LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6 Device path: C:\Siemens\Digsi4\D4PROJ\LT_Jupia\P7DI\GV\SD\00000002 Author: Creation date: 19.07.11 09:43:37 Last modified: 21.07.11 14:16:25 Operating mode: Offline Comment: Setting values in: Primary value description P R I N T - C O N T E N T S 1 Device Configuration 3 2 Configuration - complete (sorted by line) 4 2.1 Indications 4 2.1.1 Device, General Settings 4 2.1.2 Power System Data 1 7 2.1.3 Oscillographic Fault Records 7 2.1.4 Power System Data 2 8 2.1.5 50/51 Phase/Ground Overcurrent 9 2.1.6 67 Directional Phase/Ground Overcurrent 11 2.1.7 Measurement Supervision 15 2.1.8 Control Authorization 16 2.1.9 Control Device 16 2.1.10 Process Data 18 2.1.11 Set Points (Measured Values) 19 2.1.12 Statistics 19 2.1.13 Set Points (Statistic) 19 2.1.14 Threshold-Switch 20 2.2 Commands 21 2.2.1 Control Device 21 2.3 Measured values 22 2.3.1 Measurement 22 2.3.2 Set Points (Measured Values) 24 2.4 Metered values 25 2.4.1 Energy 25 2.4.2 Statistics 25 3 General Device Settings 26 3.1 Group Device, General Settings; Group General 26 4 Power System Data 1 27 SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10 Page 1 of 30

Upload: rogeriojuruaia

Post on 28-Nov-2014

43 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Document

LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6

Device path: C:\Siemens\Digsi4\D4PROJ\LT_Jupia\P7DI\GV\SD\00000002Author: Creation date: 19.07.11 09:43:37Last modified: 21.07.11 14:16:25Operating mode: OfflineComment: Setting values in: Primary value description

P R I N T - C O N T E N T S1 Device Configuration 32 Configuration - complete (sorted by line) 42.1 Indications 42.1.1 Device, General Settings 42.1.2 Power System Data 1 72.1.3 Oscillographic Fault Records 72.1.4 Power System Data 2 82.1.5 50/51 Phase/Ground Overcurrent 92.1.6 67 Directional Phase/Ground Overcurrent 112.1.7 Measurement Supervision 152.1.8 Control Authorization 162.1.9 Control Device 162.1.10 Process Data 182.1.11 Set Points (Measured Values) 192.1.12 Statistics 192.1.13 Set Points (Statistic) 192.1.14 Threshold-Switch 202.2 Commands 212.2.1 Control Device 212.3 Measured values 222.3.1 Measurement 222.3.2 Set Points (Measured Values) 242.4 Metered values 252.4.1 Energy 252.4.2 Statistics 253 General Device Settings 263.1 Group Device, General Settings; Group General 264 Power System Data 1 27

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 1 of 30

Page 2: Document

4.1 Group Power System Data 1; Group Power System 274.2 Group Power System Data 1; Group CT's 274.3 Group Power System Data 1; Group VT's 274.4 Group Power System Data 1; Group Breaker 275 Settings groups 285.1 Group Power System Data 2; Group General 285.2 Group 50/51 Phase/Ground Overcurrent; Group General 285.3 Group 50/51 Phase/Ground Overcurrent; Group 50 285.4 Group 50/51 Phase/Ground Overcurrent; Group 50N 285.5 Group 67 Directional Phase/Ground Overcurrent; Group General 295.6 Group 67 Directional Phase/Ground Overcurrent; Group 67 295.7 Group 67 Directional Phase/Ground Overcurrent; Group 67N 295.8 Group Measurement Supervision; Group General 295.9 Group Measurement Supervision; Group MeasSupervision 305.10 Group Measurement Supervision; Group Fuse Fail Mon. 305.11 Group Energy; Group Measurement 30

