 52 for 75°c wet and dry rated polyethylene.

Jacket: over top of the insulation, a continuous layer of PVc is extruded. the jacket is a weather- and sunlight-resistant, non-sulphide-staining, cut-through-resistant, 75°c/-40°c Ft1-rated material.

Neutral Conductor: one of the insulated conductors is identified as a neutral conductor by the use of a white coloured PVc jacket. the neutral conductor may be the same size as the power conductor, or it may be reduced.

PhaseIdentification: Phase identification is provided by means of jacket colour coding. three conductor cable consists of a red and a black coloured power conductor and a white coloured neutral. Four conductor cable consists of a red, black, and blue coloured phase conductor and a white coloured neutral. all cables provided with sequential print marking.

THREE CONDUCTOR TYPE USEI-75 – LLDPE/PVC – 600 VOLTS

PHASE CONDUCTORS FULL NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVE DIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 4 7 1.14 0.76 20 323 65

2 7 1.14 0.76 2 7 1.14 0.76 23 457 90

1 19 1.40 1.14 1 19 1.40 1.14 27 627 100

1/0 19 1.40 1.14 1/0 19 1.40 1.14 29 745 120

2/0 19 1.40 1.14 2/0 19 1.40 1.14 32 890 135

3/0 19 1.40 1.14 3/0 19 1.40 1.14 34 1067 155

4/0 19 1.40 1.14 4/0 19 1.40 1.14 37 1288 180

250 37 1.65 1.65 250 37 1.65 1.65 43 1625 205

350 37 1.65 1.65 350 37 1.65 1.65 48 2132 250

500 37 1.65 1.65 500 37 1.65 1.65 55 2867 310

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(75°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ® PE Underground Secondary Cable Type USEI-75600 V, aluminum conductor, LLDPe insulation, PVc Jacket, cSa Listed

Page 11: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

3

Electric Utility Low-Voltage Power Cable

FeaturesandBenefits:the USei-75 cables are suitable for direct burial or installed in ducts and are resistant to cut-through and sunlight. the cable is rated 600 V phase to phase, with a maximum conductor operating temperature of 75°c in wet or dry locations.

Applications:cSa USei-75 cable is intended for use in underground systems operating at 600 V or less. the cables are intended for underground installation, either directly buried or in duct systems, in accordance with the cec (cSa c22.1) and cSa c22.3 no. 7 Underground Systems. Portions of the cable may be exposed to sunlight on termination poles and during storage.

Options: •ClassBstrandedcompactACM(series8000) type aluminum alloy conductors

•ClassBstrandedcompactcopperconductors

•CSAC68.7fordistributionutilities

For more information, contact your general cable sales representative or e-mail [email protected].

FOUR CONDUCTOR TYPE USEI-75 – LLDPE/PVC – 600 VOLTS

PHASE CONDUCTORS FULL NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVE DIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 4 7 1.14 0.76 22 431 65

2 7 1.14 0.76 2 7 1.14 0.76 26 610 90

1 19 1.40 1.14 1 19 1.40 1.14 31 835 100

1/0 19 1.40 1.14 1/0 19 1.40 1.14 33 993 120

2/0 19 1.40 1.14 2/0 19 1.40 1.14 35 1186 135

3/0 19 1.40 1.14 3/0 19 1.40 1.14 38 1422 155

4/0 19 1.40 1.14 4/0 19 1.40 1.14 42 1717 180

250 37 1.65 1.65 250 37 1.65 1.65 48 2167 205

350 37 1.65 1.65 350 37 1.65 1.65 54 2843 250

500 37 1.65 1.65 500 37 1.65 1.65 61 3823 310

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(75°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ® PE Underground Secondary Cable Type USEI-75600 V, aluminum conductor, LLDPe insulation, PVc Jacket, cSa Listed

Page 12: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

4

Low-Voltage Power Cable Electric Utility

Product Construction:

Complete Cable:USei-90 Underground Service entrance cable consists of two, three, or four compact aluminum conductors individually insulated with black RW90 XLPe insulation, a coloured PVc jacket, and twisted together. the neutral conductor will be white. the product meets the USei-90 cable requirements of cSa c22.2 no. 52.

