S eco Bloc IEC OEM Modules 3.3kV - 17.5kV, Type BC & BV GE Industrial Solutions The next generation of reliability, performance and sustainability

Upload: others

Post on 05-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

SecoBloc IEC OEM Modules3.3kV - 17.5kV, Type BC & BV

GEIndustrial Solutions

The next generation of reliability, performance and sustainability

Page 2: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

2

GEGE is a diversified organization covering myriad market segments, including infrastructure and finance. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide.

The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896.

Industrial SolutionsIndustrial Solutions, a GE heritage business, is leading the future of electrifica-tion with advanced technologies that protect and control the distribution of electricity throughout a facility’s infrastructure. We provide customers across various industries with end-to-end product and service solutions that ensure the reliability and protection of the electrical infrastructure; from the substation, to a facility’s critical equipment, and all the power technologies in between.

Honors

2013 World’s Most Admired Companies 2010 World’s Most Innovative Companies

2012 Best Global Brand 2012 World’s Most Respected Companies

2010 World’s Most Respected Companies

Page 3: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

3

More Than 90 Years of Interrupter ExperienceGE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined the design and introduced the world’s first 15kV vacuum circuit breaker in the 1960s. This interrupter design has been a world leader in vacuum technology, with over 55 years of reliable field service.

Universal ApplicationsSecoBloc is designed, assembled and tested to meet or exceed applicable IEC standards. It is suitable for applications in all major industries including Transmission and Distribution, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, and Commercial buildings.

SecoBloc provides protection for all types of applications including coble, overhead lines, motors, capacitors, transformers and bus bar sections.

World Class QualityManufactured, assembled and tested all in the same facility, SecoBloc is the product of sophisticated manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification. Precision tooled parts, computer aided design and advanced production techniques, as well as the protection of the ‘E Coat’ (cathodic electro coating) paint process have resulted in a standard of excellence unmatched in the industry.

Environmental ConsciousnessSelecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used instead of SF6 gas for SecoVac series MV embedded pole vacuum circuit breakers.

Page 4: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

4

Page 5: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

5

Table of Contents

SecoBloc OEM Modules Overview and Applications ............6

Type BC and BV 3.3kV – 17.5kV Module Features ..................7

Technical Characteristics

Interlocking Systems ..............................................................................9

Optional Interlocking ...........................................................................10

Environmental Conditions.................................................................11

Construction ............................................................................................11

Standards .................................................................................................11

Selection Table .......................................................................................11

Scope of Supply - Optional Supply Details ...........................12

Technical Data

SecoBloc Type BC and BV Characteristics ................................13

SecoVac Embedded Pole Vacuum Circuit Breaker

Features, Benefits, Applications .....................................................14

Circuit Breaker Characteristics .......................................................15

Internal Wiring Diagram ....................................................................16

Internal Wiring Diagram (UVR) ........................................................17

SecoVac Vacuum Fuse Contactor ..........................................18

Fuse Contactor Characteristics ......................................................18

Internal Wiring Diagram ....................................................................19

Earthing Switch and Disconnect Truck Characteristics .........................................20

Components and Controls ......................................................21

SecoVac Checklist .....................................................................22

SecoVac FC Checklist ...............................................................23

SecoBloc BC and BV Modules Checklist ................................24

Page 6: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

6

SecoBloc OEM modules are designed and manufactured with advanced technology and have been comprehensively and successfully type-tested.

Designed specifically for use by OEM switchgear manufacturers building IEC designs, SecoBloc OEM modules offer greater configuration flexibility than traditional full height sections.

SecoBloc modules are rated for 3.3kV - 17.5kV applications, 630A - 3150A and up to 40kA short circuit rating. They are designed to house GE’s SecoVac embedded pole vacuum circuit breakers.

IEC SecoBloc modules include two different versions. The SecoBloc BV is a complete module that includes the apparatus and lower compartment. The SecoBloc BC module offers an apparatus compartment.

ApplicationsUtilities and Power Plants Power generation stations Transformer stationsSwitching stationsMain and auxiliary switchgear E-House

IndustrialOil & Gas MiningPulp and PaperCementTextilesChemicalsAutomotivePetrochemicalData CentersMetallurgy

TransportationAirportsPortsRailwaysUnderground Transportation

Services Supermarkets Shopping mallsHospitalsLarge infrastructure and civil works

Seco

Bloc

OEM

Mod

ules

Ove

rvie

w a

nd A

pplic

atio

ns

MarineDrilling & ExplorationMerchantCruiseFPSONaval

Page 7: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

7

Features• Air insulated OEM blocs in a compact design• Complete interlocking system to prevent

incorrect operation and to improve safety

• Tested in accordance with the IEC International Standards

• Utilizes embedded pole SecoVac vacuum circuit breakers

• Designed for universal OEM applications

Innovative in design, SecoBloc compact blocs are the next generation of reliability, performance and sustainability from GE. Fully IEC tested to IEC 62271-100 and IEC 62271-200, they meet the requirements of LSC2B. SecoBloc is suited to provide OEMs with a simple, cost effective solution that is easy to order and assemble.

SecoBloc Type BC1 and BV 3.3kV – 17.5kV Modules

3

2

4

5

6

8

9 10

1112

7Upper spout

Lower spout

Earthing switch

Earthing switch drive

Earthing switch lugs

Apparatus compartment door

Emergency trip

Viewing window

Apparatus racking operating aperture

Earthing switch operating aperture

Lower compartment1

Lower compartment door

1

7

2

8

3

9

4

10

5

11

6

12

Control socketControl plug interlock

Wiring duct coverBus bar side shutter

Cable side shutter

Shutter mechanismRail

Service/Test position mechanical indicator

1

7

2

8

3

4

5

6

1

3

2

4

5

6

87

1

1. BC Module does not include lower compartment

Module Interior

Type

BC

and

BV

3.3k

V –

17.5

kV M

odul

e Fe

atur

es

Page 8: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

8

Built to the highest quality standards SecoBloc is designed and fully tested to 2014 IEC standards. It utilizes GE’s latest SecoVac vacuum circuit breaker, third-party tested in accordance with IEC 62271-100. Manufactured in accordance with high quality standards, GE engineers have integrated core technologies. Circuit breaker and mechanism design, vacuum arc control technology, insulation technology and electrical field control and analysis combine to create a highly reliable and compact system. SecoBloc reflects GE’s best MV switchgear design practices.

