ctx industrial contactors
DESCRIPTION
Industrial Contactors for Essential EquipmentsTRANSCRIPT
-
Essential equipment
9 A TO 310 A THREE-POLEINDUSTRIAL CONTACTORS
NEW CTX CONTACTORS
for all yourrequirements
-
CTX three-poleindustrial
contactors,The new range of CTXcontactors provides safeand effective control,monitoring and protectionof circuits. It can be usedfor electricity distributionapplications for bothcommercial and industrialbuildings.
This robust range isan addition that fits inperfectly with the Legrandcircuit breaker offer (DPXor DX-MA).
a senseof family
-
1CONTENTSCONTENTSCONTENTSCONTENTSCONTENTS
An entire range .......................................................................................................p. 2
CTX-1 three-pole contactors .......................................................................p. 4
CTX-2 three-pole contactors .......................................................................p. 6
RTX-1 and RTX-2 thermal relays.............................................................p. 8
CTX-C three-pole contactors....................................................................p. 10
Catalogue pages..................................................................................................p. 12
-
2CTX industrial contactors,a comprehensive range to choose fromThe range of three-pole industrial contactors can be combined with additionalfunctions (thermal relays, auxiliary contact blocks and interlocking accessories)that are specially designed to cover the most common applications. There arealso special CTX-C contactors for controlling capacitor banks for reactive energycompensation.
CTX-1Three-pole contactors9 A to 105 A - AC 3
CTX-2Three-pole contactors150 A to 310 A - AC 3
Side-mountingauxiliarycontact blocks
Front-mountingauxiliarycontact blocks
9A
Up to 4 auxiliary contactblocks per contactor
Up to 6 auxiliary contactblocks per contactor
12A 18A25A 32A
40A50A
65A80A
95A105A
150A185A
250A
310A
Control voltage 24 V , 110 V , 220 V , 400 V - 50/60 Hz
CTX-1 CTX-2
205A
Up to 8 auxiliary contactblocks per contactor
Control voltage and
-
3Equipped with discharge resistors and auxiliary contact block (1 NO + 1 NC)
12,5 kVAR16,7 kVAR
20 kVAR
30 kVAR
45 kVAR
55 kVAR
70 kVAR
Control voltage 110 V , 230 V , 440 V
CTX-C
RTX-1, RTX-2Thermal relays for CTX-1and CTX-2 contactors
CTX -CThree-pole contactors12.5 kVAR to 70 kVAR
-
4CTX-1: flexibility,easy wiring and safetyNumerous combinations for a wide range of applications, from 9 A to 105 A.Safety, with protected screw terminals, and flexibility for your configurationswith front or side-mounting auxiliary contact blocks
Front-mountingauxiliary
contact block
Side-mountingauxiliarycontact block
3
1
4
52
6
Front and side-mounting auxiliarycontact blocksUp to 4 blocks for 40 A ratingsUp to 6 blocks for 50 to 60 A ratings
-
5> Flexibility
9jVa[gZfjZcXnXd^ah!24 VA to 400 VA
GZkZgh^WaZh^YZ"bdjci^c\auxiliary contact
IZgb^cVahXdbeVi^WaZl^i]all types of cable
> Time saving
:Vhnl^g^c\YjZidXaZVgterminal marking
8d^al^i](iZgb^cVah[dgeasier wiring and tap-off
HcVe"dc[gdci"bdjci^c\auxiliary contact
9>CgV^abdjci^c\jeid65 A rating
> Safety
I]ZhXgZliZgb^cVahare protected againstaccidental contact
>ciZgadX`^c\VXXZhhdg^Zh
1
3
5
2
4
6
Screw terminals protected againstaccidental contact
Side-mounting auxiliary contact block:reversible, with dual marking
Easy wiring due toclear terminal marking
Screw or cage terminals depending onrating of the contactor. Compatible with alltypes of cable
Front-mounting auxiliary contact block:quick, simple snap-on mounting
Mechanical or electrical interlockingfor various configurations
-
6CTX-2:even greater adaptabilitySafety, with protected screw terminals, and adaptability to specific applicationswith AC or DC control circuits. Fits in perfectly with the CTX-1 family of contactors
4
2
1
3
Integrated auxiliarycontact block(1N/O + 1 N/C)for all ratings
Side-mounting auxiliary contact blocksUp to 8 blocks per contactor
5
-
7> Flexibility
9jVa[gZfjZcXnXd^ah!230 VA and 400 VAor electronic modules,220 V to 440 VA /=
GZkZgh^WaZh^YZ"bdjci^c\auxiliary contact
8dccZXi^dck^VXdccZXi^dcplate suitable for the typeof cable
> Time saving