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 2 of 30

Page 3: Document

1 Device ConfigurationNo. Function Scope

0103 Setting Group Change Option Disabled0104 Oscillographic Fault Records Enabled0112 50/51 Definite Time only0113 50N/51N Definite Time only0115 67, 67-TOC Definite Time only0116 67N, 67N-TOC Definite Time only0127 50 1Ph Disabled0117 Cold Load Pickup Disabled0122 2nd Harmonic Inrush Restraint Disabled0131 (sensitive) Ground fault Disabled0140 46 Negative Sequence Protection Disabled0142 49 Thermal Overload Protection Disabled0150 27, 59 Under/Overvoltage Protection Disabled0154 81 Over/Underfrequency Protection Disabled0170 50BF Breaker Failure Protection Disabled0172 52 Breaker Wear Monitoring Disabled0182 74TC Trip Circuit Supervision Disabled

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 3 of 30

Page 4: Document

2 Configuration - complete (sorted by line)No filter

2.1 Indications

2.1.1 Device, General Settings >Synchronize Internal Real Time Clock Type: SP_Ev - Single point indication event >Reset LED Type: SP - Single point indication Configured to source: BI: H 2 >Back Light on Type: SP - Single point indication Configured to source: BI: H 3 Configured to destination: Operation Buffer: IO Device is Operational and Protecting Type: OUT - Output indication Configured to destination: Operation Buffer: IO At Least 1 Protection Funct. is Active Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO Reset Device Type: OUT - Output indication Configured to destination: Operation Buffer: I Initial Start of Device Type: OUT - Output indication Configured to destination: Operation Buffer: I Reset LED Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: I Resume Type: OUT - Output indication Configured to destination: Operation Buffer: I Clock Synchronization Error Type: OUT - Output indication Configured to destination: Operation Buffer: IO Daylight Saving Time

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 4 of 30

Page 5: Document

Type: OUT - Output indication Configured to destination: Operation Buffer: IO Event lost Type: OUT_Ev - Output indication event Configured to destination: Operation Buffer: I Flag Lost Type: OUT - Output indication Configured to destination: Operation Buffer: I Chatter ON Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error with a summary alarm Type: OUT - Output indication Configured to destination: Operation Buffer: IO Alarm Summary Event Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error 5V Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error 0V Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error -5V Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error Power Supply Type: OUT - Output indication Configured to destination: Operation Buffer: IO Failure: Battery empty Type: OUT - Output indication Configured to destination: Operation Buffer: IO Setting calculation is running Type: OUT - Output indication Configured to destination: Operation Buffer: IO Settings Check Type: OUT - Output indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 5 of 30

Page 6: Document

Level-2 change Type: OUT - Output indication Configured to destination: Operation Buffer: IO Stop data transmission Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO >Stop data transmission Type: SP - Single point indication Configured to destination: CFC Test mode Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO >Test mode Type: SP - Single point indication Feeder GROUNDED Type: IntSP - Internal single point indication Configured to source: CFC Breaker OPENED Type: IntSP - Internal single point indication Configured to source: CFC Hardware Test Mode Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO Clock Synchronization Type: IntSP_Ev - Internal single point indication event Configured to source: CFC Alarm: NO calibration data available Type: OUT - Output indication Configured to destination: Operation Buffer: IO Error: Offset Type: OUT - Output indication Configured to destination: Operation Buffer: IO Warn: Limit of Memory Data exceeded Type: OUT - Output indication Configured to destination: Operation Buffer: IO Warnings: X Warn: Limit of Memory Parameter exceeded Type: OUT - Output indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 6 of 30

Page 7: Document

Configured to destination: Operation Buffer: IO Warnings: X Warn: Limit of Memory Operation exceeded Type: OUT - Output indication Configured to destination: Operation Buffer: IO Warnings: X Warn: Limit of Memory New exceeded Type: OUT - Output indication Configured to destination: Operation Buffer: IO Warnings: X Disturbance CFC Type: OUT - Output indication Configured to destination: Operation Buffer: IO Warnings: X

2.1.2 Power System Data 1 >Reverse Phase Rotation Type: SP - Single point indication Configured to destination: Operation Buffer: IO Phase rotation ABC Type: OUT - Output indication Configured to destination: Operation Buffer: IO Phase rotation ACB Type: OUT - Output indication Configured to destination: Operation Buffer: IO

2.1.3 Oscillographic Fault Records >Trigger Waveform Capture Type: SP - Single point indication Configured to destination: CFC Waveform data deleted Type: OUT_Ev - Output indication event Configured to destination: Operation Buffer: I Fault Recording Start Type: IntSP - Internal single point indication Configured to source: CFC

