design of water supply for plumbing
TRANSCRIPT
-
7/30/2019 Design of Water Supply for Plumbing
1/23
Design of WATER SUPPLYFOR plumbing system inbuilding
Engr. Fortunato H. Amosco,fnampap,ce,pme,pee
PSPE-National President
-
7/30/2019 Design of Water Supply for Plumbing
2/23
DESIGN OF WATER SUPPLY SYSTEM
An Application of the Requirements of
Uniform Plumbing Code and or Revised
National Plumbing Codes of the Phils.
DESIGN OBJECTIVES:
The most important design objective in sizing thewater supply system is the satisfactory supply ofpotable water to al fixtures at all times, and atproper pressure and flow rate for normal fixtureoperation. This may be achieved only if adequatesizes of pipes and appurtenances are provided.
The sizes established must be large enough toprevent occurrence of negative pressures in anypart of the system during periods of peak demandinorder to avoid hazard of water supply
-
7/30/2019 Design of Water Supply for Plumbing
3/23
contamination due to backflow andbacksiphonage from potential sources of
pollution. Hence the sizing of building
water supply systems is a matter of vital
concern in protecting health and must be
regulated by codes. Other important
objectives in the design of water supply
system are:
-
7/30/2019 Design of Water Supply for Plumbing
4/23
to achieve economical sizing of piping andeliminate over design.
To provide against potential supply failure dueto gradual reduction of pipe bore with the
passing of time such as may result fromdeposits of corrosion or hard water scale in the
piping. To avoid erosion-corrosion effects and potential
pipe failure or leakage conditions owing tocorrosive characteristics of the water and/or to
excessive design velocities of flow. To eliminate water hammer damage and
objectionable whistling noise effect in thepiping due to excessive design velocity of flow.
-
7/30/2019 Design of Water Supply for Plumbing
5/23
The water supply system should be designed inaccordance with the minimum pressure available at
the public water main, or other source of watersupply pressure, and the minimum pressurerequired at all time at water outlets of the system,
where the pressure at the water main in insufficientto maintain the minimum required at the highest
water outlet of the system, a pressure booster pumpsystem, approved as to the capacity and reliability,or an automatically controlled water supply tank oreither the hydro pneumatic pressure type or the
elevated gravity type should be provided.
As a general rule, the minimum pressurerequired at the ordinary faucet of plumbing
fixture is 8 psi.
-
7/30/2019 Design of Water Supply for Plumbing
6/23
PRELIMINARY INFORMATION
REQUIRED FOR SIZING A SYSTEM:
First, obtain the necessary or all information forestablishing a proper basis for sizing the
building water supply system, such as:
1. The kinds of piping materials to be installed inthe system should be determined. This is a
matter of selection by the ownerof the building
or an authorized representative, who maybe an
Engineer, an architect or a contractor, for anexperienced person who will select the piping
materials, has knowledge and experience about.
-
7/30/2019 Design of Water Supply for Plumbing
7/23
THE SIGNIFICANT
CHARACTERISTICS WHICH MAY BE
APPLIED TO INDICATE WATERCORROSIVELY AND SCALE
TENDENCY FORMING SUCH AS:
pH value CO2 content
dissolved air content
carbonate hardness
Langelier index, and ryznar index
-
7/30/2019 Design of Water Supply for Plumbing
8/23
THE MOST APPROPRIATESOURCE OF THEABOVE MENTIONED IS THE LOCAL WATERAUTHORITY HAVING JURISDICTION OVER
THE SYSTEM SUPPLYING WATER.
2. Location and size of the water supply
3. Developed length of the system
4. Pressure data relative to source of supply
5. Elevations6. Minimum pressure required to the highest outlet
-
7/30/2019 Design of Water Supply for Plumbing
9/23
MANUFACTURERS RECOMMENDATIONS
FOR AVOIDING EROSION-CORROSION:
Velocity limits recommended by pipe manufacturersto avoid accelerated deterioration of their piping
materials due to erosion-corrosion should be
observed. Recent studies have shown that extreme
turbulence accompanying high flow velocities is animportant factor causing erosion-corrosion and that
it is especially prone to occur where the water supply
has high carbon dioxide content (in excess of 10
ppm) and where it has been softened to zero
hardness. Another important factor is very high
temperature (in excess of 150F).
