Sample street lighting calculation report from dialux

TRANSCRIPT

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    PHILIPS SGP551 T-POT A FG / Luminaire Data Sheet

    See our luminaire catalog for an image of the luminaire.

    Luminous emittance 1:

    Luminaire classification according to CIE: 100CIE flux code: 38 75 97 100 81

    Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

    Page 1

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet

    See our luminaire catalog for an image of the luminaire.

    Luminous emittance 1:

    Luminaire classification according to CIE: 100CIE flux code: 37 71 96 100 82

    Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

    Page 2

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet

    See our luminaire catalog for an image of the luminaire.

    Luminous emittance 1:

    Luminaire classification according to CIE: 100CIE flux code: 37 71 96 100 85

    Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

    Page 3

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    10m Corridor - Local Urban Access (Residential) / Planning data

    Street Profile

    Maintenance factor: 0.70

    Cycle Lane (Width: 2.000 m)

    Carriageway (Width: 3.650 m, Number of lanes: 1, tarmac: R3, q0: 0.070)

    Parking Bay (Width: 2.500 m)

    Foot Path (Width: 1.850 m)

    Luminaire Arrangements

    Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities

    at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the

    luminaire installed for use.

    Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.

    Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 42.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m

    Page 4

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    10m Corridor - Local Urban Access (Residential) / Carriageway / Results overview

    Maintenance factor: 0.70 Scale 1:344

    Grid: 14 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)

    Lav [cd/m] U0 Ul TI [%] SR

    Calculated values: 1.17 0.56 0.57 12 0.78Required values according to class: 0.75 0.40 0.50 30 0.50

    Fulfilled/Not fulfilled:

    Assigned Observer (1 Pieces):

    No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]

    1 Observer 1 (-60.000, 1.825, 1.500) 1.17 0.56 0.57 12

    Page 5

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    10m Corridor - Local Urban Access (Residential) / Cycle Lane / Results overview

    Maintenance factor: 0.70 Scale 1:344

    Grid: 14 x 3 Points Accompanying Street Elements: Cycle Lane.Selected Lighting Class: S2 (All lighting performance requirements are met.)

    Eav [lx] Emin [lx]

    Calculated values: 11.73 6.17Required values according to class: 10.00 3.00

    Fulfilled/Not fulfilled:

    Page 6

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    10m Corridor - Local Urban Access (Residential) / Foot Path / Results overview

    Maintenance factor: 0.70 Scale 1:344

    Grid: 14 x 3 Points Accompanying Street Elements: Foot Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)

    Eav [lx] Emin [lx]

    Calculated values: 10.50 3.07Required values according to class: 10.00 3.00

    Fulfilled/Not fulfilled:

    Page 7

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    12m Corridor - Local Urban Access (Residential) / Planning data

    Street Profile

    Maintenance factor: 0.70

    Shared Use Path (Width: 2.500 m)

    Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)

    Lay-by 1 (Width: 2.200 m)

    Sidewalk 1 (Width: 1.300 m)

    Luminaire Arrangements

    Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities

    at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the

    luminaire installed for use.

    Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.

    Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 40.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): 0.004 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m

    Page 8

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    12m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /

    Results overview

    Maintenance factor: 0.70 Scale 1:329

    Grid: 14 x 6 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)

    Lav [cd/m] U0 Ul TI [%] SR

    Calculated values: 1.29 0.48 0.52 15 0.58Required values according to class: 1.25 0.40 0.50 20 0.50

    Fulfilled/Not fulfilled:

    Assigned Observer (2 Pieces):

    No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]

    1 Observer 1 (-60.000, 1.500, 1.500) 1.40 0.49 0.63 10

    2 Observer 3 (-60.000, 4.500, 1.500) 1.29 0.48 0.52 15

    Page 9

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    12m Corridor - Local Urban Access (Residential) / Valuation Field Sidewalk 1 /

    Results overview

    Maintenance factor: 0.70 Scale 1:329

    Grid: 14 x 3 Points Accompanying Street Elements: Sidewalk 1.Selected Lighting Class: S3 (All lighting performance requirements are met.)

    Eav [lx] E

    min [lx]

    Calculated values: 8.18 5.74Required values according to class: 7.50 1.50

    Fulfilled/Not fulfilled:

    Page 10

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    12m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview

    Maintenance factor: 0.70 Scale 1:329

    Grid: 14 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)

    Eav [lx] E

    min [lx]

    Calculated values: 11.03 3.38Required values according to class: 10.00 3.00

    Fulfilled/Not fulfilled:

    Page 11

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    16m Corridor - Local Urban Access (Residential) / Planning data

    Street Profile

    Maintenance factor: 0.70

    Shared Use Path (Width: 2.500 m)

    Parking Bay (Width: 2.500 m)

    Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)

    Parking Bay (Width: 2.500 m)

    Shared Use Path (Width: 2.500 m)

    Luminaire Arrangements

    Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities

    at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the

    luminaire installed for use.

    Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.

    Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 58.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m

    Page 12

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    16m Corridor - Local Urban Access (Residential) / Planning data

    Luminaire Arrangements

    Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities

    at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the

    luminaire installed for use.

    Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.

    Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 58.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m

    Page 13

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    16m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /

    Results overview

    Maintenance factor: 0.70 Scale 1:458

    Grid: 3 x 3 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)

    Lav [cd/m] U0 Ul TI [%] SR

    Calculated values: 1.41 0.66 0.62 13 0.69Required values according to class: 1.25 0.40 0.50 20 0.50

    Fulfilled/Not fulfilled:

    Assigned Observer (2 Pieces):

    No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]

    1 Observer 1 (-60.000, 1.500, 1.500) 1.41 0.66 0.65 9

    2 Observer 3 (-60.000, 4.500, 1.500) 1.43 0.69 0.62 13

    Page 14

  • Project 1

    22.03.2013

    OperatorTelephone

    Faxe-Mail

    16m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview

    Maintenance factor: 0.70 Scale 1:458

    Grid: 20 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance