el-mr - dorot control valves · de\ el-mr electrically actuated, manual-reset, deluge valve ... the...

6
Dorot Fire Protection Division Deluge Valves Deluge Valves Certification & compliance by design Typical applications Automatic or Manual actuated Fire Suppression Systems Hangars & Airport terminals Flammable Storage Power Generation, Transformer & Transmission Plants Tunnels Petrochemical, Oil & Gas Installations Onshore-offshore Mining Model 68 DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ANSI FCI 70-2 Class VI seat leakage class UL listed under VLFT category Fire tested to EN ISO 6182-5:2006 SIL 3-4 to IEC 65508/65111 in redundant system configuration Lloyd’s & ABS type approvals Designed for • High-pressure (PN25/375psi), high-flow deluge systems Automatic or local manual emergency actuation • Hazardous-flammable and explosion classified area fire suppression Onshore & Offshore, Naval, Industrial, Commercial & Residential fire suppression Features • Superior design featuring exceptionally low pressure losses at high flow rates • Low to negligible lifelong maintenance costs thanks to no wetted metallic and mechanical moving parts design • Simple, comprised of 3 main parts, no expertise required for maintenance Fresh or Brackish water, seawater and foam Out of box fully assembled & tested valves All valves are factory trimmed for both vertical & horizontal installations without modification • Extensive valve & trim materials selection and corrosion protection coating to EN12944 C4, C5 & C5M 1

Upload: others

Post on 29-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Dorot Fire Protection Division

Deluge Valves

Deluge Valves

Certification & compliance by design

Typical applications

Automatic or Manual actuated Fire Suppression Systems

Hangars & Airport terminals

Flammable Storage

Power Generation, Transformer & Transmission Plants

Tunnels

Petrochemical, Oil & Gas Installations

CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.

The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.

The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.

Please Note:The word "MARINE" should only be used for UL Classified marine products.

200-195D 20M/11/97

Onshore-offshore

Mining

Model 68 DE\ EL-MR

Electrically Actuated, Manual-Reset, Deluge Valve

• ANSI FCI 70-2 Class VI seat leakage class• UL listed under VLFT category• Fire tested to EN ISO 6182-5:2006• SIL 3-4 to IEC 65508/65111 in redundant system

configuration• Lloyd’s & ABS type approvals

Designed for• High-pressure (PN25/375psi), high-flow deluge

systems• Automatic or local manual emergency actuation• Hazardous-flammable and explosion classified

area fire suppression• Onshore & Offshore, Naval, Industrial, Commercial

& Residential fire suppression

Features• Superior design featuring exceptionally low

pressure losses at high flow rates• Low to negligible lifelong maintenance costs

thanks to no wetted metallic and mechanical moving parts design

• Simple, comprised of 3 main parts, no expertise required for maintenance

• Fresh or Brackish water, seawater and foam• Out of box fully assembled & tested valves• All valves are factory trimmed for both vertical &

horizontal installations without modification• Extensive valve & trim materials selection and

corrosion protection coating to EN12944 C4, C5 & C5M1

Page 2: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Deluge Valve

Model 68 DE\EL-MR

2

Manually Actuated Reset to Close

Standby Position Electrically Actuated

General description and operation modes

This electrically actuated, manual-reset deluge valve is designed for fire protection systems controlled by a fire alarm control panel (F&G panel) and actuated by a solenoid valve acting as the automatic release device.The basic control valve type used in this deluge system is a direct-sealing elastomeric diaphragm, hydraulically operated control valve engineered specifically for fire protection systems. The system includes a 2/2-way N.C. solenoid as the interface between the fire alarm control panel - monitoring heat, smoke or flames - and the deluge valve.In the stand-by position, the deluge valve is held closed by the upstream water pressure, trapped in the valve's control chamber. The water pressure enters the control chamber through the priming line ball valve [2], a Y-Type strainer [3], a check valve [4] and a DMR (Dorot Manual Reset latching device) [5].Under fire conditions, a fire alarm control panel energizes the 2/2-way N.C. solenoid [9] (or de-energizes the coil of a continuously energized ED 100% normally open solenoid for SIL 3-4 rated systems). Water is drained from the deluge valve’s control chamber through the 2/2-way N.C. solenoid [9]. The deluge valve opens instantly and allows water to flow into the pipeline and through the open sprinklers over the protected area.Manual emergency actuation is enabled by opening the emergency manual activation valve [6]. The deluge valve opens instantly and allows water to flow into the pipeline and through the open sprinklers over the protected area.When the valve trips open, the DMR [5] isolates the control chamber from the upstream pressure source. Reconnecting the upstream pressure to enable the deluge valve to close can only be achieved by pressing the DMR’s [5] knob.Resetting, maintenance and periodic testing instructions must be followed as described in detail in the relevant Dorot DE\EL-MR model's IOM (Installation, Operation & Maintenance) manual.