Construction type and IP rating SecoBloc Type BC/BV is designed and constructed to meet the requirements IEC 62271-200 for Indoor installations. SecoBloc offers IP43 protection from penetration of solid objects and liquids on the front side with its door closed.

Earthing SwitchThe SecoBloc earthing switch can be closed under short-circuit up to 40kA. The earthing switch isolators are provided with a capacitive voltage sensor for connection with the voltage presence indication system.

SecoVac MechanismThe SecoVac circuit breaker utilizes a compact, spring charged operating mechanism. The open and close mecha-nisms are combined into a single, small and easily replaceable module.

Automatic ShuttersThe SecoBloc OEM blocs are equipped with grounded metal shutters in front of the primary bushings. The shutters are automatically operated by the circuit breaker movement. When the circuit breaker is racked out to the test or disconnect positions, the shutters automatically close to isolate the fixed primary contacts. As an option, shutters are available with a safety interlock, which in the absence of a withdrawable apparatus, will prevent manual activation.

Marine ApplicationSecoBloc has been tested for Marine applications according to the IEC 60068-2-6 and IEC 60092-504.

Inclination Test– Determines that SecoBloc can continue operating as intended, even when inclined at an angle up to 25 degrees on all four sides.

Vibration Test - The operating conditions on marine platforms and shipping installations require the capability to work in environments

affected by vibrations. SecoBloc was exposed to a resonance search and endurance random, which consists of a random vibration test according to IACS E10.

Vibration Sweep Test:• From 2 to 13.2 Hz displacement

1.0 (peak value)

• From 13.2 to 100 Hz acceleration amplitude of 0.7 g

• Vibration Endurance Test - 90 minutes

The exposure to these severe service conditions confirms the suitability of SecoBloc to unstable marine conditions. The SecoBloc Marine version includes a handrail in the breaker compartment door as well as doorstoppers.

Type

BC

and

BV

3.3k

V –

17.5

kV M

odul

e Fe

atur

es

Page 9: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

9

Technical CharacteristicsInterlocking SystemsSecoBloc is designed with a number of interlocking systems to help prevent mis-operation:

• The circuit breaker can only be moved from test to connect position and vice versa when the circuit breaker is in the Open position

• The earthing switch cannot be closed when the circuit breaker is in the connect position or in the traveling position between test and connect

• For BV modules, the cable compartment door can only be opened when the earthing switch is closed

• For BV modules, the earthing switch can be opened only when the cable compartment door is closed

• The secondary plug can only be inserted or removed when the circuit breaker is in the test position

• The circuit breaker cannot be closed when it is in-between the connected, test or disconnect positions

• When the circuit breaker is moved from the connect position, the metal shutters will close automatically

• The circuit breaker can only be racked-in when the Apparatus Compartment door is closed

• The Apparatus Compartment door can only be open when the circuit breaker is in test position

Description of Interlock System Key Condition

Functional truck racking-out lock

Key will be free when the truck is in the connected positionKey will be trapped when the truck is in the disconnected/ test position

Functional truck racking-in lock

Key will be free when the truck is in the disconnected/ test positionKey will be trapped when the truck is in the connected position

Earthing switch closing lock

Key will be free when earthing switch is openKey will be trapped when the earthing switch is closed

Earthing switch opening lock

Key will be free when the earthing switch is closedKey will be locked when the earthing switch is open

up/downstream key free with CB withdrawn

key free with CB rack-in from test position

key free with ES close

up/downstream key free with ES Open

Tech

nica

l Cha

ract

eris

tics

Page 10: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

10

Optional InterlockingSecoBloc provides various levels of safety operation with enhanced interlock system.

Category Condition Interlocking TypeSecoBloc 17.5kV

Standard Optional

Apparatus closing & opening

Apparatus could be closed only when:

1 Apparatus in service or test position and not in any intermediate position

Mechanical ✓

Electrical ✓

Apparatus could be opened without conditions.Padlocks allowance

1 Access to open button Padlock ✓

2 Access to close button Padlock ✓

Apparatus racking in/out locking from service to test positions

Apparatus could be Rack-Out from connected to test position only when:

1 Apparatus is openMechanical ✓

Electrical ✓

2 Key-lock A for VCB rack in is turned captive Key ✓

Apparatus could be Rack-In from test to connected position only when:

1 Apparatus is openMechanical ✓

Electrical ✓

2 Apparatus control plug is connected Electrical ✓

3 Earthing switch is openMechanical ✓

Electrical ✓

4 Apparatus compartment door is closedMechanical ✓

Electrical ✓

5 Key-lock B for VCB rack-in is turned captive Key ✓

Padlocks allowance1 Access to insert crank lever Padlock ✓

Earthing Switch closing & opening

Earthing switch could be closed only when:

1 Apparatus in test positionMechanical ✓

Electrical ✓

2 Permissive blocking magnet is energized Electrical ✓

3 Key-lock C for earthing switch is turned captive Key ✓

Earthing switch could be open only when:

1 Cable compartment door closed Mechanical ✓

Electrical ✓

2 Key-lock D for earthing switch is turned captive Key ✓

Padlocks allowance1 Access to insert operation lever Padlock ✓

Apparatus compart-ment door closing & opening

Apparatus compartment door could be opened only when:1 Apparatus in test position Mechanical ✓

Apparatus compartment door could be closed without conditions

Cable compartment door closing & opening

Cable compartment door could be opened only when:1 Earthing switch is closed Mechanical ✓

Cable compartment door could be closed without conditions

Shutters

Shutters could be opened only when:1 Activated by apparatus undercarriage Mechanical ✓

Shutters could be closed without conditions.Padlocks allowance

1 Padlock opening or closing Padlock ✓

Control PlugApparatus control plug could be connected / disconnected only when:

1 Apparatus is in test position Mechanical ✓

Note: Available Key interlocking brands: Castell, Fortress, Ronis

Tech

nica

l Cha

ract

eris

tics

Technical Characteristics

Page 11: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

11

Technical CharacteristicsStorage conditionsIn order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equip-ment is stored in its original packaging, in dry conditions sheltered from the sun and rain between –15°C and + 40°C.