:Vhnl^g^c\YjZidXaZVgterminal marking
> Safety
I]ZhXgZliZgb^cVahare protected againstaccidental contact
BZX]Vc^XVa^ciZgadX`^c\accessories
1
4
3
2
5
Mechanical interlocking forvarious configurations
Side-mounting auxiliary contact block:reversible, with dual marking
Screw terminals protected againstaccidental contact
Easy wiring due toclear terminal marking
Connection via connection plate
-
8RTX-1 & RTX-2 thermal relayssafe, effective protectionSafe and easy to use, these provide effective protection against normal,balanced overloads and against long starting times. They are very reliable,compensate the ambient temperature between -25 C and +60 C and operatewith no change in their characteristics up to an altitude of 3000 m
1
2
4
3
5
-
9> Safe and easy to use
>ciZ\gViZYiZhiWjiidcVcYindicator
> Flexibility
;^mY^gZXiandcidi]Zcontactor or DIN rail
> Adaptability todifferent types ofapplication
KVg^djhdeZgVi^c\bdYZh
2 3
1
54
Test pushbutton and trip indicator integratedon the front panel of the unit
Relay easy to fix directly on thecontactor
or separately on DIN rail (depth 35 mm)using a special base
Function switch:automatic reset; automatic reset with stop
Function switch:manual reset; manual reset with stop
-
10
CTX-C: solution specially forcapacitor banksSpecially designed to reduce current peaks when capacitor banks areXdccZXiZY!WnbZVchd[V[gdci"bdjci^c\WadX`Zfj^eeZYl^i]Y^hX]Vg\Zresistors and auxiliary contacts
5
2
1
4
3
Front-mountingauxiliarycontact block
-
11
> Flexibility
9jVa[gZfjZcXnXd^ah!110 VA to 440 VA
IZgb^cVahXdbeVi^WaZl^i]all types of cable
> Time saving
:Vhnl^g^c\YjZidXaZVgterminal marking
8d^ahl^i](iZgb^cVah[dgeasier wiring and tap-off
HcVe"dc[gdci"bdjci^c\auxiliary contact
C$D C$8egZ[VWg^XViZYauxiliary contact
> Safety
I]ZhXgZliZgb^cVahare protected againstaccidental contact
BZX]Vc^XVa^ciZgadX`^c\accessories
3 4
2
5
Integrated dual frequency control coilsAvailable in 110 VA , 230 VA , 440 VA
Discharge resistors.Wired directly on the terminals
Front-mounting auxiliary contact block:quick, simple snap-on mounting
Screw or cage terminals depending onrating of the contactor. Compatible with alltypes of cable
Screw terminals protected againstaccidental contact
1
-
12
CTX-1 contactors9 A to 105 A three-pole industrial contactors
Technical characteristics (p. 16)Dimensions (p. 24)
Three-pole contactors equipped with control coilScrew terminals protected against accidental contact in accordance with VDE 0106 T.100. VBG4IP 20 for 9 A to 18 A ratingsIP 10 for 25 A to 105 A ratingsCan be fitted with auxiliary contact blocks for front or side mounting: up to 4 blocks for 9 A to 40 A ratings and up to 6 blocks for 50 A to 105 AratingsConform to standards IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1
Pack Cat.Nos CTX-1 contactors
Three-pole contactorsControl circuit: 50/60 Hz AC
9 AWith integrated auxiliary contactPower terminals: screw terminalsMax. operating
current AC 3 Control VoltageIntegrated
auxiliary contact Dimensions
1 293 00 9 A 24 VA 1 NO Size 11 293 02 9 A 110 VA 1 NO Size 11 293 04 9 A 230 VA 1 NO Size 11 293 05 9 A 400 VA 1 NO Size 11 293 10 9 A 24 VA 1 NC Size 11 293 12 9 A 110 VA 1 NC Size 11 293 14 9 A 230 VA 1 NC Size 11 293 15 9 A 400 VA 1 NC Size 1
12 AWith integrated auxiliary contactPower terminals: screw terminals
1 293 20 12 A 24 VA 1 NO Size 11 293 22 12 A 110 VA 1 NO Size 11 293 24 12 A 230 VA 1 NO Size 11 293 25 12 A 400 VA 1 NO Size 11 293 30 12 A 24 VA 1 NC Size 11 293 32 12 A 110 VA 1 NC Size 11 293 34 12 A 230 VA 1 NC Size 11 293 35 12 A 400 VA 1 NC Size 1
18 AWith integrated auxiliary contactPower terminals: screw terminals
1 293 50 18 A 24 VA 1 NO Size 11 293 52 18 A 110 VA 1 NO Size 11 293 54 18 A 230 VA 1 NO Size 11 293 55 18 A 400 VA 1 NO Size 11 293 60 18 A 24 VA 1 NC Size 11 293 62 18 A 110 VA 1 NC Size 11 293 64 18 A 230 VA 1 NC Size 11 293 65 18 A 400 VA 1 NC Size 1
25 APower terminals: cage terminals
1 293 70 25 A 24 VA Size 21 293 72 25 A 110 VA Size 21 293 74 25 A 230 VA Size 21 293 75 25 A 400 VA Size 2
Pack Cat.Nos CTX-1 contactors (continued)
32 APower terminals: cage terminals
Max. operatingcurrent AC 3 Control Voltage Dimensions