68-DE\EL-MR

F&G

F&G

F&G

F&G

68-DE\EL-MR

F&G

F&G

F&G

F&G

68-DE\EL-MR

F&G

F&G

F&G

F&G

68-DE\EL-MR

F&G

F&G

F&G

F&G

Water Water

Sensor Line

To System

Sensor Line

Sensor Line

Sensor Line

Water To System Water

Press

[6]

[1]

[9]

[2] [3] [4][5]

[6]

[1]

[9]

[2] [3] [4][5]

[6]

[1]

[9]

[2] [3] [4] [5]

[6]

[1]

[9]

[2] [3] [4][5]

Page 3: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Deluge Valve

Model 68 DE\EL-MR

Typical control trim materials

3

2

7

3

4

1

9

8

5

6

2

7

3

4

1

9

8

5

6

68-DE\EL-MRID Description1 S-68 Control Valve2 Ball Valve3 Y Control Filter4 Check Valve5 Dorot Latching & Manual Reset device6 Emergency manual activation Valve7 1/2" Drip Valve8 Pressure Gauge9 2way, 1/2" Solenoid Valve

ID Description Standard POG (1) Applications

1 Valve body See Series 100 Engineering data (2)

2 Ball valve Brass \ SST ball SST316

3 Y-Type strainer Brass \ SST screen SST316

4 Check valve Brass SST316

5 DMR (manual-reset device) Brass SST316

6 Manual emergency valve Brass SST316

7 Drip valve Brass SST316

8 Pressure gauge Brass case \ SST connection SST316

9 2/2-way N.C. solenoid (3) Brass SST316

(1) Petrochemical, Oil & Gas(2) Refer to material selection guidelines,

Engineering Data - Materials:Ductile Iron A-536 65-45-12;Cast Steel A-216 WCB;Cast Steel A-352 LCB;Austenitic Stainless-Steel A-351/CF8M;Super Duplex 2507;Nickel-Aluminum-Bronze B-148 UNS C95800

(3) Refer to solenoid selection guidelines

Page 4: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Deluge Valve

Model 68 DE\EL-MR

4

General arrangement and valve dimensions

Valve 2 (50) 2.5 (65) 3 (80) 4 (100) 6 (150) 8 (200) 10 (250)inch mm inch mm inch mm inch mm inch mm inch mm inch mm

A 95/8 243 93/16 233 123/16 310 14 356 173/16 436 207/8 530 25 635AG(1) 95/8 243 10 253 133/16 336 15 380 175/16 440 217/8 556 N/A

B 65/8 168 73/8 185 77/8 200 93/8 238 121/8 306 143/16 360 167/8 430C 413/16 122 413/16 122 61/8 155 6 154 711/16 198 93/8 238 115/16 287D 511/16 145 511/16 145 511/16 145 511/16 145 65/16 160 77/8 200 913/16 249E 911/16 247 911/16 247 123/8 313 123/8 309 153/8 392 165/16 412 171/8 435F 103/8 262 911/16 262 103/8 262 103/8 262 103/8 262 103/8 265 121/2 317

Approx. Weight

Ibs kg Ibs kg Ibs kg Ibs kg Ibs kg Ibs kg Ibs kg35 16 35 16 77 35 95 43 176 80 282 128 430 195

* Dimensions are approximate(1) Grooved model length

CONTROL VALVES

SST

190

CONTROL VALVES

Brass

247

CONTROL VALVES

E

B

DC

F

A

DE-EL-MR

CONTROL VALVES

E

B

DC

F

A

DE-EL-MR

CONTROL VALVES

E

B

DC

F

A

DE-EL-MR

Optional Upstream Drain Valve

Page 5: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Deluge Valve

Model 68 DE\EL-MR

5

Typical system layoutDorot’s DE\EL-MR, electrically actuated, manual-reset deluge valve is held shut drip-tight in its standby position. When a fire alarm control panel energizes the 2/2 way N.C. solenoid (or de-energizes the coil of a continuously energized ED 100% normally open solenoid for SIL 3-4 rated systems), the deluge valve's control chamber is vented. The DMR latches the deluge valve open, allowing water to flow into all of the open sprinklers over the protected area.