Conductors: the aluminum stranded conductors are class B compact 1350-H16 (3/4 hard) aluminum.

Insulation: the insulation is a black cross-linked Polyethylene (XLPe) meeting the requirements of cSa c22.2 no. 52 for type RW90 insulation.

Jacket: a continuous layer of PVc is extruded over the insulation. the jacket is a weather-resistant, non-sulphide-staining, cut-through-resistant, 90°c/-40°c Ft1-rated material.

Neutral Conductor: one of the insulated conductors is identified as a neutral conductor by the use of a white coloured PVc jacket. the neutral conductor may be the same size as the power conductor, or it may be reduced.

PhaseIdentification: Phase identification is provided by means of jacket colour coding. three conductor cable consists of a red and a black coloured power conductor and a white coloured neutral. Four conductor cable consists of a red, black, and blue coloured phase conductor and a white coloured neutral. all cables provided with sequential print marking.

THREE CONDUCTOR TYPE USEI-90 – XLPE/PVC – 600 VOLTS

PHASE CONDUCTORS FULL NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVE DIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 4 7 1.14 0.76 20 324 65

2 7 1.14 0.76 2 7 1.14 0.76 23 458 95/100*

1 19 1.40 1.14 1 19 1.40 1.14 27 628 105

1/0 19 1.40 1.14 1/0 19 1.40 1.14 29 746 120

2/0 19 1.40 1.14 2/0 19 1.40 1.14 32 891 145

3/0 19 1.40 1.14 3/0 19 1.40 1.14 34 1068 165

4/0 19 1.40 1.14 4/0 19 1.40 1.14 37 1290 185/200*

250 37 1.65 1.65 250 37 1.65 1.65 43 1628 215

350 37 1.65 1.65 350 37 1.65 1.65 48 2135 260

500 37 1.65 1.65 500 37 1.65 1.65 55 2871 330

PHASE CONDUCTORS REDUCED NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVE DIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 6 7 1.14 0.76 19 295 65

2 7 1.14 0.76 4 7 1.14 0.76 22 413 95/100*

1 19 1.40 1.14 3 7 1.14 0.76 27 560 105

1/0 19 1.40 1.14 2 7 1.14 0.76 28 650 120

2/0 19 1.40 1.14 1 19 1.40 1.14 31 803 145

3/0 19 1.40 1.14 1/0 19 1.40 1.14 33 961 165

4/0 19 1.40 1.14 2/0 19 1.40 1.14 36 1157 185/200*

250 37 1.65 1.65 3/0 19 1.40 1.14 41 1450 215

350 37 1.65 1.65 250 37 1.65 1.65 47 1966 260

500 37 1.65 1.65 350 37 1.65 1.65 53 2626 330

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(90°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

*NOTE: The CEC allows 100A for No. 2 AWG and 200A for 4/0 AWG when used for 3 wire 120/240 V or 120/208 V residential services or subservices. When the higher ampacity is used, the CEC 5% ampacity adjustment rule 8-106 (1) cannot be used.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®XLUndergroundSecondaryCableTypeUSEI-90600 V, aluminum conductor, XLPe insulation, PVc Jacket, cSa Listed

Page 13: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

5

Electric Utility Low-Voltage Power Cable

Features and Benefits:the USei-90 cables are suitable for direct burial or installed in ducts and are resistant to cut-through and sunlight. the cable is rated 600 V phase to phase, with a maximum conductor operating temperature of 90°c in wet or dry locations.

Applications:cSa USei-90 cable is intended for use in underground systems operating at 600 V or less. the cables are intended for underground installation, either directly buried or in duct systems, in accordance with the cec (cSa c22.1) and cSa c22.3 no. 7 Underground Systems. Portions of the cable may be exposed to sunlight on termination poles and during storage.