1 293 80 32 A 24 VA Size 21 293 82 32 A 110 VA Size 21 293 84 32 A 230 VA Size 21 293 85 32 A 400 VA Size 2
40 APower terminals: cage terminals
1 293 90 40 A 24 VA Size 31 293 92 40 A 110 VA Size 31 293 94 40 A 230 VA Size 31 293 95 40 A 400 VA Size 3
50 APower terminals: cage terminals
1 294 00 50 A 24 VA Size 41 294 02 50 A 110 VA Size 41 294 04 50 A 230 VA Size 41 294 05 50 A 400 VA Size 4
65 APower terminals: cage terminals
1 294 10 65 A 24 VA Size 41 294 12 65 A 110 VA Size 41 294 14 65 A 230 VA Size 41 294 15 65 A 400 VA Size 4
80 APower terminals: cage terminals
1 294 20 80 A 24 VA Size 41 294 22 80 A 110 VA Size 41 294 24 80 A 230 VA Size 41 294 25 80 A 400 VA Size 4
95 APower terminals: cage terminals
1 294 30 95 A 24 VA Size 51 294 32 95 A 110 VA Size 51 294 34 95 A 230 VA Size 51 294 35 95 A 400 VA Size 5
105 APower terminals: cage terminals
1 294 40 105 A 24 VA Size 51 294 42 105 A 110 VA Size 51 294 44 105 A 230 VA Size 51 294 45 105 A 400 VA Size 5
293 04 293 74 294 04 294 34
-
CTX-1 contactorsauxiliary contacts, accessories, replacement coils
RTX-1 thermal relaysFor CTX-1 industrial contactors
13
Technical characteristics (p. 16)Dimensions (p. 24)
Pack Cat.Nos Auxiliary contact blocks
For CTX-1 contactorsScrew terminals
Front mountingType of contact
10 297 12 1 NO10 297 13 1 NC
Side mounting10 297 14 2 NO10 297 15 1 NO + 1 NC
Interlocking accessoriesFor CTX-1 contactors
For 9 A to 105 A contactors5 297 16 Mechanical interlock5 297 17 Mechanical/electric interlock
2 x NC contacts
Terminal shieldsFor CTX-1 contactors
1 297 18 For 25 A and 32 A contactors (kits of 8 terminalshields)
1 297 19 For 40 A contactors (kits of 6 terminal shields)1 297 20 For 50 A and 80 A contactors (kits of 8 terminal
shields)1 297 21 For 95 A and 105 A contactors (kits of 8 terminal
shields)
Replacement coilsFor CTX-1 contactors
For 9 A to 18 A contactorsControl Voltage(50/60 Hz)
5 297 00 24 VA5 297 01 110 VA5 297 02 230 VA5 297 03 400 VA
For 25 A to 40 A contactors5 297 04 24 VA5 297 05 110 VA5 297 06 230 VA5 297 07 400 VA
For 50 A to 105 A contactors5 297 08 24 VA5 297 09 110 VA5 297 10 230 VA5 297 11 400 VA
Technical characteristics (p. 20)Dimensions (p. 26)
Thermal protection against normal overloadsResidual current protection against unbalanced overloadsProtection against long starting timesAmbient temperature compensation between -25 C and 60 CFront test push-buttonTrip indicationIndependent double break auxiliary contacts (1 NO + 1 NC)Function switch: manual reset; manual reset and stop; automatic resetwith stop; automatic reset without stop
Pack Cat.Nos Thermal relays
For 9 A to 40 A CTX-1 contactorsClass 10 A
Adjustment range Integrated auxiliarycontacts DimensionsI min. (A) I max. (A)
1 294 58 0.65 1.1 1 NO + 1 NC Size 11 294 59 1 1.5 1 NO + 1 NC Size 11 294 60 1.3 1.9 1 NO + 1 NC Size 11 294 61 1.8 2.7 1 NO + 1 NC Size 11 294 62 2.5 4 1 NO + 1 NC Size 11 294 63 4 6.3 1 NO + 1 NC Size 11 294 64 5.5 8.5 1 NO + 1 NC Size 11 294 65 8 12 1 NO + 1 NC Size 11 294 66 10 16 1 NO + 1 NC Size 11 294 67 14.5 18 1 NO + 1 NC Size 11 294 68 17.5 22 1 NO + 1 NC Size 11 294 69 21 26 1 NO + 1 NC Size 11 294 70 25 32 1 NO + 1 NC Size 11 294 71 30 40 1 NO + 1 NC Size 1
For 50 A to 105 A CTX-1 contactorsClass 10
1 294 72 24 32 1 NO + 1 NC Size 21 294 73 30 43 1 NO + 1 NC Size 21 294 74 42 55 1 NO + 1 NC Size 21 294 75 54 65 1 NO + 1 NC Size 21 294 76 64 82 1 NO + 1 NC Size 21 294 77 78 97 1 NO + 1 NC Size 21 294 78 90 110 1 NO + 1 NC Size 2
Fixing accessoryFor RTX-1 thermal relaysMounting on 35 mm DIN rail
1 294 94 Separate fixing base for Cat.Nos 294 58 to 294 711 294 95 Separate fixing base for Cat.Nos 294 72 to 294 78
297 12 297 14 297 16 297 00 294 58 294 94
-
14
CTX-2 contactors150 A to 310 A three-pole industrial contactors
CTX-2 contactorsauxiliary contacts, accessories, replacement coils
Technical characteristics (p. 18)Dimensions (p. 25)
Three-pole contactors equipped with control coilScrew terminals protected against accidental contact in accordance withVDE 0106 T.100. VBG4Supplied with auxiliary contact block Cat.Nos 297 15 (1 NO + 1 NC)Can be fitted with up to 8 auxiliary contact blocks for side mountingConform to standards IEC/EN 60947-1, IEC/EN 60947-4-1