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 7 of 30

Page 8: Document

Configured to destination: Operation Buffer: IO Fault recording is running Type: OUT - Output indication

2.1.4 Power System Data 2 >Manual close signal Type: SP - Single point indication >Enable 50/67-(N)-2 (override 79 blk) Type: SP - Single point indication Configured to destination: Operation Buffer: IO Primary fault current Ia Type: VI - Value indication Configured to destination: Trip log: IO Primary fault current Ib Type: VI - Value indication Configured to destination: Trip log: IO Primary fault current Ic Type: VI - Value indication Configured to destination: Trip log: IO Relay PICKUP Type: OUT - Output indication Configured to destination: BO: U 7 Trip log: I Relay GENERAL TRIP command Type: OUT - Output indication Configured to destination: BO: U 1 LED: L 1 Trip log: I CFC Manual close signal detected Type: OUT - Output indication Configured to destination: Operation Buffer: IO >52-a contact (OPEN, if bkr is open) Type: SP - Single point indication Configured to source: BI: H 5 Configured to destination: Operation Buffer: IO >52-b contact (OPEN, if bkr is closed)

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 8 of 30

Page 9: Document

Type: SP - Single point indication Configured to source: BI: H 4 Configured to destination: Operation Buffer: IO Protection ON/OFF (via system port) Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO

2.1.5 50/51 Phase/Ground Overcurrent 50(N)/51(N) O/C PICKUP Type: OUT - Output indication Configured to destination: Trip log: IO 50(N)/51(N) TRIP Type: OUT - Output indication Configured to destination: Trip log: I >BLOCK 50/51 Type: SP - Single point indication >BLOCK 50-2 Type: SP - Single point indication Configured to source: BI: H 1 >BLOCK 50-1 Type: SP - Single point indication 50/51 O/C switched OFF Type: OUT - Output indication Configured to destination: Operation Buffer: IO 50/51 O/C is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 50/51 O/C is ACTIVE Type: OUT - Output indication Configured to destination: Operation Buffer: IO 50/51 Phase A picked up Type: OUT - Output indication Configured to destination: LED: L 2 Trip log: IO 50/51 Phase B picked up Type: OUT - Output indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 9 of 30

Page 10: Document

Configured to destination: LED: L 3 Trip log: IO 50/51 Phase C picked up Type: OUT - Output indication Configured to destination: LED: L 4 Trip log: IO 50-2 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 50-2 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 50-1 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 50-1 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 50-2 Time Out Type: OUT - Output indication 50-1 Time Out Type: OUT - Output indication 50-2 BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 50-1 BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO >BLOCK 50N/51N Type: SP - Single point indication >BLOCK 50N-2 Type: SP - Single point indication Configured to source: BI: H 1 >BLOCK 50N-1 Type: SP - Single point indication 50N/51N is OFF Type: OUT - Output indication Configured to destination:

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 10 of 30

Page 11: Document

Operation Buffer: IO 50N/51N is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 50N/51N is ACTIVE Type: OUT - Output indication Configured to destination: Operation Buffer: IO 50N/51N picked up Type: OUT - Output indication Configured to destination: LED: L 5 Trip log: IO 50N-2 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 50N-2 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 50N-1 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 50N-1 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 50N-2 Time Out Type: OUT - Output indication 50N-1 Time Out Type: OUT - Output indication 50N-2 BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 50N-1 BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO

2.1.6 67 Directional Phase/Ground Overcurrent

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 11 of 30

Page 12: Document

67/67N picked up Type: OUT - Output indication Configured to destination: Trip log: IO 67/67N TRIP Type: OUT - Output indication Configured to destination: Trip log: I >BLOCK 67/67-TOC Type: SP - Single point indication >BLOCK 67-2 Type: SP - Single point indication >BLOCK 67-1 Type: SP - Single point indication 67/67-TOC switched OFF Type: OUT - Output indication Configured to destination: Operation Buffer: IO 67/67-TOC is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 67/67-TOC is ACTIVE Type: OUT - Output indication Configured to destination: Operation Buffer: IO 67-2 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 67-2 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 67-1 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 67-1 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 67/67-TOC Phase A picked up Type: OUT - Output indication Configured to destination: LED: L 2 Trip log: IO 67/67-TOC Phase B picked up