Normal operating conditionsSecoBloc is designed for the normal service conditions in indoor switchgear per IEC Standards:

• Temperature

– Maximum Ambient: +40°C

– Minimum Ambient: -30°C

• Humidity

– Maximum Relative: 95%

• Altitude

– Maximum: 1000m a.s.l.

– High Altitude: At altitudes above 1000m, consult IEC 60071-2 for derating factors applicable to dielectric and current values.

Construction• Indoor construction, up to IP43

• All the metal surfaces in the panels are painted or plated for corrosion protection

• Panels are produced using Alu-Zn steel sheet

IEC StandardsSecoBloc complies with the standards and specification for OEM assembled switchgear and has been tested in accor-dance with the IEC publication below:

• IEC 62271-200: AC Metal enclosed switchgear and control gear for rated voltages above 1kV and up to 52kV

SecoBloc Selection Table Type

Incoming / Feeder Bus Tie

Bus Riser/ Direct Arrival

Bus Bar VT (Measurement)

Single Line Diagram

Lower Compartment Apparatus Compartment

YES(VT Included or VT

Provision or Empty)

SecoVac VB2+ 17.5kVBV-B

N/A

N/A

Disconnect TruckSecoVac FC 12kV BV-C N/AEmpty N/A BV-E

NO

SecoVac VB2+ 17.5kVBC-B

N/ADisconnect TruckSecoVac FC 12kV BV-C

N/AWithdrawable VT Truck N/A BC-VEmpty BC-E N/A

• IEC 62271-102: High-voltage alternating current disconnector and earth switches

• IEC 62271-1: The common specification for high voltage switchgear and control gear standards

• IEC 60529: Degrees of protection as provided by enclosures (IP Code)

• IEC 60068-2-6: Environmental testing - Part 2.6: Test FC Vibration (Sinusoidal)

• IEC 60092-504: Electrical installation in ships - Part 504: special features; control and Instrument

Tech

nica

l Cha

ract

eris

tics

Page 12: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

12

Scope of Supply - Optional Supply DetailsEarthing SwitchOptional supply allows earthing the elements connected to the earthing switch lugs. It is typically used to earth incoming/outgoing power cables. When earthing switch is provided additional elements may also be provided:

• Mechanical interlock that prevents the SecoVac breaker to be racked-in from test to service position with the earthing switch closed, and prevents closing the earthing switch with the SecoVac breaker in service or any intermediate position, can be complemented with an optional supply redundant electrical interlock for the same purpose.

• On BV modules, earthing switch can be provided with a motor that allows opening and closing remotely.

• Voltage sensor is always provided together with the earthing switch and allows the customer to detect the presence of voltage of the elements electrically connected to the earthing switch lugs. Voltage sensor requires a voltage indicator display.

Emergency Pushbutton• Provides a mechanical trip of the circuit breaker with the SecoBloc module

apparatus door closed. It is typically used to open the breaker in case of loss of auxiliary voltage.

Marine Options• Handrails and door stoppers: Located in the apparatus compartment door

and door stoppers for the SecoBloc BC or BV module

• IP43 Cover: Metallic cover for the ESW operating aperture. The front side of the SecoBloc module achieves Ingress Protection Degree IP43.

Voltage TransformersSecondary windings, connection, accuracy class can be configured from multiple options

Mechanical InterlocksOptional safety interlocks for increased operational safety:

• Shutter Interlock: Prevents manual activation of the shutters, which will be only activated by the apparatus truck.

Key InterlocksKey interlocks provide the capability to have operation logic between multiple SecoBloc modules or upstream/downstream elements of the system. Available selections include Castell, Fortress and Ronis commercial brands.

• ESW Key Interlock: Up to two locks are available for the earthing switch. Either one or both of the two locks can be configured, providing multiple possible combinations for the condition of the key, trapped or released, when the ESW is in open position.

• VCB Key Interlock: Up to two locks are available for the VCB condition. Either one or both of the two locks can be configured, providing multiple possible combinations for the condition of the key, trapped or released, when the VCB is in test position.

Scop

e of

Sup

ply

- O

ptio

nal S

uppl

y D

etai

ls

Page 13: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

13

Technical DataSecoBloc Type BC and BV Characteristics Module Type SecoBloc BC SecoBloc BVRated Voltage (kV) 7.2 / 12 /15 / 17.5 7.2 / 12 /15 / 17.5

Rated Insulation LevelPower Frequency Withstand Voltage (kV) 20 / 28 / 36 / 38 20 / 28 / 36 / 38

Lightning Impulse Withstand Voltage (kV) 60 / 75 / 95 / 95 60 / 75 / 95 / 95

Rated Current (A at 40º)

630 ✓ ✓

1250 ✓ ✓

1600 ✓ ✓

2000 ✓ ✓

2500 ✓ ✓

3150 ✓ ✓

Breaking Capacity (kA)25 ✓ ✓

31.5 ✓ ✓ ✓ ✓ ✓ ✓

40 ✓ ✓ ✓ ✓

Short time Withstand Current (kA/3s)25 ✓ ✓

31.5 ✓ ✓ ✓ ✓ ✓ ✓

40 ✓ ✓ ✓ ✓

Dimensions (mm)Width [A] 600 750 1000 600 750 1000Height [B] 1135 1135 1135 1680 1680 1680Total Depth [C] 1055 1043 1043 1055 1043 1043Earthing Switch Lug Depth [D] 1003 991 991 1003 991 991Module Depth [E] 716 704 704 716 704 704Distance Between Phases 150 210 275 150 210 275Weight (kg)Estimated Weight 200 300 400 250 350 450