Pack Cat.Nos CTX-2 contactors
Three-pole contactorsControl circuit: 50/60 Hz AC
150 AConnect using connection plateMax. operating
current AC 3 Control VoltageIntegrated auxiliary
contact Dimensions1 295 00 150 A 24 VA 1 NO + 1 NC Size 11 295 02 150 A 110 VA 1 NO + 1 NC Size 11 295 04 150 A 230 VA 1 NO + 1 NC Size 11 295 05 150 A 400 VA 1 NO + 1 NC Size 1
185 AConnect using connection plate
1 295 10 185 A 24 VA 1 NO + 1 NC Size 11 295 12 185 A 110 VA 1 NO + 1 NC Size 11 295 14 185 A 230 VA 1 NO + 1 NC Size 11 295 15 185 A 400 VA 1 NO + 1 NC Size 1
CTX-2 contactors with electronic controlThree-pole contactorsControl circuit: 50/60 Hz AC or DC
205 AConnect using connection plate
Max. operatingcurrentAC 3 Control Voltage
Integrated auxiliarycontact Dimensions
1 295 20 205 A 24 - 28 VA/ = 1 NO + 1 NC Size 21 295 22 205 A 110 - 127 VA/ = 1 NO + 1 NC Size 21 295 24 205 A 230 - 250 VA/ = 1 NO + 1 NC Size 21 295 25 205 A 380 - 415 VA/ = 1 NO + 1 NC Size 2
250 AConnect using connection plate
1 295 30 250 A 24 - 28 VA/ = 1 NO + 1 NC Size 21 295 32 250 A 110 - 127 VA/ = 1 NO + 1 NC Size 21 295 34 250 A 230 - 250 VA/ = 1 NO + 1 NC Size 21 295 35 250 A 380 - 415 VA/ = 1 NO + 1 NC Size 2
310 AConnect using connection plate
1 295 42 310 A 110 - 127 VA/ = 1 NO + 1 NC Size 21 295 44 310 A 230 - 250 VA/ = 1 NO + 1 NC Size 2
Pack Cat.Nos Auxiliary contact blocks
For CTX-2 contactors
For combination of max. 2 blocksSide mountingScrew terminalsMax. 1 additional block per contactor (in addition tothat supplied with the device)Type of contact
10 297 14 2 NO10 297 15 1 NO + 1 NC
For combination of more than 2 blocksSide mountingScrew terminals
10 297 58 2 NO10 297 59 1 NO + 1 NC10 297 60 2 NC
Interlocking accessoriesFor CTX-2 contactors
For 150 A to 310 A contactors1 297 61 Horizontal mechanical interlock1 297 62 Vertical mechanical interlock (not UL)
Single pole terminal shieldFor CTX-2 contactors
For 150 A and 185 A contactors1 297 66 IPXXB terminal shield
For 205 A, 250 A and 310 A contactors1 297 67 IPXXB terminal shield (kit of 3 terminal shields)
Replacement coils for CTX-2 contactors150 A to 185 A contactorsControl Voltage (50/60 Hz)
1 297 32 230 VA1 297 33 400 VA
Control assembly for 205 to 310 AcontactorsComprises two elements: coil + module
Replacement coilsControl Voltage (50/60 Hz)
1 297 36 220 - 250 VA/ =1 297 37 380 - 415 VA/ =
Electronic modules1 297 47 220 - 250 VA/ =1 297 48 380 - 415 VA/ =
Technical characteristics (p. 18)Dimensions (p. 25)
295 04 295 24 297 61297 14
-
15
RTX-2 thermal relaysFor CTX-2 thermal contactors
Technical characteristics (p. 20)Dimensions (p. 26)
Thermal protection against normal overloadsResidual current protection against unbalanced overloadsProtection against long starting timesAmbient temperature compensation between -25 C and 60 CFront test push-buttonTrip indicationIndependent double break auxiliary contacts (1 NO + 1 NC)Function switch: manual reset; manual reset and stop; automatic resetwith stop; automatic reset without stop
Pack Cat.Nos Thermal relays
For 150 A to 185 A CTX-2 contactorsClass 10
Adjustment range Integrated auxiliarycontact DimensionsI min. (A) I max. (A)
1 294 82 63 90 1 NO + 1 NC Size 11 294 83 90 120 1 NO + 1 NC Size 11 294 84 110 140 1 NO + 1 NC Size 11 294 85 140 190 1 NO + 1 NC Size 1
For 205 A to 310 A CTX-2 contactorsClass 10
1 294 86 120 190 1 NO + 1 NC Size 21 294 87 175 280 1 NO + 1 NC Size 21 294 88 200 310 1 NO + 1 NC Size 2
Our solutionfor connectingcapacitor banksinstallations
> Control voltage: 110 VA, 230 VA et 440 VA
>>>CTX-C CONTACTORS
> Three-pole contactors from 12.5 kVARto 70 kVAR for capacitors banks installations
> Equipped with auxiliary contact and dischargeresistors for connecting three-phase capacitorsbanks
p. 27
294 82 294 86
-
16
CTX-1 contactorstechnical characteristics
NStandards
Conform to standards:
- IEC/EN 60947-1
- IEC/EN 60947-4-1
- IEC/EN 60947-5-1
- UL 508
NAmbient conditions
Storage temperature: - 55 C to 80 COperating temperature - 40 C to 60 CWorking altitude
up to 3000 m: Nominal Valuebetween 3000 and 4000 m: 90%Ie 80%Uebetween 4000 and 5000 m: 80%Ie 75%Ue
NMounting position
30
30
NPower circuit characteristics
