dm3000_quick start guide

2
QUICK START GUIDE Caution, Risk of danger – Documentation should be consulted wherever the symbol is used. Caution, Risk of electric shock which can cause severe injury or death. User accessible area is protected through out by DOUBLE INSULATION Measurement category III ISO 14001:2004 Certified ISO 9001:2000 Certified www.conzerv.com Page 1 of 2 DM3000 - 3 f Digital V, A Meters This document is applicable for DM3110 & DM3210 meters invoice + Check our website for latest help, FAQs + Or call our Help desk number 1800 425 0555 (Toll Free) or Call +9180 2852 0604 (Standard Charges Apply) + Question persists? Then send us an email to + Remember to include Model, Serial number, Type of problem, settings & Wiring diagram www.conzerv.com [email protected] Need to know about Refer 1.1 1.2 2.1 2.2 2.3 2.4 3.1 3.2 3.3 List of safety symbols used Safety first Box contents Electrical & Mechanical installations Mechanical dimensions & Panel cut-out Wiring diagrams Intuitive Dual function key Menu Hierarchy Setup Menu - Editing CT/PT ratio + Intended use: DM3000 series meters are designed for use in Industrial & Commercial Installations, not for domestic use. + Building installation shall be included with a disconnecting device like switch or circuit breaker, with clear ON/OFF markings and within close proximity to equipment and the reach of operator, to cut-off the supply mains in case of any hazardous voltages. + The protection provided by the manufacturer will be impaired, if the equipment is not used in the specified manner. + Only qualified and trained personnel should carry out + Installation & wiring + Disconnection & removal of the meter + De-energize the connected circuits before meter installation or Disconnection. + Always use a properly rated voltage sensing device to confirm that all power is off. + Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the DM3000 series meter is installed, disconnect all input and output wires to the meter. High voltage testing may damage electronic components contained in the DM3000 series meter. + During normal operation of this meter, hazardous voltages might be present at the rear terminals, which can cause severe injury or death. + High voltages are likely to be present inside even after the meter has been switched off. + Do not open the cover of the meter – there are no user serviceable parts inside. + Contact your nearest authorized Schneider Electric Conzerv service center for all your servicing requirements. Need help? We are here

Upload: mariavdenet

Post on 02-Apr-2015

127 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: dm3000_quick start guide

QUICK START GUIDE

Caution, Risk of danger – Documentation should be consulted wherever the symbol is used.

Caution, Risk of electric shock which can cause severe injury or death.

User accessible area is protected through out by DOUBLE INSULATION

Measurement category III

ISO 14001:2004 Certified

ISO 9001:2000 Certified

www.conzerv.com

Page 1 of 2

DM3000 - 3 f Digital V, A Meters

This document is applicable for DM3110 & DM3210 meters

invoice

+ Check our website for latest help, FAQs+ Or call our Help desk number 1800 425 0555 (Toll Free) or Call +9180 2852 0604 (Standard Charges Apply)

+ Question persists? Then send us an email to + Remember to include Model, Serial number, Type of problem, settings & Wiring diagram

www.conzerv.com

[email protected]

Need to know about Refer

1.1

1.2

2.1

2.2

2.3

2.4

3.1

3.2

3.3

List of safety symbols used

Safety first

Box contents

Electrical & Mechanical installations

Mechanical dimensions & Panel cut-out

Wiring diagrams

Intuitive Dual function key

Menu Hierarchy

Setup Menu - Editing CT/PT ratio

+ Intended use: DM3000 series meters are designed for use in Industrial & Commercial Installations, not for domestic use. + Building installation shall be included with a disconnecting device like switch or circuit breaker, with clear ON/OFF markings and within close proximity to equipment and the reach of operator, to cut-off the supply mains in case of any hazardous voltages.+ The protection provided by the manufacturer will be impaired, if the equipment is not used in the specified manner.+ Only qualified and trained personnel should carry out

+ Installation & wiring+ Disconnection & removal of the meter

+ De-energize the connected circuits before meter installation or Disconnection.+ Always use a properly rated voltage sensing device to confirm that all power is off.+ Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the DM3000 series meter is installed, disconnect all input and output wires to the meter. High voltage testing may damage electronic components contained in the DM3000 series meter.+ During normal operation of this meter, hazardous voltages might be present at the rear terminals, which can cause severe injury or death. + High voltages are likely to be present inside even after the meter has been switched off.+ Do not open the cover of the meter – there are no user serviceable parts inside. + Contact your nearest authorized Schneider Electric Conzerv service center for all your servicing requirements.