Side/Front View

E

B

DC

AE

B

DC

A

A

E

E

D

D

C

C

B

B

Type BC

Type BV

Tech

nica

l Dat

a

Page 14: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

14

SecoVac Embedded Pole Vacuum Circuit Breaker Reliability and high performance in a compact package

Modular design

Features and benefits• Environmentally friendly design

• Conformance to the current 2014 IEC standards

• Numerous safety features for maximum personnel protection

• User friendly operation with easy access and minimal inspection required

• Compact and cost effective

• Flexible with a full line of accessories and OEM Solution

Applications• Serving global 50 Hz and 60 Hz systems

• All segments of the electrical industry: industrial, commercial, utility, mining, marine and off-shore

• Protecting transformers, capacitor banks, motors, busbar sections and cables

• Contact GE sales office for special environment conditions: shock, vibration and high ambient temperature

Operation ToolRack handle for truck

Earthing switch handle

Seco

Vac

Embe

dded

Pol

e Va

cuum

Circ

uit B

reak

er

Page 15: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

15

Type Name (GE) Rated Voltage Resistance Value (Ω) Rated Current (A) Inrush Current (A) Maximum Power (W)P-CAX 120 Vac 45 2.78 16.67 347.22P-CBX 240 Vac 320 0.72 - 0.75 4.32 - 4.5 165.89 - 180P-C5X 36 Vdc 3.12 11.54 69.23 415.38P-C6X 48 Vdc 3.1 15.48 92.9 743.23P-C7X 60 Vdc 10.78 5.57 33.4 333.95P-C1X 110 Vdc 51 2.16 12.94 237.25P-C2X 220 Vdc 198 1.11 6.67 244.44

Rated Voltage (V) Normal Operation Voltage Range (%) Charging Time at Rated Voltage (s) Input Power (W)110 Vac 85 - 110 < 15s 150125 Vac 85 - 110 < 15s 150220 Vac 85 - 110 < 15s 150230 - 240 Vac 85 - 110 < 15s 15024 Vdc 85 - 110 < 15s 15030 Vdc 85 - 110 < 15s 15048 Vdc 85 - 110 < 15s 15060 Vdc 85 - 110 < 15s 150110 Vdc 85 - 110 < 15s 150125 Vdc 85 - 110 < 15s 150220 Vdc 85 - 110 < 15s 150230 - 240 Vdc 85 - 110 < 15s 150

Item ValueRated Current (A) 1250~1600 2000~4000Resistance (μΩ) ≤ 45 ≤ 25

Coil Characteristics

Motor Characteristics

Main Circuit Resistance

Circuit Breaker CharacteristicsSpecifications DataRated Voltage (kV) 7.2 / 12 / 15 / 17.5Rated Power Frequency Withstand Voltage (1 min) (kV) 20 / 28 / 36 / 38Rated Lightning Impulse Withstand Voltage (1.2/50μs) (kVp) 60 / 75 / 95 / 95Rated Frequency (Hz) 50 / 60Rated Current (A) 630 / 1250 / 1600 / 2000 / 2500 / 3150Rated Short-circuit Breaking Current (kA) 25 / 31.5 / 40Percentage of DC Component Up to 50%Rated Short-circuit Closing Current (kAp) 65 / 82 / 104Rated Short-time Withstand Current (kA) 25 / 31.5 / 40Rated Peak Value Withstand Current (kAp) 65 / 82 / 104Rated Duration Time for Short-circuit (s) 3Opening Time (ms) 20 ~ 50Closing Time (ms) 30 ~ 70Rated Auxiliary Control Voltage (V) 36 / 48 / 60 / 110 / 220 Vdc - 110 / 220 VacOperation Sequence O – 0.3s – CO – 180s – CO / O – 0.3s - CO – 15s – COMechanical Life Operations (Quantity) 15.000 (M2)Electrical Endurance Class E2Single Capacitor Bank Switching Current (A) 400Rating Earthing Switch Short-time Withstand Current (kA 1s) 40

Seco

Vac

Embe

dded

Pol

e Va

cuum

Circ

uit B

reak

er

Page 16: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

16

S9: Limit switch (connected position) CC: Closing coil KO: Anti-pumping relay (optional)

S8: Limit switch (test position) TC: Trip coil BC: Electromagnet for locking (optional)

S4: Electromagnet for locking auxiliary switch M: Spring charge motor ZC: Electromagnet for locking truck (optional)

S5: Auxiliary switch V1–V4: Rectifier

S1–S3: Energy storing limit switch

Notes:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.3. Rectifier will be removed if DC supply voltage is being used.

SecoVac Vacuum Circuit Breaker Internal Wiring Diagram

Spar

e Pa

rts

SecoGear 3.3kV-27kV Air Insulated Switchgear

S9

512221

44S522 S5

4321

13

14

11

1250 4914 48 58 56

81

82S514

13

S5

14S8 S8

34 24S8

13 33 23

S854

53

2434

33 23

S9 54

53

S9 S9

2 474 57 55

36 34 35 20

(21)(13)(21)

S3(14)S3(22) S1(22)

(52)

(51)

V1

2426 25

V2

Spring Charge Motor Closing Circuit

10

53 54 31 32

S844

43

44 S9

43

371513 1917 33 3938

S4

S5(74)

S5(54)

(2)(5)

(3)K0

(53)

S5

(73)

(12)

(11)

S5

(13)

(14) S2

CCK0

TC

6472 624232

4131 6371 61

8424 34

8323 33

S5

V4 V3

Breaker Interlock Circuit

52

Opening Circuit

30 273 5 97 23 2928

92

91

94

93

16

6

18

8

40

Truck Interlock Circuit

1

M BC

A~

D~

2

1

C+ B-

ZC

V5

Y4

SecoVac Vacuum Circuit Breaker Internal wiring diagram (AC) 17.5kV/27kV

S9: Limit switch (working position) CC: Closing coil KO: Anti-pumping relay (optional)

S8: Limit switch (testing position) TC: Trip coil BC: Electromagnet for locking (optional)

S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor ZC: Electomagnet for locking truck (optional)

S5: Auxiliary switch V1~V4: Rectitier

S1~S3: Energy storing travel switch

Note:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.