9 A 12 A 18 A 25 A 32 A 40 A 50 A 65 A 80 A 95 A 105 A
Nominal thermal rating Ith Q 55C (A) 25 25 32 45 60 60 90 110 110 140 140
Nominal operating current Ie (A) 9 12 18 25 32 40 50 65 80 95 105
Nominal operating Voltage Ue (V) 690 690 690 690 690 690 690 690 690 690 690
Nominal insulation Voltage (Ui) (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Maximum permanent current in AC1 (A) 25 25 32 45 60 60 90 110 110 140 140
Frequency range (Hz) 25...400 25...400 25...400 25...400 25...400 25...400 25...400 25...400 25...400 25...400 25...400
Making capacity (rms) (IEC 947) (A) 450 450 450 550 550 550 1000 1000 1000 1280 1280
Breaking capacity(rms) (IEC 947)
Ue 400 V (A) 250 250 250 450 450 450 920 920 920 1050 1050
Ue = 500 V (A) 250 250 250 450 450 450 920 920 920 1050 1050
Ue = 690 V (A) 130 130 130 205 205 205 780 780 780 950 950
Short-time current
1 sec. (A) 455 455 570 1010 1010 1265 1580 2530 2530 3300 3300
5 sec. (A) 205 205 254 450 450 450 710 1130 1130 1485 1485
10 sec. (A) 144 144 180 320 320 400 500 800 800 1050 1050
30 sec. (A) 85 85 104 185 185 230 290 460 460 600 600
1 min. (A) 60 60 74 130 130 165 205 325 325 430 430
3 min. (A) 35 35 46 90 90 100 120 185 185 250 250
Recovery time (min.) 10 10 10 10 10 10 10 10 10 10 10
Protection againstshort-circuitsWithout thermal relay
Type "1" coordinationgL/gG (A) 50 50 63 100 100 125 200 200 200 250 250
Type "2" coordinationgL-gG (A) 25 35 35 63 63 80 100 125 125 160 200
gL-gG without welding (A) 10 10 25 35 35 50 80 100 100 140 160
Impedance per pole (m ) 2.35 2.35 2.41 1.28 1.28 0.95 0.85 0.86 0.86 0.76 0.76
Dissipation per poleAC-1 (W) 1.47 1.47 2.46 2.59 4.6 3.42 6.86 10.40 10.40 14.89 14.89
AC-3 (W) 0.19 0.34 0.78 0.80 1.31 1.52 2.12 3.63 5.5 6.86 8.37
Insulation resistance
Between adjacent poles (m ) >10 >10 >10 >10 >10 >10 >10 >10 >10 >10 >10
Between poles andexposed conductive part (m ) >10 >10 >10 >10 >10 >10 >10 >10 >10 >10 >10
Between input and output (m ) >10 >10 >10 >10 >10 >10 >10 >10 >10 >10 >10
No Variation of nominal powersNo Variation of holding and drop-out Voltage
-
17
NControl circuit characteristics
AC 9 A to 18 A 25 A to 40 A 50 A to 80 A 95 A and 105 A
Nominal insulation Voltage Ui (V) 1000 1000 1000 1000
Standard Voltages Us 50 Hz (V) 24...690 24...690 24...690 24...690
Standard Voltages Us 60 Hz (V) 24...600 24...600 24...600 24...600
50/60 Hz coil limit Voltage
50 Hz service xUs 0.8...1.1 0.8...1.1 0.8...1.1 0.8...1.1
60 Hz service xUs 0.85...1.1 0.85...1.1 0.85...1.1 0.85...1.1
50 Hz closing xUs 0.5...0.8 0.6...0.8 0.6...0.8 0.6...0.8
60 Hz closing xUs 0.65...0.85 0.7...0.85 0.7...0.85 0.7...0.85
50 Hz opening xUs 0.3...0.55 0.35...0.60 0.35...0.60 0.35...0.60
60 Hz opening xUs 0.35...0.35 0.4...0.6 0.4...0.6 0.4...0.6
Dual frequency coil consumptionHolding (50 Hz/60 Hz) (VA) 6.8/5.6 11.4/9.5 20/16.6 20/16.6
Inrush (50 Hz/60 Hz) (VA) 53/44 120/100 245/204 245/204
Heat dissipation (50 Hz/60 Hz) (W) 2.2/1.8 3.2/2.6 5.2/4.3 5.2/4.3
Power factor
Magnetic circuitclosed cos 0.33 0.28 0.26 0.26
Magnetic circuit open cos 0.84 0.73 0.54 0.54
Holding and drop-outtimes
Values between + 10% Usand - 20% Us
NO closing time atenergisation (ms) 6...20 7...25 9...35 9...35
NO opening time atde-energisation (ms) 6...13 5...25 9...15 9...15
Values at Us
NO closing time atenergisation (ms) 8...20 10...19 15...30 15...30
NO opening time atde-energisation (ms) 6...13 5...25 9...15 9...15
Mechanical endurance Dual frequency coil (at 50 Hz) 106 operations 10 10 8 8
Maximum rate
AC1 at nominal power operations/hour 1200 1200 1200 1200
AC2 at nominal power operations/hour 1000 1000 1000 750
AC3 at nominal power operations/hour 1200 1200 1200 600
AC4 at nominal power operations/hour 360 360 200 200
Dual frequency coil with no load operations/hour 3600 3600 3600 3600
-
18
CTX-2 contactorstechnical characteristics
NStandards
Conform to standards:
- IEC/EN 60947-1
- IEC/EN 60947-4-1
NAmbient conditions
Storage temperature: - 55 C to 80 COperating temperature - 40 C to 60 CWorking altitude
up to 3000 m: Nominal Valuebetween 3000 and 4000 m: 90%Ie 80%Uebetween 4000 and 5000 m: 80%Ie 75%Ue
NMounting position
With no variation of nominal powersWith no variation of holding and dropout voltage