-
7/30/2019 Design of Water Supply for Plumbing
10/23
TO CONTROL EROSION-CORROSION
EFFECTS IN COPPER WATER TUBES, AND
COPPER AND BRASS PIPE, MANUFACTURERS
RECOMMENDATIONS ARE AS FOLLOWS:
Where the water supply has a pH value higher that
6.9 and a positive scale-forming tendency, such as
may be shown by a positive Langelier index, velocityshould be limited to no more than 8 fps. (2.4 mps)
Where water has a pH value lower than 6.9 and may
be classified as aggressively corrosive or where water
supply has been softened to zero hardness by passagethrough a softener, velocity should be limited to no
more than 4 fps (1.2 mps)
-
7/30/2019 Design of Water Supply for Plumbing
11/23
The 4 fps (1. 2mps) velocity limitshould be applied to all not water
piping conveying water at atemperature above 150oF because ofthe accelerated rate of corrosion at such
temperature. q = 60.8 d 21.2 x (P/L)1/2 for across and cover
piping
d = inside dia. If pH value < 6.9 velocity not more than 4bp
pH > 6.9 velocity not more than 6 bps
-
7/30/2019 Design of Water Supply for Plumbing
12/23
Problem No. 1
Given:
WCWater Closet URUrinal
All WC are 1.6 GPF
All UR are 1.0 GPF
Static pressure at meter74 psi
Distance from meter to most remote outlet150ft.
Elevation of highest outlet above meter40ft.
All pipe is L Copper Design velocity per standard8 ft/sec.
Note: Lavatory group and drinking fountains were not
includes in the design as their demands are minimal.
-
7/30/2019 Design of Water Supply for Plumbing
13/23
From Chart: Revised National Plumbing Code of the
Philippines
Tabulation per sample diagram of Sizing Water System
-
7/30/2019 Design of Water Supply for Plumbing
14/23
DRAWING
-
7/30/2019 Design of Water Supply for Plumbing
15/23
Solution: The demand for this system is computed from the
fixture:
1. Unit values given in the tables
Therefore: 15 x 8 fu = 120 fixtures units13 x 5 fu = 65 fixture units
Total demand = 185 fixture units
2. Distance from meter to most remote fixture = 150 ft
3. Elevation of highest outlet above meter = 40 ft
4. Minimum pressure at the meter = 74 psi
5. From table, 185 f.u = 88 GPM; show tabulated
for all pipe runs etc.
6. Determine the total pressure available for friction loss in pound persq.
inch (psi) per 100 feet or pipe
a. Flushometric valve requires a minimum available pressure of 15 psito operate properly.
-
7/30/2019 Design of Water Supply for Plumbing
16/23
Therefore:
Minimum pressure to be maintained =15 psi
b. Total static pressure loss (head loss)This isdetermined by multiplying the elevation distance by 0.433
Therefore:
40 ft x 0.433 psi/ft = 17.2 psi
c. Pressure loss through meter, filters, reducing valves,backflow preventers, etc. In this illustration, we have
chosen a 2 disc meter.This meter has a pressure loss
of 6.5 psi at 85 gpm.
Therefore: Meter loss = 6.5 psi
Total Pressure Loss = 38.7 psi
-
7/30/2019 Design of Water Supply for Plumbing
17/23
Therefore: (minimum static pressureTotal pressure loss)
= 74 psi38.7 psi = 35.3 psi
NOTE:The remaining pressure of 35.3 psi is the maximumamount of pressure we have available for pressure loss dueto
friction in our system while maintaining the minimumpressure of 15 psi at the highest outlet. However, this 35.3psi
of pressure must be distributed throughout the total lengthof the system, which in this case has a total length of 150ft.
Determine now the pressure loss per 100 ft of pipe. Thetotal loss is 35.3 psi for 150 ft. of pipe, we calculate this way:
(100 x 35.3) divided by 150 = 23.53 psi loss per 100 ft of pipe.
-
7/30/2019 Design of Water Supply for Plumbing
18/23
7. From the Copper tubing chart project 23.53
psi up until it intersect with GPM horizontalline as demand. Note that it intersect above
line of velocity of 15 ft/sec., which is almost
16.5 ft/sec. as their rated flow.a. Since recommended velocity is 8ft/sec.,
however, good Engineering practice would
further reduce this to between 4-6 ft/sec. but
since our design call for 8ft/sec, we movefurther along the 8 GPM line until it intersect
with 8 ft./sec.
-
7/30/2019 Design of Water Supply for Plumbing
19/23
b. Note that the intersection of our new point isanother pipe size line. This will be our newstarting point which is pipe size 21/2 dia at 8
ft/sec. the GPM capacity will be 120 GPM.Going down to our 8 ft/sec transverse line as itintersect with the 2 line, the maximum GPMis:
2 pipe = 73 GPM
1 = 42 GOM
1 = 10 GPM
3/2 = 12 GPM
Note that as we follow the line to below 1 there
are three dotted lines.
-
7/30/2019 Design of Water Supply for Plumbing
20/23
-
7/30/2019 Design of Water Supply for Plumbing
21/23
-
7/30/2019 Design of Water Supply for Plumbing
22/23
These represent wall thicknesses ofsmaller pipes.
Please note that the charts and tables are
also found in the Uniform Plumbing
Code, and also in our Revised Phil.National
Plumbing Code, however there is no
problem similar or problem with solutionlike what I have discussed today.
-
7/30/2019 Design of Water Supply for Plumbing
23/23
Thank you. Good day!
God Bless Us!