Need help? We are here

Page 2: dm3000_quick start guide

Page 2 of 2

Schneider Electric Conzerv recommends the use of insulated 2sleeved U lugs (2.5 mm ) for wiring terminals. Don’t use pin

lugs which may reduce the safety isolation

3.1 Intuitive Dual function key

3.2 Menu Hierarchy

DM3110 - 3 f Ammeter

DM3210 - 3 f Voltmeter

+ V, A meter: One number+ Quick start guide (QSG): One number+ Test and calibration certificate for the meter: One number

2.1 Box contents

2.2 Electrical & Mechanical installations

2.3 Mechanical dimensions & recommended panel cut-out

2.4 Wiring diagrams

Duration of press

Five seconds

Long press -Two seconds

Short press - Simple one touch

Setup entry

Digit/Value selection to edit in setup

Output

+ Scroll down through the display pages+ Digit/Value editing in setup

+ Connecting cable recommendations

+ Tools & Equipments

Insulation Rating

Voltage Circuit

Current Circuit

> 480 VAC

Current Rating

> 480 VAC

> 0.1 A

> 7.5 A2 Or 2.5 mm minimum

< 5 mm. Diameter = 5 mm or more will get stuck in the safety cover

Tightening Torque: (2.5 to 6) N.mLoosening Torque: (5.5 to 6) N.mTorque greater than 6 N.m may strip the screw or break the safety cover.

V1

V12

V2

V3

V23

V31

A1

A3

A2

SE

C/D

M3

00

0/0

61

0/V

2

Line LoadL1

L2L3

Fuse Fuse

Fuse

0.25 A0.25 A

0.25 A

Aux supply (Control power)

Aux supply (control power)

90 to 300 VAC

90 to 300 VAC

CT

S1

S1

S1

S2

S2

S2

* * * * other meter in series

Line LoadL1L2L3N

Fuse 0.25 A

3.3 Setup Menu - Editing CT/PT ratio V02.01

To edit CT ratioThe following example explains how to set the CT ratio 2500/5 i.e. 0500 in DM3110 Ammeter.

0100 0 100 0 1 00

0 5 00 0500

PASS

Run mode

CT ratio

Short press continuously until

1. From Run mode, press for five seconds.2. The meter flashes CTr and shows the default value 0100 indicating the successful entry to setup mode.3. Long press .4. The display shows 0100 with 0 blinking.5. Long press .6. The display shows 0100 with 1 blinking. 7. Short press four times.8. The display shows 0500 with 5 blinking.9. To accept the new value, long press . 10.The new value is accepted.11.To save the new value, short press .12.The display flashes PASS and come out of the setup mode.

To edit PT ratio

The following example explains how to set the PT ratio 11kV/110 i.e. 100 in DM3210 Voltmeter.

1. From Run mode, press for five seconds.2. The meter flashes PTr and shows the default value 1.000 indicating the successful entry to setup mode.3. Long press four times.4. The display shows 1.000 with last digit/value 0 blinking.5. Long press .6. The display shows 1.000 with “.” blinking. 7. Short press twice to shift the decimal point.8. The display shows 100.0 with “.” blinking.9. To accept the new value, long press . 10.The new value is accepted.11.To save the new value, short press .12.The display flashes PASS and come out of the setup mode.

DM3110 DM3210

- Key Long press

- Key Long press

- Digit/Value selection

- Digit/Value selection

1 - Digit/Value 1 is selected

1 - Digit/Value 1 is selected

- Key Short press

- Key Short press

NOTE:1. The maximum value for PTr and CTr setting is 9999.2. To edit the CTr/PTr values again, long press and repeat the above steps.

Use PT, if VLL > 480V

Not to scale All dimensions in mm

50mA to 6A

VER:xx.xx.xx

S/N: Acc Cl:xxxxxx/xxxxxx-xxxx x.x

0 t o Vac3009 50/60 Hz

VER:xx.xx.xx

80 to 480 Vac(LL)

S/N: Acc Cl:xxxxxx/xxxxxx-xxxx x.x

0 t o Vac3009 50/60 Hz