Spring Charge Motor Closing Circuit Opening CircuitBreaker Interlock Circuit Truck Interlock Circuit

Seco

Vac

Embe

dded

Pol

e Va

cuum

Circ

uit B

reak

er

Page 17: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

17

S9: Limit switch (connected position) CC: Closing coil UM: UVR

S8: Limit switch (test position) TC: Trip coil KO: Anti-pumping relay (optional)

S4: Electromagnet for locking auxiliary switch M: Spring charge motor ZC: Electromagnet for locking truck (optional)

S5: Auxiliary switch MM: UVR PCB (optional) V1–V4: Rectifier

S1–S3: Energy storing travel switch BC: Electromagnet for locking (optional)

Notes:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.

SecoVac Vacuum Circuit Breaker Internal Wiring Diagram (UVR)

Spar

e Pa

rts

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoVac Vacuum Circuit Breaker Internal wiring diagram (AC) 17.5kV/27kV (with UVB)

S9: Limit switch (service position) CC: Closing coil UM: UVR

S8: Limit switch (test position) TC: Opening coil

S4: Electromagnet for locking's A.S. M: Motor K0: Anti-pumping relay (optional)

S1~S3: Energy storing travel switch MM:UVR PCB(optional) ZC: Electromagnet for locking truck(optional)

S5: Auxiliary switch BC: Electromagnet for locking (optional)

Note:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.

S9

44 512221

44S522 S5

4321

13

14

43 11

1250 4914 48 58 56

81

82S514

13

S5

14S8 S8

34 24S8

13 33 23

S854

53

2434

33 23

S9 54

53

S9 S9

2 474 57 55

36 34 35 20

(21)(13)(21)

S3(14)S3(22) S1(22)

(52)

(51)

V1

2526 24

V2

10

53 54 31 32

S844

43

44 S9

43

371513 1917 33 3938

S4

S5(74)

S5(54)

(2)(5)

(3)K0

(53)

S5

(73)

(12)

(11)

S5

(13)

(14) S2

CCK0

TC

6472 624232

4131 6371 61

8424 34

8323 33

S5

V4 V3

52 30 273 5 97 23 2928

92

91

94

93

16

6

18

8

40

1

M BC

UMMM

motor circuit closing circuit locking circuit opening circuit latch circuit

UVR circuit

A~

D~

2

1

C+ B-

ZC

V5

Y4

Spring Charge Motor Closing Circuit Opening CircuitBreaker Interlock Circuit Truck Interlock Circuit

UVR Circuit

Seco

Vac

Embe

dded

Pol

e Va

cuum

Circ

uit B

reak

er

Page 18: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

18

Seco

Vac

Vacu

um F

use

Con

tact

or

SecoVac Vacuum Fuse Contactor

Features• Withdrawable type

• Conformance to the latest IEC standards. IEC 62271-1 and IEC 62271-106

• Comformance to IEC 60282-1 for high voltage fuse

• With/without mechanical latch

• HV fuse protection

• Interlocking features for safety

• Compact and robust

SecoVac fuse contactors are provided in withdrawable type and include high voltage fuses.

Specifications DataRated Voltage (Kv) 12Rated Frequency (Hz) 50/60 Hz±5%Rated Power Freq Withstand Voltage (1min) (kV) 28Rated Lightning Impulse Withstand Voltage (kV) 75Rated Currents for Contactor (A) 400Rated Short-time Withstand Current (3s) (kA) 4Rated Making Current (kA) 4Rated Peak Withstand Current (kA) 10.4Maximum Rated Breaking Current (A) 3200Minimum Rated Breaking Current (A) 80Use Type AC3/AC4Latch Type (Both Latched & Non-Latched Required) MechanicalMechanical Life (Times) 300kNumber of Auxiliary Contacts 5a/5bMinimum Auxiliary Contacts Rating AC 110V/10A, AC 220V/5A or DC

Control Voltage 48/110/125/220/230 VDC 110/125/220/230 VAC

Undervoltage and Tripping Coil for Mechanical Latched Type Contactor RequiredAnti-pumping Relay RequiredDrop-out Voltage of Contactor AC 85%/DC 70%SC Breaking Capacity for Fuse (kA) 50Rated Take-over Current (A) 3200

Specifications Unit EFEN SIBARated Current A 200 250Thermal Current A 140 160

Specifications Unit Fuse ContactorRated Current A 400Withdrawable μΩ ≤ 250

Fuse Contactor Characteristics

High Voltage Fuse Characteristics

Main Circuit Resistance of Fuse Contactor

Applications• Serving global 50 Hz and 60 Hz systems

• Segments of industry: Power generation, marine, water treatment, mining

• Medium voltage motor control applications

• Suitable for special environment conditions: Shock, vibration, high ambient temperature

• Suitable for marine applications

Page 19: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

19

Seco

Vac

Vacu

um F

use

Con

tact

or

SecoVac Vacuum Fuse ContactorInternal Wiring Diagram for Mechanical Latch Type Contactor