30
30
NPower circuit characteristics
150 A 185 A 205 A 250 A 310 A
Nominal thermal rating Ith 40C (A) 250 250 315 315 450
Nominal operating current Ie in AC3 (A) 150 185 205 250 309
Nominal operating Voltage Ue (V) 1000 1000 1000 1000 1000
Nominal insulation Voltage Ui (V) 1000 1000 1000 1000 1000
Maximum permanent current in AC1 (A) 250 250 315 315 450
Frequency limits (Hz) 25...400 25...400 25...400 25...400 25...400
Making capacity (rms) (A) 1850 2200 2500 2500 3700
Breaking capacity (rms)
Ue 400V (A) 1600 1850 2000 3500 3500Ue = 500 V (A) 1600 1850 2000 3500 3500
Ue = 690 V (A) 1000 1200 1660 2200 2200
Ue = 1000 V (A) 350 350 850 1100 1100
Short-time current
1 sec. (A) 2500 2500 4000 5500 5500
5 sec. (A) 2500 2500 3200 3500 3500
10 sec. (A) 2300 2300 2400 2500 2500
30 sec. (A) 1250 1250 1400 1600 1600
1 min. (A) 900 900 1000 1200 1200
3 min. (A) 600 600 750 900 900
Recovery time (min.) 10 10 10 10 10
Short-circuit protection by fuseWithout welding
Type "1" coordination gL/gG (A) 355 355 500 500 630
Type "2" coordination gL/gG (A) 250 250 315 400 500
Without welding (A) 200 200 250 315 425
Impedance per pole (m) 0.30 0.30 0.28 0.28 0.28Dissipated power AC-1 (W) 19 19 27.7 27.7 56.7
per pole AC-3 (W) 6.8 10.3 11.7 17.5 26.7
Insulation resistance
between adjacent poles (m) > 10 > 10 > 10 > 10 > 10between poles and exposed
conductive part (m) > 10 > 10 > 10 > 10 > 10
between input and output (m) > 10 > 10 > 10 > 10 > 10
-
19
NControl circuit characteristics
AC 150 A 185 A 205 A 250 A 310 A
Nominal insulation Voltage Ui (V) 1000 1000 1000 1000 1000
Standard Voltages Us (50/60 Hz) (V) 24...690 24...690 24...690 24...690 24...690
Voltage limitsOperating Voltage xUs 0.8...1.1 0.8...1.1 0.8...1.1 0.8...1.1 0.8...1.1
Trip Voltage xUs 0.4...0.6 0.4...0.6 0.4...0.6 0.4...0.6 0.4...0.6
Dual frequency coilconsumption
Held closed(CTX-2 150 to 185 A)
50 Hz (VA) 46 46 60 - -
60 Hz (VA) 38.3 38.3 50 - -
Held open(CTX-2 150 to 185 A)
50 Hz (VA) 568 568 1082 - -
60 Hz (VA) 473 473 901 - -
Dissipated power(CTX-2 150 to 185 A)
50 Hz (W) 23 23 22.2 - -
60 Hz (W) 19.1 19.1 18.5 - -
Power factor
Held closed
CTX-2150 to185 A
cos 0.4 0.4 0.37 - -
CTX-2205 to310 A
cos - - - - -
Held open
CTX-2150 to185 A
cos 0.6 0.6 0.6 - -
CTX-2205 to310 A
cos - - - - -
Holding and drop-out timesat Us
NO closing time atenergisation (ms) 20...25 20...25 36...40 60...70 60...70
NO opening time atde-energisation (ms) 10...13 10...13 10...15 13...17 13...17
Mechanical endurance 106 operations 10 10 10 10 10
Maximum rate
No-load operations/hour 2400 2400 2400 1200 1200
AC1/AC3 at nominal power operations/hour 600 600 600 600 60
AC2 at nominal power operations/hour 250 250 250 250 250
AC4 at nominal power operations/hour 150 150 150 150 150
DC 205 A 250 A 310 A
Nominal insulation Voltage Ui (V) 1000 1000 1000
Standard Voltages Us (V) 24...500 24...500 24...500
Voltage limitsOperating Voltage xUs 0.8...1.1 0.8...1.1 0.8...1.1
Trip Voltage xUs 0.35...0.5 0.4...0.6 0.4...0.6
ConsumptionHolding (W) 3.5 3.5 3.5
Inrush (W) 350 350 350
Holding and drop-outtimes at U
NO closing time atenergisation (ms) 60,..70 60,..70 60,..70
NO opening time atde-energisation (ms) 13...17 13...17 13...17
Mechanical endurance 106 operations 10 10 10
Maximum rate
No-load operations/hour 1200 1200 1200
AC3 at nominal power operations/hour 600 600 600
AC4 at nominal power operations/hour 150 150 150
-
20
RTX-1 and RTX-2 thermal relaystechnical characteristics
NStandards
Conform to standards:
- IEC/EN 60947-4-1
- IEC/EN 60947-5-1
NAmbient conditions
Storage temperature: - 40 C to 70 COperating temperature - 25 C to 60 CWorking altitude
up to 3000 m: with no change in characteristicsRelative humidity: 98%Protective treatment: Tropicalised
NMounting position
-30 +30
-90-
90
+90
NPower circuit and control circuit characteristics
RTX-1 RTX-2
For CTX contactors: 9 to 40 A 50 to 105 A 150 to 185 A 205 to 310 A
GENERAL
Class 10 A 10 A 10 A 10 AAdjustment range (A) 0.65...40 24...110 63...190 120...400Suitable for CTX 1, 9 to 40 A CTX 1, 50 to 105 A CTX 2, 150 to 185 A CTX 2, 205 to 310 A
POWER CIRCUIT
Nominal insulation Voltage(IEC 947-4) U
(V) 690 1000 1000 1000