Options: • ClassBstrandedcompactACM(series8000) type aluminum alloy conductors

• ClassBstrandedcompactcopperconductors

• TwoconductorUSEI-90cables

•CSAC68.7fordistributionutilities

For more information, contact your general cable sales representative or e-mail [email protected].

FOUR CONDUCTOR TYPE USEI-90 – XLPE/PVC – 600 VOLTS

PHASE CONDUCTORS FULL NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVEDIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 4 7 1.14 0.76 22 432 65

2 7 1.14 0.76 2 7 1.14 0.76 26 611 95

1 19 1.40 1.14 1 19 1.40 1.14 31 837 105

1/0 19 1.40 1.14 1/0 19 1.40 1.14 33 995 120

2/0 19 1.40 1.14 2/0 19 1.40 1.14 35 1188 145

3/0 19 1.40 1.14 3/0 19 1.40 1.14 38 1425 165

4/0 19 1.40 1.14 4/0 19 1.40 1.14 42 1720 185

250 37 1.65 1.65 250 37 1.65 1.65 48 2170 215

350 37 1.65 1.65 350 37 1.65 1.65 54 2847 260

500 37 1.65 1.65 500 37 1.65 1.65 61 3828 330

PHASE CONDUCTORS REDUCED NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

EFFECTIVEDIAMETER (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

4 7 1.14 0.76 6 7 1.14 0.76 22 403 65

2 7 1.14 0.76 4 7 1.14 0.76 25 566 95

1 19 1.40 1.14 3 7 1.14 0.76 31 770 105

1/0 19 1.40 1.14 2 7 1.14 0.76 31 899 120

2/0 19 1.40 1.14 1 19 1.40 1.14 34 1100 145

3/0 19 1.40 1.14 1/0 19 1.40 1.14 37 1317 165

4/0 19 1.40 1.14 2/0 19 1.40 1.14 40 1587 185

250 37 1.65 1.65 3/0 19 1.40 1.14 46 1984 215

350 37 1.65 1.65 250 37 1.65 1.65 52 2678 260

500 37 1.65 1.65 350 37 1.65 1.65 59 3582 330

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(90°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®XLUndergroundSecondaryCableTypeUSEI-90600 V, aluminum conductor, XLPe insulation, PVc Jacket, cSa Listed

Page 14: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

6

Low-Voltage Power Cable Electric Utility

Product Construction:

Complete Cable:USeB-90 Underground Service entrance cable consists of two compact aluminum conductors individually insulated with RW90 XLPe insulation, laid in parallel, with a helical plain copper wire serving and an overall PVc jacket covering. the copper wire serving is the neutral. the product meets the USeB-90 cable requirements of cSa c22.2 no. 52.

Conductors: the aluminum stranded conductors are class B compact 1350-H16 (3/4 hard) aluminum.

Insulation: the insulation is a black cross-linked Polyethylene (XLPe) meeting the requirements of cSa c22.2 no. 38 for type RW90 insulation.

Neutral Conductor: an annealed, plain copper wire serving is applied over top of the two power conductors. the neutral conductor may be equal to the equivalent copper aWg size of the power conductor, or it may be reduced.

Binder/SeparatorTape: a separator tape is applied overtop the helically applied neutral conductor wires.

Jacket: Black PVc jacket is extruded over top of the cable assembly. the jacket is a weather-resistant, sunlight-resistant, 60°c/-40°c Ft1-rated material.

PhaseIdentification: Both of the XLPe insulated power conductors are black. one conductor will have a white coloured print legend on the surface of the insulation. the print legend includes the required cSa markings and general cable manufacturing plant code, year marking, and “1-one-1” printed phase identifier. the other conductor will only have the “2-tWo-2” marking. all cables provided with sequential print marking.