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 12 of 30

Page 13: Document

Type: OUT - Output indication Configured to destination: LED: L 3 Trip log: IO 67/67-TOC Phase C picked up Type: OUT - Output indication Configured to destination: LED: L 4 Trip log: IO 67-2 Time Out Type: OUT - Output indication 67-1 Time Out Type: OUT - Output indication Phase A forward Type: OUT - Output indication Configured to destination: Operation Buffer: I Phase B forward Type: OUT - Output indication Configured to destination: Operation Buffer: I Phase C forward Type: OUT - Output indication Configured to destination: Operation Buffer: I Phase A reverse Type: OUT - Output indication Configured to destination: Operation Buffer: I Phase B reverse Type: OUT - Output indication Configured to destination: Operation Buffer: I Phase C reverse Type: OUT - Output indication Configured to destination: Operation Buffer: I 67-1 is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 67-2 is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO >BLOCK 67N/67N-TOC Type: SP - Single point indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 13 of 30

Page 14: Document

>BLOCK 67N-2 Type: SP - Single point indication >BLOCK 67N-1 Type: SP - Single point indication 67N/67N-TOC switched OFF Type: OUT - Output indication Configured to destination: Operation Buffer: IO 67N/67N-TOC is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 67N/67N-TOC is ACTIVE Type: OUT - Output indication Configured to destination: Operation Buffer: IO 67N-2 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 67N-2 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 67N-1 picked up Type: OUT - Output indication Configured to destination: Trip log: IO 67N-1 TRIP Type: OUT - Output indication Configured to destination: Trip log: I 67N/67N-TOC picked up Type: OUT - Output indication Configured to destination: LED: L 5 Trip log: IO 67N-2 Time Out Type: OUT - Output indication 67N-1 Time Out Type: OUT - Output indication Ground reverse Type: OUT - Output indication Configured to destination: Operation Buffer: I Ground forward Type: OUT - Output indication Configured to destination:

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 14 of 30

Page 15: Document

Operation Buffer: I 67N-2 is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO 67N-1 is BLOCKED Type: OUT - Output indication Configured to destination: Operation Buffer: IO Trip log: IO

2.1.7 Measurement Supervision Failure: Current Summation Type: OUT - Output indication Configured to destination: BO: U 4 LED: U 6 Operation Buffer: IO Failure: Current Balance Type: OUT - Output indication Configured to destination: BO: U 4 LED: U 6 Operation Buffer: IO Failure: Voltage Balance Type: OUT - Output indication Configured to destination: BO: U 4 LED: U 6 Operation Buffer: IO Failure: General Current Supervision Type: OUT - Output indication Configured to destination: Operation Buffer: IO Failure: Phase Sequence Type: OUT - Output indication Configured to destination: Operation Buffer: IO Failure: Phase Sequence Voltage Type: OUT - Output indication Configured to destination: BO: U 4 LED: U 6 Operation Buffer: IO Failure: Phase Sequence Current Type: OUT - Output indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 15 of 30

Page 16: Document

Configured to destination: BO: U 4 LED: U 6 Operation Buffer: IO Measurement Supervision is switched OFF Type: OUT - Output indication Configured to destination: Operation Buffer: IO >Failure: Feeder VT Type: SP - Single point indication Configured to destination: Operation Buffer: IO >Failure: Busbar VT Type: SP - Single point indication Configured to destination: Operation Buffer: IO VT Fuse Failure (alarm >10s) Type: OUT - Output indication Configured to destination: Operation Buffer: IO VT Fuse Failure (alarm instantaneous) Type: OUT - Output indication Configured to destination: Operation Buffer: IO

2.1.8 Control Authorization Controlmode REMOTE Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO Control Authority Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO Controlmode LOCAL Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO

2.1.9 Control Device 52 Breaker Type: DP - Double point indication Configured to source: BI: X 4 Configured to destination: Operation Buffer: IO

