earthing in electrical network
DESCRIPTION
Earthing of electrical house hold items and industrial earthingTRANSCRIPT
EARTHING
To save human life from danger of electrical shock or deathTo protect buildings, machinery &
appliances under fault conditions.To ensure that all exposed conductive parts do not reach a dangerous
potential.To provide safe path to dissipate
lightning and short circuit currents.To maintain the line voltage constant to
prevent over current or excessive voltage on the appliances or equipment .
Earth Resistance Value
Major power station= 0.5 Ohm.Major Sub-stations= 1.0 OhmMinor Sub-station = 2 OhmNeutral Bushing. =2 OhmService connection = 4 OhmMedium Voltage Network =2 OhmL.T.Lightening Arrestor= 4 OhmL.T.Pole= 5 OhmH.T.Pole =10 OhmTower =20-30 Ohm
Nos. of Earthing
Single phase 1 HP motor –01 earth Socket/geyser/heater/fan/1phase
appliance–01 earth Three phase
motor/generator/transformer/gadgets –02 earth
Metallic support of O/H line after every 03 poles –02 earth
Stay wire for overhead line -01 earthNeutral and frame earthing-separately
While doing Earthing
Distance –from the equipment not more than 1.5 meter
Cross section of earth continuity conductor-not less than 14 SWG copper wire
Cross section of earth wire-not less than half of the main wire
Voltage between Earth Pit conductors to Neutral of Mains Supply 220V AC 50 Hz it should be less than 2.0 Volts.
Factors Affecting Earth Resistance
Soil resistivity Soil condition Moisture Dissolved saltsClimate conditionsPhysical composition Location of earth pit Effect of grain size Effect of current magnitude Area available
Type Of Earthing
Plate earthing :where digging is easy
Pipe earthing :very common, used for domestic, small substations
Strip earthing :where earth bed have rocky soil
Rod earthing: done is sandy area/small lamp post
Pipe Earthing
GI pipe [C-class] of 75 mm diameter
10 feet long welded with welded flat having 4 numbers of holes for connections
Earth pits are generally filled with alternate layer of charcoal & salt or earth reactivation compound.
Strip Earthing
Strip earthing :where earth bed have rocky soil
Copper strip size 5 SWG or 25mmX1.6mm is buried in horizontal trenches
Earth resistance remains high i.e. 5 ohm
Plate Earthing
Cast iron plate of size 600 mm x600 mm x12 mm. OR
Galvanized iron plate of size 600 mm x600 mm x6 mm. OR
Copper plate of size 600 mm * 600 mm * 3.15 mm
Plate burred at the depth of 8 feet in the vertical position and GI strip of size 50 mmx6 mm bolted with the plate is brought up to the ground level.
Earth pit are generally filled with alternate layer of charcoal & salt up to 4 feet from the bottom of the pit.
Insulation Resistance and Megger
Earth resistance test
Three point method
The distance of Current Spike from Earth Electrode D = 60 ft, Then, distance of Potential Spike would be 62 % of D = 0.62D i.e. 0.62 x 60 ft = 37 ft.
Difference between Insulation Resistance and Earth resistance Insulation
Resistance :measured between earth and conductor, value in tens/thousand/mega ohm, in built DC generator
Earth resistance: measured for a earthed body or neutral point by earth resistance tester, value less than 10 ohm
Specification Of Earthing as per ISI
Sr. Capacity Size of earth wire Size Of Earth Electrode
Cu GI Cu GI
1 01- 10 HP 8 SWG 8 SWG 60cmX60cmX3.18mm 60cmX60cmX6.35mm
2 10 – 15 HP 8 SWG 6 SWG 60cmX60cmX3.18mm 60cmX60cmX6.35mm
3 15 – 30 HP 6 SWG 4SWG 60cmX60cmX3.18mm 90cmX90cmX6.35mm
4 30 – 50 HP 4SWG 25mmX3 mm 90cmX90cmX6.35mm 90cmX90cmX6.35mm
Method used to reduce earth resistance
Soldering/welding nuts and bolts By pouring water Increase in plate area By pouring salt and charcoal ,ratio 1:5
Depth of plate Installation of parallel electrode
Preventive Maintenance Of Earthing System
Check half yearly in dry season Check for earth pit noRepair of damage/broken pit cover Tighten the earth connectionsReplace broken earth leadsCorroded part change immediately Pass earth conductor through GI pipeMandatory : bi-yearly and recorded
Typical Earthing In House Wiring