TWO CONDUCTOR TYPE USEB-90 – XLPE/PVC – FULL NEUTRAL – 600 VOLTS

PHASE CONDUCTORSFULL NEUTRAL CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

NO. OF WIRES x SIZE(AWG)

EQUIVALENT AWG SIZE

EFFECTIVE DIAMETER

THKN. X WIDTH (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

AMPACITY (3)

4 7 1.14 2.03 11x#16 6 15x22 456 65 140

2 7 1.14 2.03 17x#16 4 16x25 632 95/100* 180

1 19 1.40 2.03 21x#16 3 17x28 770 105 205

1/0 19 1.40 2.03 26x#16 2 18x30 916 120 235

2/0 19 1.40 2.03 33x#16 1 19x32 1105 145 265

3/0 19 1.40 2.03 26x#14 1/0 21x35 1340 165 300

4/0 19 1.40 2.03 33x#14 2/0 22x37 1633 185/200* 350

250 37 1.65 2.03 26x#12 3/0 25x41 1969 215 370

350 37 1.65 2.79 25x#10 250 30x49 2985 260 445

500 37 1.65 2.79 34x#10 350 33x55 3843 330 540

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(75°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

*NOTE: The CEC allows 100A for No. 2 AWG and 200A for 4/0 AWG when used for 3 wire 120/240 V or 120/208 V residential services or subservices. When the higher ampacity is used, the CEC 5% ampacity adjustment rule 8-106 (1) cannot be used.

(3)Theampacityratingsarebasedonanengineeringcalculationfordirectburiedcable,36”depthofburial,90°Cconductortemperature,20°Cambient,100%loadfactor,singlecableinstallation,soilrho90°C-cm/W.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®XLUndergroundSecondaryCableTypeUSEB-90600 V, aluminum conductor, XLPe insulation, overall PVc Jacket, cSa Listed

Page 15: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

7

Electric Utility Low-Voltage Power Cable

FeaturesandBenefits:the USeB-90 cables are suitable for direct burial or installed in ducts. the cable is rated 600 V phase to phase, with a maximum conductor operating temperature of 90°c in wet or dry locations.

Applications:cSa USeB-90 cable is intended for use in underground systems operating at 600 V or less. the cables are intended for underground installation, either directly buried or in duct systems, in accordance with the cec (cSa c22.1) and cSa c22.3 no. 7 Underground Systems. Portions of the cable may be exposed to sunlight on termination poles and during storage.

Options: • ClassBstrandedcompactACM(series8000) type aluminum alloy conductors

• ClassBstrandedcompactcopperconductors

• Solidredcolouredpolyvinylchloride(PVC) jacket

• CSAC68.7fordistributionutilities

For more information, contact your general cable sales representative or e-mail [email protected].

TWO CONDUCTOR TYPE USEB-90 – XLPE/PVC – REDUCED NEUTRAL – 600 VOLTS

PHASE CONDUCTORSREDUCED NEUTRAL

CONDUCTOR OVERALL

SIZE (AWG

OR kcmil)

NO. OF WIRES (1)

INS. THKN. (mm)

JACKETTHKN. (mm)

NO. OF WIRES x SIZE (AWG)

EQUIVALENT AWG SIZE

EFFECTIVE DIAMETER

THKN. x WIDTH (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

AMPACITY (3)

4 7 1.14 2.03 9x1.12mm 8 15x22 405 65 140

2 7 1.14 2.03 11x#16 6 16x25 557 95/100* 180

1 19 1.40 2.03 13x#16 5 17x28 670 105 205

1/0 19 1.40 2.03 17x#16 4 18x30 804 120 235

2/0 19 1.40 2.03 21x#16 3 19x32 956 145 265

3/0 19 1.40 2.03 26x#16 2 20x34 1143 165 300

4/0 19 1.40 2.03 33x#16 1 22x37 1385 185/200* 350

250 37 1.65 2.03 26x#14 1/0 24x40 1651 215 370

350 37 1.65 2.79 26x#12 3/0 29x48 2436 260 445

500 37 1.65 2.79 25x#10 250 33x55 3392 330 540

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)TheampacityratingsarebasedonTable4oftheCanadianelectricCode(C22.1)(75°Cconductortemperature,30°C

ambient).Ampacityratingsmaybeusedforsinglecircuitapplicationsofcablesdirectlyburied,inburiedduct,inductbank,orinconduit.