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 16 of 30

Page 17: Document

CFC Control Display Default Display Disconnect Switch Type: DP - Double point indication Configured to destination: Operation Buffer: IO CFC Control Display Default Display Ground Switch Type: DP - Double point indication Configured to destination: Operation Buffer: IO CFC Control Display Default Display Interlocking: 52 Open Type: IntSP - Internal single point indication Configured to source: CFC Interlocking: 52 Close Type: IntSP - Internal single point indication Configured to source: CFC Interlocking: Disconnect switch Open Type: IntSP - Internal single point indication Configured to source: CFC Interlocking: Disconnect switch Close Type: IntSP - Internal single point indication Configured to source: CFC Interlocking: Ground switch Open Type: IntSP - Internal single point indication Configured to source: CFC Interlocking: Ground switch Close Type: IntSP - Internal single point indication Configured to source: CFC Unlock data transmission via BI Type: IntSP - Internal single point indication Configured to source: CFC Q2 Open/Close Type: DP - Double point indication Configured to destination: Operation Buffer: IO

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 17 of 30

Page 18: Document

Q9 Open/Close Type: DP - Double point indication Configured to destination: Operation Buffer: IO Fan ON/OFF Type: DP - Double point indication Configured to destination: Operation Buffer: IO

2.1.10 Process Data >CB ready Spring is charged Type: SP - Single point indication Configured to destination: CFC >Door closed Type: SP - Single point indication Configured to destination: CFC >Cabinet door open Type: SP - Single point indication Configured to destination: Operation Buffer: IO CFC >CB waiting for Spring charged Type: SP - Single point indication Configured to destination: Operation Buffer: IO CFC >No Voltage (Fuse blown) Type: SP - Single point indication Configured to destination: Operation Buffer: IO CFC >Error Motor Voltage Type: SP - Single point indication Configured to destination: Operation Buffer: IO >Error Control Voltage Type: SP - Single point indication Configured to destination: Operation Buffer: IO >SF6-Loss Type: SP - Single point indication Configured to destination: Operation Buffer: IO >Error Meter Type: SP - Single point indication

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 18 of 30

Page 19: Document

Configured to destination: Operation Buffer: IO >Transformer Temperature Type: SP - Single point indication Configured to destination: Operation Buffer: IO >Transformer Danger Type: SP - Single point indication Configured to destination: Operation Buffer: IO

2.1.11 Set Points (Measured Values) Set Point 37-1 Undercurrent alarm Type: OUT - Output indication Configured to source: CFC Configured to destination: Operation Buffer: IO Set Point 55 Power factor alarm Type: OUT - Output indication Configured to source: CFC Configured to destination: Operation Buffer: IO

2.1.12 Statistics Counter of operating hours Type: VI - Value indication >BLOCK Op Counter Type: SP - Single point indication Configured to destination: Operation Buffer: IO Accumulation of interrupted current Ph A Type: VI - Value indication Accumulation of interrupted current Ph B Type: VI - Value indication Accumulation of interrupted current Ph C Type: VI - Value indication

2.1.13 Set Points (Statistic) Set Point Operating Hours Type: OUT - Output indication Configured to destination: Operation Buffer: IO

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 19 of 30

Page 20: Document

2.1.14 Threshold-Switch Threshold Value 1 Type: IntSP - Internal single point indication Configured to destination: Operation Buffer: IO Control Menu

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 20 of 30

Page 21: Document

2.2 Commands

2.2.1 Control Device 52 Breaker Type: CF_D12 - Double command 12, with feedback Configured to destination: BO: Tr 1 CFC Control Display Default Display Control Menu Disconnect Switch Type: CF_D2 - Double command 2, with feedback Configured to destination: CFC Control Display Default Display Control Menu Ground Switch Type: CF_D2 - Double command 2, with feedback Configured to destination: CFC Control Display Default Display Control Menu Q2 Open/Close Type: CF_D2 - Double command 2, with feedback Q9 Open/Close Type: CF_D2 - Double command 2, with feedback Fan ON/OFF Type: CF_D2 - Double command 2, with feedback

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 21 of 30

Page 22: Document

2.3 Measured values

2.3.1 Measurement Ia Type: MV - Measured value Configured to destination: CFC Ib Type: MV - Measured value Configured to destination: CFC Ic Type: MV - Measured value Configured to destination: CFC In Type: MV - Measured value Configured to destination: CFC I1 (positive sequence) Type: MV - Measured value Configured to destination: CFC I2 (negative sequence) Type: MV - Measured value Configured to destination: CFC 3Io (zero sequence) Type: MV - Measured value Configured to destination: CFC Va Type: MV - Measured value Configured to destination: CFC Vb Type: MV - Measured value Configured to destination: CFC Vc Type: MV - Measured value Configured to destination: CFC Va-b Type: MV - Measured value Configured to destination: CFC