SecoGear 3.3kV-27kV Air Insulated Switchgear

AC control circuit scheme

Internal wiring diagram for mechanical latch type contactor

SC

SB

SA

Close circuit

13

14

29

39

23

24

24

34

33

34

53

54

53

54

57

58

13

14

16

6

23

24

36

26

33

34

52

51

53

54

56

55

43

44

14

43

44

Work position

Test position

11

12

30

31

21

22

3

13

31

32

5

15

51

52

46

12

41

42

28

38

53

54

9

19

23

24

8

18

33

34

23

33

43

44

7

17

14

13

14

13

14

13

KM1

10

20

41

49

KM2

YC2

YC1 YT

1 2

Open circuit Close start

4

KM1

KM2 JSQ

27 43

13

14

Open start

48

12

11

12

11

12

11

SA

SB

SC

44

SA SB SC

S8

S9

22

21

22

21

22

21

QF

KM1

SC

SB

SA

Close circuit

13

14

29

39

23

24

24

34

33

34

53

54

53

54

57

58

13

14

16

6

23

24

36

26

33

34

52

51

53

54

56

55

43

44

14

43

44

Work position

Test position

11

12

30

31

21

22

3

13

31

32

5

15

51

52

46

12

41

42

28

38

53

54

9

19

23

24

8

18

33

34

23

33

43

44

7

17

14

13

14

13

14

13

10

20

41

49

KM2

YC2 YC1 YT

1 2

Open circuit Close start

4

KM1

KM2JSQ

27 43

13

14

Open start

48

12

11

12

11

12

11

SA

SB

SC

44

SA SB SC

S8

S9

22

21

22

21

22

21

QF

KM1 KM2

QF: Spindle auxiliary contact

YT: Open coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electro-magnetic counter

QF: Spindle auxiliary contact

YT: Open coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electro-magnetic counter

SecoGear 3.3kV-27kV Air Insulated Switchgear

AC control circuit scheme

Internal wiring diagram for mechanical latch type contactor

SC

SB

SA

Close circuit

13

14

29

39

23

24

24

34

33

34

53

54

53

54

57

58

13

14

16

6

23

24

36

26

33

34

52

51

53

54

56

55

43

44

14

43

44

Work position

Test position

11

12

30

31

21

22

3

13

31

32

5

15

51

52

46

12

41

42

28

38

53

54

9

19

23

24

8

18

33

34

23

33

43

44

7

17

14

13

14

13

14

13

KM1

10

20

41

49

KM2

YC2

YC1 YT

1 2

Open circuit Close start

4

KM1

KM2 JSQ

27 43

13

14

Open start

48

12

11

12

11

12

11

SA

SB

SC

44

SA SB SC

S8

S9

22

21

22

21

22

21

QF

KM1

SC

SB

SA

Close circuit

13

14

29

39

23

24

24

34

33

34

53

54

53

54

57

58

13

14

16

6

23

24

36

26

33

34

52

51

53

54

56

55

43

44

14

43

44

Work position

Test position

11

12

30

31

21

22

3

13

31

32

5

15

51

52

46

12

41

42

28

38

53

54

9

19

23

24

8

18

33

34

23

33

43

44

7

17

14

13

14

13

14

13

10

20

41

49

KM2

YC2 YC1 YT

1 2

Open circuit Close start

4

KM1

KM2JSQ

27 43

13

14

Open start

48

12

11

12

11

12

11

SA

SB

SC

44

SA SB SC

S8

S9

22

21

22

21

22

21

QF

KM1 KM2

QF: Spindle auxiliary contact

YT: Open coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electro-magnetic counter

QF: Spindle auxiliary contact

YT: Open coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electro-magnetic counter

AC control circuit scheme

DC control circuit scheme

FC: Opened and in working position QF: Spindle auxiliary switch

YT: Open Coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC Contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electromagnetic counter

FC: Opened and in working position QF: Spindle auxiliary switch

YT: Open Coil S8: Test position auxiliary contact

YC1, YC2: Close coil S9: Work position auxiliary contact

KM1, KM2: DC Contactor SA, SB, SC: Limit switches for fuse strikers

JSQ: Electromagnetic counter

Page 20: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

20

Voltage Transformer TruckThe withdrawable trucks also allow fuse replacement with the switchboard in service. Truck racking out with the door closed automatically operates closure of a metallic segregation shutter between the live parts of the switchgear and the instrument compartment.

Disconnect TruckDisconnect truck is used to disconnect primary circuit and normally coupling with bus bar tie breaker to achieve two section power supply. Disconnect truck can be provided with bus tie/ riser panels.

Earthing SwitchThe earthing switch can be operated from the front of the module. It is mechanically interlocked with the circuit breaker truck so that the earthing switch can only be operated when the circuit breaker is open in the test/disconnect position. The switch is also mechanically interlocked with the cable compartment door for additional safety.

Earthing Switch Characteristics

Disconnect Truck Characteristics

Specifications DataRated Voltage (kV) 7.2 / 12 / 15 / 17.5Rated Work Frequency Withstand Voltage (1 min) (kV) in open condition of switch 20 / 28 / 36 / 38Rated Lightning Impulse Withstand Voltage (peak value) in open condition of switch (kAp) 60 / 75 / 95 / 95Rated Short-time Withstand Current (3s) (kA) 31.5 / 40Rated Peak Value Withstand Current (kAp) 82 / 104Rated Short-circuit Making Current (kAp) 82 / 104Center Distance Between Phases (mm) 170 / 210 / 275Electric Endurance Class E1Mechanical Endurance (times) 2000

Specifications DataRated Voltage (kV) 17.5Rated Power Frequency Withstand Voltage (1 min) (kV) 38Rated Lightning Impulse Withstand Voltage (kV) 95Rated Frequency (Hz) 50 / 60Rated Current (A) 1250 / 1600 / 2000 / 2500 / 3150Rated Short-time Withstand Current (kA) 31.5 / 40 / 40 / 40Rated Peak Value Withstand Current (kAp) 82 / 104 / 104 / 104Rated Duration Time for Short-circuit (s) 3Dimensions As same current rating VCB

Earthing Switch and Disconnect Truck CharacteristicsEa

rthi

ng S

witc

h an

d D

isco

nnec

t Tru

ck C

hara

cter

istic

s

Page 21: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

21

Current TransformerCurrent transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteris-tics for measuring metering and protec-tion purposes.