*NOTE: The CEC allows 100A for No. 2 AWG and 200A for 4/0 AWG when used for 3 wire 120/240 V or 120/208 V residential services or subservices. When the higher ampacity is used, the CEC 5% ampacity adjustment rule 8-106 (1) cannot be used.

(3)Theampacityratingsarebasedonanengineeringcalculationfordirectburiedcable,36”depthofburial,90°Cconductortemperature,20°Cambient,100%loadfactor,singlecableinstallation,soilrho90°C-cm/W.

Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®XLUndergroundSecondaryCableTypeUSEB-90600 V, aluminum conductor, XLPe insulation, overall PVc Jacket, cSa Listed

Page 16: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

8

Low-Voltage Power Cable Electric Utility

Product Construction:

Complete Cable: Duplex nS75 Service Drop cable consists of one compact aluminum conductor insulated with Linear Low-Density Polyethylene (LLDPe), twisted around a bare compact acSR stranded neutral conductor, which serves as a supporting neutral.

triplex nS75 consists of two insulated conductors around a bare neutral.

Quadruplex nS75 consists of three insulated conductors around a bare neutral.

nS75 Service Drop cable meets the requirements of cSa c22.2 no. 129 and can/cSa c61089 standards, as applicable.

Insulated Conductors: the all-aluminum stranded conductors are class a smooth body compact 1350-H19 (full hard) aluminum.

Insulation: the standard product is a black, sunlight-resistant, -40°c rated Linear Low-Density Polyethylene (LLDPe).

Bare Neutral: the aluminum conductor Steel Reinforced (acSR) stranded neutral conductors are class a smooth body compact stranded. the direction of lay of the outer layer is right-hand.

PhaseIdentification: Phase identification is provided by means of white print legend markings on one of the black coloured phase conductors and three longitudinal red stripes on the second black coloured phase conductor. Quadruplex cables would be provided with three blue stripes on the third black coloured phase conductor. all cables provided with sequential print marking in the print legend.

UNJACKETED DUPLEX TYPE NS75 – LLDPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTOR ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWG)

NO. OF WIRES

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWG)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(1)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.0 12 111 80

4 7 5.41 1.04 7.75 4 6/1 8.27 6.4 14 169 105

2 7 6.88 1.04 9.14 2 6/1 12.7 8.1 17 260 140

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 22 412 185

(1)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(2)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof75°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ® OH Duplex Neutral-Supported Cable Type NS75600 V, aluminum conductor, LLDPe insulation, acSR neutral, cSa Listed

Page 17: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

9

Electric Utility Low-Voltage Power Cable

FeaturesandBenefits:the insulated conductors of nS75 Service Drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. the cable is rated 600 V with a maximum conductor operating temperature of 75°c for polyethylene insulation.

Applications:Duplex and triplex nS75 Service Drop cable is intended to deliver single phase power from the secondary overhead power line or pole-mounted transformer to the service entrance conductors at the user’s building or other structure.

Quadruplex nS75 Service Drop cable is intended to deliver three phase power from the secondary overhead power line or pole-mounted transformers to the service entrance conductors at the user’s building or other structure.

nS75 cable may also be used as pole line secondary with service splices at the pole (also refer to cec rule 12-318).

nS75 cable is rated for use on systems having nominal voltages of 600 V or less.

Options:• Reduced-sizeinsulatedconductorforuseas a water heater control conductor

• Colour-codedorribbedPVCjacketswhichare used for phase identification and Ft1-rated for flame retardancy

• Alternatephaseidentificationbytheuse of printed numbers on the black coloured insulation

• Neutralconductorcorrosion-resistantinhibitor treatment

• Neutralsupportedcableisavailablewith annealed copper conductors

• ConcentricstrandedClassA,6101-T81 aluminum alloy stranded neutral messenger conductor (a2)

• ConcentricstrandedClassA,6101-T81 aluminum alloy – high strength steel- reinforced stranded neutral messenger conductor (a2/S3a, aacSR)

•CSAC68.8fordistributionutilities

For more information, contact your general cable sales representative or e-mail [email protected].