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 22 of 30

Page 23: Document

Vb-c Type: MV - Measured value Configured to destination: CFC Vc-a Type: MV - Measured value Configured to destination: CFC VN Type: MV - Measured value Configured to destination: CFC V1 (positive sequence) Type: MV - Measured value Configured to destination: CFC V2 (negative sequence) Type: MV - Measured value Configured to destination: CFC P (active power) Type: MV - Measured value Configured to destination: CFC Q (reactive power) Type: MV - Measured value Configured to destination: CFC S (apparent power) Type: MV - Measured value Configured to destination: CFC Frequency Type: MV - Measured value Configured to destination: CFC Vo (zero sequence) Type: MV - Measured value Configured to destination: CFC Power Factor Type: MV - Measured value Configured to destination: CFC Pa (active power, phase A) Type: MV - Measured value Configured to destination: CFC Pb (active power, phase B)

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 23 of 30

Page 24: Document

Type: MV - Measured value Configured to destination: CFC Pc (active power, phase C) Type: MV - Measured value Configured to destination: CFC Qa (reactive power, phase A) Type: MV - Measured value Configured to destination: CFC Qb (reactive power, phase B) Type: MV - Measured value Configured to destination: CFC Qc (reactive power, phase C) Type: MV - Measured value Configured to destination: CFC Power Factor, phase A Type: MV - Measured value Configured to destination: CFC Power Factor, phase B Type: MV - Measured value Configured to destination: CFC Power Factor, phase C Type: MV - Measured value Configured to destination: CFC

2.3.2 Set Points (Measured Values) 37-1 under current Type: LV - Limit value Configured to destination: Measured value window Set Points(MV) CFC |Power Factor|< Type: LV - Limit value Configured to destination: Measured value window Set Points(MV) CFC

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 24 of 30

Page 25: Document

2.4 Metered values

2.4.1 Energy Wp Forward Type: MVMV - Metered value of measured value Configured to source: Measured value:WpDelta= Configured to destination: Metered value window Wq Forward Type: MVMV - Metered value of measured value Configured to source: Measured value:WqDelta= Configured to destination: Metered value window Wp Reverse Type: MVMV - Metered value of measured value Configured to source: Measured value:WpDelta= Configured to destination: Metered value window Wq Reverse Type: MVMV - Metered value of measured value Configured to source: Measured value:WqDelta= Configured to destination: Metered value window Pulsed Energy Wp (active) Type: PMV - Pulse metered value Configured to destination: Metered value window Pulsed Energy Wq (reactive) Type: PMV - Pulse metered value Configured to destination: Metered value window

2.4.2 Statistics Number of TRIPs= Type: PMV - Pulse metered value

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 25 of 30

Page 26: Document

3 General Device Settings

3.1 Group Device, General Settings; Group GeneralNo. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All0640 Start image Default Display image 1 All

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 26 of 30

Page 27: Document

4 Power System Data 1

4.1 Group Power System Data 1; Group Power SystemNo. Settings Value Group

0214 Rated Frequency 50 Hz All0209 Phase Sequence A B C All0276 Unit of temperature measurement Degree Celsius All0201 CT Starpoint towards Line All0213 VT Connection, three-phase Van, Vbn, Vcn All0240 VT Connection, single-phase NO All0235A Storage of th. Replicas w/o Power Supply NO All0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All0613A 50N/51N/67N Ground Overcurrent with Ignd (measured) All

4.2 Group Power System Data 1; Group CT'sNo. Settings Value Group

0204 CT Rated Primary Current 100 A All0205 CT Rated Secondary Current 5A All0217 Ignd-CT rated primary current 60 A All0218 Ignd-CT rated secondary current 5A All

4.3 Group Power System Data 1; Group VT'sNo. Settings Value Group

0202 Rated Primary Voltage 12,00 kV All0203 Rated Secondary Voltage (L-L) 100 V All0206A Matching ratio Phase-VT To Open-Delta-VT 1,73 All