Frequency limits (Hz) 0...400 0...400 0...400 50...60
Cabling capacity
Flange - solid wire (mm2) 16 50 120 -
Flange - flexible wire (mm2) 10 50 120 -
With flat terminal (mm) - - 25 x 5 -
Loop (solid) (mm) - - - 30 x 10Tightening torque (Nm) 2.5 4.5 6.5 23
CONTROL CIRCUIT
Nominal insulation Voltage(IEC 947-4) Ui
(V) 690
Nominal thermal rating Ith (A) 10
Nominal Voltageand current
AC-15 - Ue-Ie (V - A) 110/120 - 3; 220/240 - 2; 380/415 - 1; 480/500 - 0.8; 660/690 - 0.3DC-13 - Ue-Ie (V - A) 24 - 2; 48 - 1.4; 110 - 0.6; 250 - 0.3; 440 - 0.1
Use according to Ul and CSA B600 - Q600gL fuse (A) 10Cabling capacity (mm2) 2.5Tightening torque (Nm) 0.8
-
21
RTX-1 thermal relaystripping curves
RTX-2 thermal relaystripping curves
NTripping curves
RTX-1 Class 10 for 9 A to 40 A CTX-1 contactors
1
1.52
4
68
10
20
40
6080
100
200
15002000
4000
60008000
10000
400
600800
1000
Tripping time (s)
Multiples of the current setting
1 1.2
1.05
2 3 4 5 6 8 10 12I/Ir
Three-phaseHot state
Three-phaseCold state
Single phaseCold state
RTX-1 Class 10 for 50 A to 105 A CTX-1 contactors
1
1.52
4
68
10
20
40
6080
100
200
15002000
4000
60008000
10000
400
600800
1000
1 1.2
1.05
2 3 4 5 6 8 10 12I/Ir
Tripping time (s)
Multiples of the current setting
Three-phaseHot state
Three-phaseCold state
Single phaseCold state
NTripping curves
RTX-2 Class 10 for 150 A to 185 A CTX-2 contactors
RTX-2 Class 10 for 205 A to 310 A CTX-2 contactors
1
1.52
4
68
10
20
40
6080
100
200
15002000
4000
60008000
10000
400
600800
1000
1 1.2
1.05
2 3 4 5 6 8 10 12I/Ir
Tripping time (s)
Multiples of the current setting
Three-phaseHot state
Three-phaseCold state
Single phaseCold state
1
1.52
4
68
10
20
40
6080
100
200
15002000
4000
60008000
10000
400
600800
1000
1 1.2
1.05
2 3 4 5 6 8 10 12I/Ir
Tripping time (s)
Multiples of the current setting
Three-phaseHot state
Three-phaseCold state
Single phaseCold state
-
22
CTX-1 and CTX-2 contactors
Motor Circuit breaker Contactor Thermal relay Test
Nominalpower(kW)
Nominalcurrent
(A)Type
Nominalcurrent
(A)
Magneticthreshold
(A)Cat.Nos Type Type
Adjustmentrange
(A)Cat.Nos
Conditionalshort-circuit
currentIq (kA)
Voltage(V)
0.75 1.9 DX-MA 2.5 32 071 62 CTX-1 9 A RTX-1 1.8 - 2.7 294 61 15 4001.1 2.7 DX-MA 4 50 071 63 CTX-1 9 A RTX-1 2.5 - 4 294 62 15 4001.5 3.5 DX-MA 4 50 071 63 CTX-1 9 A RTX-1 2.5 - 4 294 62 15 4002.2 5 DX-MA 6.3 80 071 64 CTX-1 9 A RTX-1 4 - 6.3 294 63 15 4002.5 5.7 DX-MA 6.3 80 071 64 CTX-1 9 A RTX-1 4 - 6.3 294 63 15 4003 6.7 DX-MA 10 125 071 52 CTX-1 12 A RTX-1 5.5 - 8.5 294 64 15 400
3.7 8 DX-MA 10 125 071 52 CTX-1 12 A RTX-1 5.5 - 8.5 294 64 15 4004 8.5 DX-MA 10 125 071 52 CTX-1 12 A RTX-1 8 - 12 294 65 15 400
5.5 11 DX-MA 12.5 160 071 53 CTX-1 25 A RTX-1 8 - 12 294 65 15 4006.3 13 DX-MA 16 200 071 54 CTX-1 25 A RTX-1 10 - 16 294 66 15 4007.5 15 DX-MA 16 200 071 54 CTX-1 25 A RTX-1 10 - 16 294 66 15 40010 20 DX-MA 25 320 071 55 CTX-1 25 A RTX-1 17.5 - 22 294 68 15 40011 22 DX-MA 25 320 071 55 CTX-1 25 A RTX-1 17.5 - 22 294 68 15 400
12.5 25 DX-MA 25 320 071 55 CTX-1 25 A RTX-1 21 - 26 294 69 15 40015 29 DX-MA 40 500 071 56 CTX-1 32 A RTX-1 25 - 32 294 70 10 40016 31 DX-MA 40 500 071 56 CTX-1 32 A RTX-1 25 - 32 294 70 10 400
18.5 35 DX-MA 40 500 071 56 CTX-1 40 A RTX-1 30 - 40 294 71 10 40020 38 DX-MA 40 500 071 56 CTX-1 40 A RTX-1 30 - 40 294 71 10 40022 41 DX-MA 63 880 071 60 CTX-1 50 A RTX-1 30 - 43 294 73 10 40025 47 DX-MA 63 880 071 60 CTX-1 50 A RTX-1 42 - 55 294 74 10 40030 57 DX-MA 63 880 071 60 CTX-1 65 A RTX-1 54 - 65 294 75 10 400
31.5 59 DX-MA 63 880 071 60 CTX-1 65 A RTX-1 54 - 65 294 75 10 400
Motor Circuit breaker Contactor Thermal relay Test
Nominalpower (kW)
Nominalcurrent
(A)Type
Nominalcurrent
(A)
Magneticthreshold
(A)Cat.Nos Type Type
Adjustmentrange
(A)Cat.Nos
Conditionalshort-circuit
currentIq (kA)
Voltage(V)
12.5 25 DPX-H 125 25 250 250 51 CTX-1 50 A RTX-1 24 - 32 294 72 36 400
15 29 DPX-H 125 40 400 250 52 CTX-1 95 A RTX-1 24 - 32 294 72 36 400
16 31 DPX-H 125 40 400 250 52 CTX-1 95 A RTX-1 24 - 32 294 72 36 400
18.5 35 DPX-H 125 40 400 250 52 CTX-1 95 A RTX-1 30 - 43 294 73 36 400
20 38 DPX-H 125 40 400 250 52 CTX-1 95 A RTX-1 30 - 43 294 73 36 400
22 41 DPX-H 125 63 630 250 53 CTX-1 95 A RTX-1 30 - 43 294 73 36 400