UNJACKETED TRIPLEX TYPE NS75 – LLDPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.03 13 167 80

4 7 5.41 1.04 7.75 4 6/1 8.27 6.35 16 252 105

2 7 6.88 1.04 9.14 2 6/1 12.7 8.11 19 383 140

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 24 601 185

2/0 7 9.65 1.37 12.6 2/0 6/1 23.6 11.5 27 751 210

3/0 7 10.7 1.37 13.8 3/0 6/1 29.5 12.8 29 931 245

4/0 7 12.1 1.37 15.2 4/0 6/1 37.1 14.3 32 1157 280

266.8 19 13.6 1.83 17.7 266.8 26/7 50.3 16.3 38 1486 325

336.4 19 15.3 1.83 19.4 336.4 26/7 62.7 18.3 42 1844 375

397.5 19 16.7 1.83 20.8 397.5 26/7 72.5 19.9 45 2157 415

477 19 18.3 1.83 22.4 477 26/7 86.5 21.8 49 2565 460

UNJACKETED TRIPLEX TYPE NS75 – LLDPE – ACSR REDUCED SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

4 7 5.41 1.04 7.75 6 6/1 5.29 5.03 15 220 105

2 7 6.88 1.04 9.14 4 6/1 8.27 6.35 18 333 140

1/0 7 8.53 1.37 11.6 2 6/1 12.7 8.11 23 527 185

2/0 7 9.65 1.37 12.6 1 6/1 15.8 8.99 25 650 210

3/0 7 10.7 1.37 13.8 1/0 6/1 19.5 10.1 28 803 245

4/0 7 12.1 1.37 15.2 2/0 6/1 23.6 11.5 30 996 280

266.8 19 13.6 1.83 17.7 3/0 6/1 29.5 12.8 35 1282 325

336.4 19 15.3 1.83 19.4 4/0 6/1 37.1 14.3 39 1588 375

397.5 19 16.7 1.83 20.8 266.8 26/7 50.3 16.3 42 1890 415

477 19 18.3 1.83 22.4 336.4 26/7 62.7 18.3 46 2277 460

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(3)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof75°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ® OH Triplex Neutral-Supported Cable Type NS75600 V, aluminum conductor, LLDPe insulation, acSR neutral, cSa Listed

Page 18: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

10

Low-Voltage Power Cable Electric Utility

PowrServ® OH Quadruplex Neutral-Supported Cable Type NS75600 V, aluminum conductor, LLDPe insulation, acSR neutral, cSa Listed

UNJACKETED QUADRUPLEX TYPE NS75 – LLDPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.03 15 224 70

4 7 5.41 1.04 7.75 4 6/1 8.27 6.35 18 335 95

2 7 6.81 1.04 9.14 2 6/1 12.7 8.11 21 507 125

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 27 803 165

2/0 7 9.65 1.37 12.6 2/0 6/1 23.6 11.5 30 991 190

3/0 7 10.7 1.37 13.8 3/0 6/1 29.5 12.8 33 1224 220

4/0 7 12.1 1.37 15.2 4/0 6/1 37.1 14.3 36 1519 255

266.8 19 13.6 1.83 17.7 266.8 26/7 50.3 16.3 42 1955 290

336.4 19 15.3 1.83 19.4 336.4 26/7 62.7 18.3 46 2421 335

397.5 19 16.7 1.83 20.8 397.5 26/7 72.5 19.9 50 2828 370

477 19 18.3 1.83 22.4 477 26/7 86.5 21.8 54 3359 415

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(3)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof75°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

Page 19: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

11

Electric Utility Low-Voltage Power Cable

Product Construction:

Complete Cable: Duplex nS75/nS90 Service Drop cable consists of one compact aluminum conductor insulated with cross-linked Polyethylene (XLPe), twisted around a bare compact acSR stranded neutral conductor, which serves as a supporting neutral.

triplex nS75/nS90 consists of two insulated conductors around a bare neutral.