13

DMR

2

4

5

Fire alarm control panel3

Electrically actuated, manual-reset, deluge valve

1

DMR (latching manual-reset device)2

2/2-way N.C. solenoid4

Heat/smoke/other detectors5

Page 6: EL-MR - Dorot Control Valves · DE\ EL-MR Electrically Actuated, Manual-Reset, Deluge Valve ... The basic control valve type used in this deluge system is a direct-sealing elastomeric

Deluge Valve

Model 68 DE\EL-MR

Ed

itio

n 1

2.20

19

6

Dorot Control Valves www.dorot.come-mail: [email protected]

Dorot & Dorot companies worldwide reserve the right to make changes without notice including product specification and configuration, content, description(s), dimensions etc. The Information herein is subject to change without notice. Dorot shall not be held liable for any errors. All rights reserved. © Copyright by Dorot.

Ordering guide

Specification for engineers The deluge valve shall be hydraulically operated, direct elastomeric diaphragm-seal, single chamber weir type. The valve shall consist of three major components: the body, cover and the diaphragm assembly. The diaphragm shall be the only moving part. The diaphragm forms a sealed control chamber in the upper portion of the valve, separating operating pressure from line pressure. Packing glands’ stuffing boxes and dynamic o-ring seals are not permitted and there shall be no shafts, discs, bearings or pistons operating the main valve. No hourglass-shaped disc retainers shall be permitted and no V-type, U-type or other slotted type disc guides shall be used. The valve shall contain a nylon reinforced rubber diaphragm, elastic & resilient through its entire surface without vulcanized radial discs and/or reinforcements. The diaphragm shall not be guided by any shafts or bearings and shall not be in close contact with other valve parts except for its sealing surface. Maintenance, disassembly and reassembly of all the valve’s components shall be made possible on site and in-line, without the need to remove the valve from the line. Standard material valves such as Ductile Iron (ASTM A-536 65-45-12) and Cast Steel (WCB A-216) should be coated with high-built fusion-bonded epoxy (FBE) and a UV protective topcoat conforming to EN12944 C4 & C5 high & very high corrosivity protection grades. Naval quality/very high corrosivity protection grade conforming to EN12944 C5M is available upon request. Other coating standards such as NORSOK or ANSI/NACE as well as coatings for special material valves such as austenitic Stainless Steel (CF8M/ASTM A-316 ) and Nickel Aluminum Bronze (ASTM B-148) can be supplied upon request. The valve should be UL listed under category VLFT for fire protection service.

68 P SS - 3 - AN15RF - DE\EL\MR - S - PI-HA-...

Model 68 68 Optional add-on

Optional add-on PI Pressure switch

Spring P HA Alarm test trim

Position Indicator I UV Upstream drain valve

Material LS Limit-proximity switch

Ductile Iron Ex Explosion-proof

Cast Steel CS Trim

CF8M (SST316) SS Brass-Copper

Ni-Al-Br NAB S Stainless Steel 316

Size (inch) 2”-24” X Other

Control function

End connection standard

AN15RF ANSI #150 (FF or RF)

AN30RF ANSI #300 (FF or RF)

GRV Grooved

ISO PN16 ISO PN16

ISO PN25 ISO PN25

xxx Other (specify)

Ordering example: 68PSS-3-AN15RF-DE\EL\MR-S-PI-HA

Technical data:• Media up to 80°C = 176°F• Elastomers suitable for extreme climates are

available upon request.

Sizes:• Straight Flow: 2”-24”• Angle: 1.5” - 8”

UL listed sizes:• Model 68: 2”-10”

End connections:• Flanged:

ISO PN10, ISO-PN16 & ISO-PN25 ANSI B16.42 Class # 150 and # 300 AS Tables D & E, JIS Additional options available upon request

• Grooved: Sizes: 2”-8”

Pressure rating:• 250 psi for Class #150• 375 psi for Class #300

Please specify in addition to the above:• Electrical features other than standard (24VDC, IP65/NEMA4)• If explosion-proof accessories are required such as solenoids,

pressure switches, etc., please define classification.• Control trim material other than standard• Required standards, certifications and approval Standard- leave empty