Current < 1250A the CT type is LZZB-17 150A1 or A4

Current > 1250A the CT type is LMZB1-17

HV Components

Ground Fault Sensing CTThe ground fault sensing CT is insulated in resin and is used to supply measure-ment and protection devices. These CTs can be furnished in either a solid or split core design. They can be used either for measuring phase currents or for detecting the ground fault current. They conform to the IEC 60044-1 Standards.

CT type: LMZC

Voltage TransformerVoltage transformers are cast in resin and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different character-istics for measuring, metering and protection purposes.

LV Components GE Industrial Solutions offers additional LV switchgear components for the completion of the switchgear control compartment, such as the voltage presence indicator display and a complete range of LV modular and control products.

Protection, Control and CommunicationGE Digital Energy offers a complete and extensive portfolio of hardware and software solutions including Multilin protection IEDs, communication devices and substation automation systems solutions.

Components and Controls

Com

pone

nts

and

Con

trol

s

Page 22: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

22

SecoVac Checklist1 & 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Seco

Vac

VB2+

Bre

aker

Dev

ice

Type

Stru

ctur

e

Phas

e D

ista

nce

& V

olta

ge

Rate

d Cu

rren

t

Brea

king

Cur

rent

(kA)

Ope

n Co

il

Clos

e Co

il

Char

ging

Mot

or

Anti

Pum

p

Clos

e In

terl

ock

Truc

k In

terl

ock

Doo

r In

terl

ock

& P

adlo

ck

Und

er V

olta

ge

Seco

nd O

pen

Coil

Mot

oriz

ed R

ack

In/o

ut

Seco

ndar

y W

irin

g

DescriptionSV SecoVac VB2+ Breaker

I IEC SecoVac VB2+ G IEC/IEEE SecoVac VB2+G

W WithdrawableF Fixed

0 17.5kV, Pole Distance 150mm1 17.5kV, Pole Distance 210mm2 17.5kV, Pole Distance 275mm5 27kV, Pole Distance 210mm6 27kV, Pole Distance 275mm8 40.5kV, Pole Distance 275mmD 15kV Type G IEC/IEEE Pole Distance 210mmE 15kV Type G IEC/IEEE Pole Distance 275mm

0 630A1 1250A2 1600A3 2000A4 2500A5 3150A6 4000A

0 25kA1 31.5kA2 40kA3 50kA

X 0 0 0 0 0 0 None1 1 1 1 1 1 1 AC/DC110V2 2 2 2 2 2 2 2 AC/DC220V3 3 3 3 3 3 3 DC24V4 4 4 4 4 4 4 DC30V5 5 5 5 5 5 DC36V6 6 6 6 6 6 6 DC48V7 7 7 7 7 7 7 DC60V8 8 8 8 8 8 8 AC/DC125V9 9 9 9 9 9 9 AC/DC230-240V

Z Provided1 Door Interlock2 Padlock3 Door Interlock + Padlock

1 Through terminal block above SecoVac frame2 Through secondary plug with socket3 Through secondary socket above SecoVac frame with plug

Seco

Vac

Che

cklis

t

Page 23: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

23

SecoVac FC Checklist

Seco

Vac

FC C

heck

list

1 & 2 & 3 4 5 6 7 8 9 10 11 12 13 14 15

Prod

uct C

ode

Rate

d Vo

ltage

Latc

h M

echa

nism

Cont

acto

r Cu

rren

t Rat

ing

Cont

rol V

olta

ge o

f Ope

n/Cl

ose

Coil

Auxi

liary

Con

tact

s

Fuse

Cur

rent

Rat

ing

Fuse

Vol

tage

Rat

ing

Fuse

Sho

rt C

ircu

it Ca

paci

ty

Fuse

Typ

e

Oth

er

Fuse

Bra

nd

Mot

oriz

ed R

ack

In/O

ut

WFC SecoVac FC Withdrawable, IEC Standard1 12kV2 7.2kV

E Electrical LatchM Mechanical Latch

1 400AA AC110VB DC110VC AC220VD DC220VE AC125VF DC125VG AC230VH DC230VI DC48V

0 None2 6 open & 6 closed4 5 open & 5 closed

A 200AB 250AC 224AD 160AE 125AF 100AG 80AH 90AI 31.5AJ 150AK 63AL 315AM 71AN 50AO 112AP 16AQ 40AR 355AS 25AZ None

0 None1 12kV2 7.2kV

0 None1 50kA

0 NoneM MotorT TransformerC Capacitor

0 NoneA Close Door Operation

1 Siba2 EFEN3 Xirong (Chinese Bussman)4 None (fuse not required)

0 None1 AC/DC110V2 AC/DC220VE 120VAC/125VDCF 240VAC/250VDC

Page 24: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

24

SecoBloc BC and BV Modules Checklist 1 - 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Seco

Bloc

Upp

er C

ompa

rtm

ent T

ype

Bloc

Wid

th

Rate

d Vo

ltage

Rate

d Cu

rren

t

Shor

t-Ci

rcui

t Cur

rent

Eart

hing

Sw

itch

Volta

ge S

enso

r

Elec

tric

al In

terl

ocki

ng V

olta

ge

Key

Inte

rloc

k Br

and

Key

Inte

rloc

k fo

r ES

W

Key

Inte

rloc

k fo

r Ap

para

tus

Ra

ckin

g In

/out

Opt

iona

l Int

erlo

cks

Opt

iona

l Ele

men

ts

Mar

ine

Vers

ion

VT T

ruck

DescriptionBC IEC Module with Apparatus CompartmentBV IEC Module with Apparatus and Lower Compartments