Quadruplex nS75/nS90 consists of three insulated conductors around a bare neutral.

nS75/nS90 Service Drop cable meets the requirements of cSa c22.2 no. 129 and can/cSa c61089 standards, as applicable.

Insulated Conductors: the all-aluminum stranded conductors are class a smooth body compact 1350-H19 (full hard) aluminum.

Insulation: the standard product is a black, sunlight-resistant, -40°c rated extruded cross-linked Polyethylene (XLPe).

Bare Neutral: the aluminum conductor steel reinforced (acSR) stranded neutral conductors are class a smooth body compact stranded. the direction of lay of the outer layer is right-hand.

PhaseIdentification: Phase identification is provided by means of white print legend markings on one of the black coloured phase conductors and three longitudinal red stripes on the second black coloured phase conductor. Quadruplex cables would be provided with three blue stripes on the third black coloured phase conductor. all cables provided with sequential print marking in the print legend.

PowrServ®OHDuplexNeutral-SupportedCableTypeNS75/NS90600 V, aluminum conductor, XLPe insulation, acSR neutral, cSa Listed

UNJACKETED DUPLEX TYPE NS75/NS90 – XLPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWG)

NO. OF WIRES

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWG)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(1)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (2)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.0 12 111 95

4 7 5.41 1.04 7.75 4 6/1 8.27 6.4 14 169 110

2 7 6.88 1.04 9.14 2 6/1 12.7 8.1 17 260 150

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 22 412 200

(1)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(2)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof90°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

Page 20: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

12

Low-Voltage Power Cable Electric Utility

FeaturesandBenefits:the insulated conductors of nS75/nS90 Service Drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. the cable is rated 600 V with a maximum conductor operating temperature of 90°c for cross-linked Polyethylene insulation, which allows for higher ampacity compared to nS75 cable.

Applications:Duplex and triplex nS75/nS90 Service Drop cable is intended to deliver single phase power from the secondary overhead power line or pole-mounted transformer to the service entrance conductors at the user’s building or other structure.

Quadruplex nS75/nS90 Service Drop cable is intended to deliver three phase power from the secondary overhead power line or pole-mounted transformers to the service entrance conductors at the user’s building or other structure.

nS75/nS90 cable may also be used as pole line secondary with service splices at the pole (also refer to cec rule 12-318).

nS75/nS90 cable is rated for use on systems having nominal voltages of 600 V or less.

Options:• Reduced-sizeinsulatedconductorforuseas a water heater control conductor

• Colour-codedorribbedPVCjacketswhichare used for phase identification and Ft1-rated for flame retardancy

• Alternatephaseidentificationbytheuse of printed numbers on the black coloured insulation

• Neutralconductorcorrosion-resistantinhibitor treatment

• FT1-ratedflame-retardantinsulation

• Neutral-supportedcableisavailablewith annealed copper conductors

• ConcentricstrandedClassA,6101-T81 aluminum alloy stranded neutral messenger conductor (a2)

• ConcentricstrandedClassA,6101-T81 aluminium alloy – high strength steel- reinforced stranded neutral messenger conductor (a2/S3a, aacSR)

•CSAC68.8fordistributionutilities

For more information, contact your general cable sales representative or e-mail [email protected].

UNJACKETED TRIPLEX TYPE NS75/NS90 – XLPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.03 13 167 95

