TECHNICAL SELECTION

AFO/AFU F06 MOD_A 90 Softwrae version: 2.2.0.0 - 2.2.0.0Report version: 1.0.1.0DB version: 1.15.0.0User: ELVIS LIIVAKANT

The perfomances mentioned above is obtained by means of theoretical calculations and they are affected by consequent tolerances.

GENERAL DATAModel AFO/AFU F06 MOD_A 90Version MOD_AFrame F06Primary circuit type DIRECT EXPANSION WATER COOLED + FREECOOLINGNo. Circuits N° 2Refrigerant R410A

MAIN CIRCUIT

DESIGN CONDITIONSDry bulb temperature °C 24,0Relative humidity % 50Altitude m 0Air flow m³/h 24000ESP External Static Pressure Pa 20Outdoor air temperature °C 35,0Condenser's fluid type ETHYLENE GLYCOLGlycol % 35Condenser's inlet fluid temperature °C 40,0Condenser's outlet fluid temperature °C 45,0FC coil's inlet temperature °C 10,0

PERFORMANCES AT DESIGNED CONDITIONSTotal cooling capacity gross kW 93,1Sensible cooling capacity gross kW 86,5Net cooling capacity kW 87,0Net sensible cooling capacity kW 80,4SHR 0,93Total power input (Comp.+fans) kW 30,1EER (Indoor unit) 3,09Outlet air temperature °C 13,3Relative humidity outlet % 94

PERFORMANCES AT FREECOOLING MODE

Freecooling nominal performancesFC total capacity kW 70,3FC sensible capacity kW 70,3FC coil's inlet temperature °C 10,0FC Coil's fluid flow m³/h 23,0Fluid pressure drop Freecooling mode kPa 144FC outdoor air temperature °C 6,6Air temperature outlet °C 15,3Relative humidity outlet % 86

100% Freecooling performancesFC total capacity kW 93,1FC sensible capacity kW 84,7FC coil's inlet temperature °C 6,6FC Coil's fluid flow m³/h 23,0Fluid pressure drop Freecooling mode kPa 144FC outdoor air temperature °C 2,0Air temperature outlet °C 13,5Humidity ratio outlet % 92

Page 1 / 3

Page 2: TECHNICAL SELECTION - AFO/AFU F06 MOD A 90 · TECHNICAL SELECTION AFO/AFU F06 MOD_A 90 Softwrae version: 2.2.0.0 - 2.2.0.0 Report version: 1.0.1.0 DB version: 1.15.0.0 User: ELVIS

TECHNICAL SELECTION

AFO/AFU F06 MOD_A 90 Softwrae version: 2.2.0.0 - 2.2.0.0Report version: 1.0.1.0DB version: 1.15.0.0User: ELVIS LIIVAKANT

The perfomances mentioned above is obtained by means of theoretical calculations and they are affected by consequent tolerances.

DRYCOOLERCode BDC123m-LTOutdoor air temperature °C 35,0Air flow m³/h 47220Fluid type ETHYLENE GLYCOLGlycol % 35Inlet fluid temperature °C 45,0Outlet fluid temperature °C 40,0Fluid flow m³/h 20,6Fluid pressure drop kPa 46,2Heating capacity kW 108Dimension A mm 3658Dimension B mm 760Dimension H mm 2286Weight kg 601Packaged dimension A mm 4030Packaged dimension B mm 820Packaged dimension H mm 2450Packaged weight kg 700Power supply V/ph/Hz 230/1/50Elettrical power abs. kW 3,60Max absorbed current A 15,7Noise Power dB(A) 87

CONDENSERCondenser's inlet fluid temperature °C 40,0Condenser's outlet fluid temperature °C 45,0Condenser fluid flow m³/h 23,0Fluid pressure drop DX mode kPa 122

COMPRESSORSCompressor type SCROLLCompressors nr. N° 2Compressors power absorbition kW 24,0

FANSFans type EC BASICQuantity N° 3Air flow m³/h 24000Fans power input kW 6,10

ACCESSORIES

FILTERSAccessory filter type G4 filter

ELECTRICAL HEATERHeater description Enhanced electrical heaters 27 kWQuantity N° 1Steps N° 3Elettrical power abs. kW 27,0Max absorbed current (FLA) A 39,0Power supply V/ph/Hz 400/3/50

HUMIDIFIERHumidifier type Humidifier 8 kg/hQuantity N° 1Capacity kg/h 8,0Elettrical power abs. kW 6,00Max absorbed current (FLA) A 8,70Power supply V/ph/Hz 400/3/50

Page 2 / 3

Page 3: TECHNICAL SELECTION - AFO/AFU F06 MOD A 90 · TECHNICAL SELECTION AFO/AFU F06 MOD_A 90 Softwrae version: 2.2.0.0 - 2.2.0.0 Report version: 1.0.1.0 DB version: 1.15.0.0 User: ELVIS

TECHNICAL SELECTION

AFO/AFU F06 MOD_A 90 Softwrae version: 2.2.0.0 - 2.2.0.0Report version: 1.0.1.0DB version: 1.15.0.0User: ELVIS LIIVAKANT

The perfomances mentioned above is obtained by means of theoretical calculations and they are affected by consequent tolerances.

AIR DELIVERYDescription OVER with frontal suction

NOISE DATA

HPAC UNITSpectrum Hz 63 125 250 500 1000 2000 4000 8000 TotNoise Power dB(A) 77 82 88 85 79 80 82 72 88Noise Pressure Level dB(A) 56 61 67 64 58 59 61 51 67Distance m 2,0

DRYCOOLERNoise Power dB(A) 87Noise Pressure dB(A) 65Distance m 2,0

WEIGHT & DIMENSIONSDimension A mm 2650Dimension B mm 790Dimension H mm 1980Weight kg 892Packaged dimension A mm 2710Packaged dimension B mm 850Packaged dimension H mm 2160Packaged weight kg 914

ELECTRICAL DATA (refer to indoor unit)Power supply V/ph/Hz 400/3+N/50Max Electrical power absorbed (FLI) kW 52,1Max absorbed current (FLA) A 89,6Max inrush current (SA) A 230Power input (OI) kW 30,1