4.4 Group Power System Data 1; Group BreakerNo. Settings Value Group

0210A Minimum TRIP Command Duration 0,15 sec All0211A Maximum Close Command Duration 1,00 sec All0212 Closed Breaker Min. Current Threshold 4 A All

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 27 of 30

Page 28: Document

5 Settings groups

5.1 Group Power System Data 2; Group GeneralNo. Settings Value Group

1101 Measurem:FullScaleVoltage(Equipm.rating) 12,00 kV A1102 Measurem:FullScaleCurrent(Equipm.rating) 100 A A1108 P,Q operational measured values sign not reversed A

5.2 Group 50/51 Phase/Ground Overcurrent; Group General

No. Settings Value Group

1201 50, 51 Phase Time Overcurrent ON A1213A Manual Close Mode 50-2 instantaneously A1215A 50 Drop-Out Time Delay 0,00 sec A1301 50N, 51N Ground Time Overcurrent ON A1313A Manual Close Mode 50N-2 instantaneously A1315A 50N Drop-Out Time Delay 0,00 sec A

5.3 Group 50/51 Phase/Ground Overcurrent; Group 50No. Settings Value Group

1202 50-2 Pickup 200 A A1203 50-2 Time Delay 0,00 sec A1204 50-1 Pickup 100 A A1205 50-1 Time Delay 0,50 sec A1214A 50-2 active Always A

5.4 Group 50/51 Phase/Ground Overcurrent; Group 50NNo. Settings Value Group

1302 50N-2 Pickup 30 A A1303 50N-2 Time Delay 0,10 sec A1304 50N-1 Pickup 12 A A1305 50N-1 Time Delay 0,50 sec A1314A 50N-2 active Always A

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 28 of 30

Page 29: Document

5.5 Group 67 Directional Phase/Ground Overcurrent; Group General

No. Settings Value Group

1501 67, 67-TOC Phase Time Overcurrent OFF A1513A Manual Close Mode 67-2 instantaneously A1516 Phase Direction Forward A1518A 67 Drop-Out Time Delay 0,00 sec A1519A Rotation Angle of Reference Voltage 45 ° A1601 67N, 67N-TOC Ground Time Overcurrent OFF A1613A Manual Close Mode 67N-2 instantaneously A1616 Ground Direction Forward A1617 Ground Polarization with VN and IN A1618A 67N Drop-Out Time Delay 0,00 sec A1619A Rotation Angle of Reference Voltage -45 ° A

5.6 Group 67 Directional Phase/Ground Overcurrent; Group 67

No. Settings Value Group

1502 67-2 Pickup 200 A A1503 67-2 Time Delay 0,10 sec A1504 67-1 Pickup 100 A A1505 67-1Time Delay 0,50 sec A1514A 67-2 active always A

5.7 Group 67 Directional Phase/Ground Overcurrent; Group 67N

No. Settings Value Group

1602 67N-2 Pickup 30 A A1603 67N-2 Time Delay 0,10 sec A1604 67N-1 Pickup 12 A A1605 67N-1 Time Delay 0,50 sec A1614A 67N-2 active always A

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 29 of 30

Page 30: Document

5.8 Group Measurement Supervision; Group GeneralNo. Settings Value Group

8101 Measurement Supervision ON A5301 Fuse Fail Monitor OFF A

5.9 Group Measurement Supervision; Group MeasSupervisionNo. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 6,0 kV A8103 Balance Factor for Voltage Monitor 0,75 A8104 Current Threshold for Balance Monitoring 50 A A8105 Balance Factor for Current Monitor 0,50 A8106 Summated Current Monitoring Threshold 10 A A8107 Summated Current Monitoring Factor 0,10 A

5.10 Group Measurement Supervision; Group Fuse Fail Mon.No. Settings Value Group

5302 Zero Sequence Voltage 3,6 kV A5303 Residual Current 6 A A

5.11 Group Energy; Group MeasurementNo. Settings Value Group

8315 Meter resolution Standard A

SIMATIC LT_Jupia-Tres_Irmaos_Jup / Folder / 7SJ622 V4.6/7SJ622 21.07.11 14:18:10

Page 30 of 30