4 7 5.41 1.04 7.75 4 6/1 8.27 6.35 16 252 125

2 7 6.88 1.04 9.14 2 6/1 12.7 8.11 19 383 165

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 24 601 220

2/0 7 9.65 1.37 12.6 2/0 6/1 23.6 11.5 27 751 255

3/0 7 10.7 1.37 13.8 3/0 6/1 29.5 12.8 29 931 290

4/0 7 12.1 1.37 15.2 4/0 6/1 37.1 14.3 32 1157 335

266.8 19 13.6 1.83 17.7 266.8 26/7 50.3 16.3 38 1486 390

336.4 19 15.3 1.83 19.4 336.4 26/7 62.7 18.3 42 1844 450

397.5 19 16.7 1.83 20.8 397.5 26/7 72.5 19.9 45 2157 500

477 19 18.3 1.83 22.4 477 26/7 86.5 21.8 49 2565 560

UNJACKETED TRIPLEX TYPE NS75/NS90 – XLPE – ACSR REDUCED SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

4 7 5.41 1.04 7.75 6 6/1 5.29 5.03 15 220 125

2 7 6.88 1.04 9.14 4 6/1 8.27 6.35 18 333 165

1/0 7 8.53 1.37 11.6 2 6/1 12.7 8.11 23 527 220

2/0 7 9.65 1.37 12.6 1 6/1 15.8 8.99 25 650 255

3/0 7 10.7 1.37 13.8 1/0 6/1 19.5 10.1 28 803 290

4/0 7 12.1 1.37 15.2 2/0 6/1 23.6 11.5 30 996 335

266.8 19 13.6 1.83 17.7 3/0 6/1 29.5 12.8 35 1282 390

336.4 19 15.3 1.83 19.4 4/0 6/1 37.1 14.3 39 1588 450

397.5 19 16.7 1.83 20.8 266.8 26/7 50.3 16.3 42 1890 500

477 19 18.3 1.83 22.4 336.4 26/7 62.7 18.3 46 2277 560

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(3)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof90°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®OHTriplexNeutral-SupportedCableTypeNS75/NS90600 V, aluminum conductor, XLPe insulation, acSR neutral, cSa Listed

Page 21: ELECTRIC UTILITY - STABILOY · ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION march 2012. Electric Utility This catalog

13

Electric Utility Low-Voltage Power Cable

UNJACKETED QUADRUPLEX TYPE NS75/NS90 – XLPE – ACSR FULL SIZE NEUTRAL – 600 VOLTS

PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL

SIZE (AWGORkcmil)

NO. OF WIRES (1)

COND. O.D. (mm)

MIN. INS. THKN. (mm)

NOM. INS. O.D. (mm)

SIZE (AWGORkcmil)

NO. OF WIRES (A1/S1A)

RATED STRENGTH kN(2)

COND. O.D. (mm)

EFFECTIVE O.D. (mm)

APPROX. WEIGHT (kg/km)

AMPACITY (3)

6 7 4.29 1.04 6.63 6 6/1 5.29 5.03 15 224 85

4 7 5.41 1.04 7.75 4 6/1 8.27 6.35 18 335 110

2 7 6.81 1.04 9.14 2 6/1 12.7 8.11 21 507 150

1/0 7 8.53 1.37 11.6 1/0 6/1 19.5 10.1 27 803 200

2/0 7 9.65 1.37 12.6 2/0 6/1 23.6 11.5 30 991 230

3/0 7 10.7 1.37 13.8 3/0 6/1 29.5 12.8 33 1224 265

4/0 7 12.1 1.37 15.2 4/0 6/1 37.1 14.3 36 1519 305

266.8 19 13.6 1.83 17.7 266.8 26/7 50.3 16.3 42 1955 355

336.4 19 15.3 1.83 19.4 336.4 26/7 62.7 18.3 46 2421 410

397.5 19 16.7 1.83 20.8 397.5 26/7 72.5 19.9 50 2828 455

477 19 18.3 1.83 22.4 477 26/7 86.5 21.8 54 3359 510

(1) Forcompactstrandedconstructions,thenumberofwiresmaybereducedasfollows: 19-WireConstructions–18WiresMinimum 37-WireConstructions–35WiresMinimum(2)RatedstrengthsarebasedonCAN/CSAC61089standardcalculationmethod.(3)AmpacityratingisperCeCTable36A,at30°Cambient,withsun-radiatedheatenergyof1025W/m²,awindspeedof

0.6m/s,andmaximumconductortemperatureof90°C.Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

PowrServ®OHQuadruplexNeutral-SupportedCableTypeNS75/NS90600 V, aluminum conductor, XLPe insulation, acSR neutral, cSa Listed