B Breaker ApplicationC Contactor ApplicationV VT ApplicationE Empty Application

1 600mm2 750mm3 1000mm

1 7.2kV2 12kV3 17.5kV7 15kV

0 200A1 400A2 630A3 1250A4 1600A5 2000A6 2500A7 3150AN 0 0 0 0 0 0 0 0 0 0 None

0 25kA1 31.5kA2 40kA3 50kA

1 Manual ESW with Electrical Interlock2 Manual ESW without Electrical Interlock3 Electrical ESW with Electrical Interlock4 Electrical ESW without Electrical Interlock

1 3.3kV2 6.6kV3 10kV4 11kV5 20kV6 25kVA 4.16kVB 7.2kVC 13.8kVD 15kVE 15.5kVF 25.8kV

1 AC/DC110V2 AC/DC220V3 DC24V4 DC30V5 DC36V6 DC48V7 DC60V8 AC/DC125V9 AC/DC230-240V

1 Castell2 Fortress3 Ronis

1 1 Key + 1 Lock - 1 Key trapped Earthing Switch Open 2 1 Key + 1 Lock - 1 Key released Earthing Switch Open 3 2 Keys + 2 Locks - 1 Key trapped & 1 Key released Earthing Switch Open4 2 Keys + 2 Locks - 2 Keys trapped Earthing Switch Open 5 2 Keys + 2 Locks - 2 Keys released Earthing Switch Open

1 1 Key + 1 Lock - 1 Key trapped Apparatus in Test Position2 1 Key + 1 Lock - 1 Key released when the Apparatus in Test Position3 2 Keys + 2 Locks - 1 Key trapped & 1 Key released Apparatus in Test Position4 2 Keys + 2 Locks - 2 Keys trapped Apparatus in Test Position5 2 Keys + 2 Locks - 2 Keys released when the Apparatus in Test Position

1 Shutter Interlock to prevent manual activation1 Emergency trip push button2 Breaker compartment heater3 Emergency trip + Heater

1 Marine Version (Handrail + Door Stopper)2 IP43 Earthing Switch Apperture Cover3 Marine Version + IP43 Cover

1 With VT truck (w/o VT) on Lower Compartment2 With VT truck (w/ VT) on Lower Compartment3 With VT truck (w/o VT) on Apparatus Compartment4 With VT truck (w/ VT) on Apparatus Compartment

Seco

Bloc

BC

and

BV

Che

cklis

t

Page 25: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

25

IEEE OEM Modules 5 - 15kV for SecoVac Vacuum Circuit Breakers

For more information on GE’s SecoBloc IEEE OEM Modules, please refer to the following publications:• DEA-612: SecoBloc IEEE OEM Modules Brochure

• DEQ-211: SecoBloc IEEE OEM Modules Factsheet

• DEH-50002: SecoBloc IEEE OEM Modules User Manual

• DEH-50001: SecoVac IEEE VCB User Manual

Specifications 1200/31.5 1200/40 2000/40 3000/40Rated Current (A) 1200 1200 2000 3000

Rated Voltage (kV) 4.76 / 8.25 / 15 4.76 / 8.25 / 15 4.76 / 8.25 / 15 4.76 / 8.25 / 15

Rated Power Frequency (1 min)Phase to Phase and to Earth (kV) 36 36 36 36

Between Isolating Distance (kV) 36 36 36 36

Rated Lighting Impulse (1.2/50μs)Phase to Phase and to Earth (kV) 95 95 95 95

Between Isolating Distance (kV) 95 95 95 95

Rated Frequency (Hz) 60 60 60 60

Rated Short Time Withstand (kA) 31.5 40 40 40

Rated Peak Value Withstand Current (kAp) 82 104 104 104

Rated Duration Time for Short-circuit (s) 2 2 2 2

IP Level for Door NEMA 250 Type 1 /Type 1+2 (IEC IP4X)

DimensionsWeight (kg / lbs) 350 / 772 350 / 772 362 / 796 382 / 840

Phase to Phase Distance (mm / in) 254 / 10 254 / 10 254 / 10 275/10.8

A (mm/in) 914 / 36.0 914 / 36.0 914 / 36.0 914 / 36.0

B (mm/in) 1100 / 43.3 1100 / 43.3 1100 / 43.3 1100 / 43.3

C (mm/in) 947 / 38.3 934 / 36.8 934 / 36.8 934 / 36.8

D (mm/in) 1025 / 40.4 1012 / 39.8 1012 / 39.8 1012 / 39.8

E (mm/in) 1205 / 47.4 1205 / 47.4 1205 / 47.4 1205 / 47.4

F (mm/in) 1283 / 50.5 1283 / 50.5 1205 / 47.4 1205 / 47.4

Technical Data

Front/Side View

1205

1283

914

1100

947

468

275

1025

1205

1283

914

1100

947

468

275

1025

914

1100

1205

1283

483

310

934

1012914

1100

1205

1283

483

310

934

1012

1200/31.5kA or 1200/40kA

A AC CD D

E EF F2000/40kA

275mm 10.80in

468mm 18.40in

310mm 12.20in

483mm 19.02in

Page 26: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined
Page 27: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined
Page 28: DEA-605 SecoBloc IEC OEM Modules Brochure...3 More Than 90 Years of Interrupter Experience GE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined

To view the entire Medium Voltage Seco Product Offering please visit: www.geindustrial.com

Seco Cube Seco RMU Seco Gear SecoBloc SecoVac

*SecoBloc is a trademark of General Electric Company

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.

4.15 DEA-605

Imagination at work

GE Industrial Solutions 41 Woodford Avenue Plainville, CT 06062 www.geindustrial.com

SecoVac & SecoBloc Reference Publications

SecoVac - Embedded Pole Vacuum CB Printing Code: IN201301B30EN

Seco Gear - Air Insulated Switchgear Printing Code: IN201401B29EN