25 47 DPX-H 125 63 630 250 53 CTX-1 95 A RTX-1 42 - 55 294 74 36 400
30 57 DPX-H 125 63 630 250 53 CTX-1 105 A RTX-1 54 - 65 294 75 36 400
31.5 59 DPX-H 125 63 630 250 53 CTX-1 105 A RTX-1 54 - 65 294 75 36 400
37 68 DPX-H 125 100 1000 250 54 CTX-1 105 A RTX-1 64 - 82 294 76 36 400
40 74 DPX-H 125 100 1000 250 54 CTX-1 105 A RTX-1 64 - 82 294 76 36 400
45 82 DPX-H 125 100 1000 250 54 CTX-1 105 A RTX-1 78 - 97 294 77 36 400
50 92 DPX-H 125 100 1000 250 54 CTX-1 105 A RTX-1 78 - 97 294 77 36 400
55 102 DPX-H 125 125 1250 250 55 CTX-2 150 A RTX-2 90 - 120 294 83 36 400
63 115 DPX-H 125 125 1250 250 55 CTX-2 150 A RTX-2 90 - 120 294 83 36 400
NCoordination of contactors / circuit breakers
According to IEC 60947-2Type 2 coordinationThree-pole combination
-
23
Motor Circuit breaker Contactor Thermal relay Test
Nominalpower (kW)
Nominalcurrent
(A)Type
Nominalcurrent
(A)
Magneticthreshold
(A)Cat.Nos Type Type
Adjustmentrange
(A)Cat.Nos
Conditionalshort-circuit
currentIq (kA)
Voltage(V)
15 29 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 24 - 32 294 72 50 40016 31 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 24 - 32 294 72 50 400
18.5 35 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 30 - 43 294 73 50 40020 38 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 30 - 43 294 73 50 40022 41 DPX-H 250 63 220 - 630 253 53 CTX-1 50 A RTX-1 30 - 43 294 73 50 40025 47 DPX-H 250 63 220 - 630 253 53 CTX-1 95 A RTX-1 42 - 55 294 74 50 40030 57 DPX-H 250 63 220 - 630 253 53 CTX-1 105 A RTX-1 54 - 65 294 75 50 400
31.5 59 DPX-H 250 63 220 - 630 253 53 CTX-1 105 A RTX-1 54 - 65 294 75 50 40037 68 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 64 - 82 294 76 50 40040 74 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 64 - 82 294 76 50 40045 82 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 78 - 97 294 77 50 40050 92 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 78 - 97 294 77 50 40055 102 DPX-H 250 100 350 - 1000 253 54 CTX-1 95 A RTX-2 90 - 120 294 83 50 40063 115 DPX-H 250 160 560 - 1600 253 55 CTX-2 150 A RTX-2 90 - 120 294 83 50 40075 137 DPX-H 250 160 560 - 1600 253 55 CTX-2 185 A RTX-2 110 - 140 294 84 50 40090 164 DPX-H 250 250 900 - 2500 253 56 CTX-2 185 A RTX-2 140 - 190 294 85 50 400110 204 DPX-H 250 250 900 - 2500 253 56 CTX-2 250 A RTX-2 175 - 280 294 87 50 400132 238 DPX-H 250 250 900 - 2500 253 56 CTX-2 250 A RTX-2 175 - 280 294 87 50 400150 262 DPX-H 630 320 1600 - 3200 255 42 CTX-2 250 A RTX-2 175 - 280 294 87 50 400160 282 DPX-H 630 320 1600 - 3200 255 42 CTX-2 250 A RTX-2 200 - 310 294 88 50 400
Motor Circuit breaker Contactor Thermal relay Test
Nominalpower (kW)
Nominalcurrent
(A)Type
Nominalcurrent
(A)
Magneticthreshold
(A)Cat.Nos Type Type
Adjustmentrange
(A)Cat.Nos
Conditionalshort-circuit
currentIq (kA)
Voltage(V)
15 27 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 24 - 32 294 72 50 44016 29 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 24 - 32 294 72 50 440
18.5 34 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 24 - 32 294 73 50 44020 37 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 30 - 43 294 73 50 44022 40 DPX-H 250 40 140 - 400 253 52 CTX-1 50 A RTX-1 30 - 43 294 73 50 44025 45 DPX-H 250 63 220 - 630 253 53 CTX-1 105 A RTX-1 42 - 55 294 74 50 44030 53 DPX-H 250 63 220 - 630 253 53 CTX-1 105 A RTX-1 42 - 55 294 74 50 440
31.5 56 DPX-H 250 63 220 - 630 253 53 CTX-1 105 A RTX-1 54 - 65 294 75 50 44037 65 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 64 - 82 294 76 50 44040 71 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 64 - 82 294 76 50 44045 78 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 64 - 82 294 76 50 44050 88 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 78 - 97 294 77 50 44055 98 DPX-H 250 100 350 - 1000 253 54 CTX-1 105 A RTX-1 90 - 110 294 78 50 44063 110 DPX-H 250 160 560 - 1600 253 55 CTX-2 150 A RTX-1 90 - 110 294 78 50 44075 129 DPX-H 250 160 560 - 1600 253 55 CTX-2 150 A RTX-2 110 - 140 294 84 50 44090 157 DPX-H 250 160 560 - 1600 253 55 CTX-2 185 A RTX-2 140 - 190 294 85 50 440110 188 DPX-H 250 250 900 - 2500 253 56 CTX-2 250 A RTX-2 175 - 280 294 87 50 440132 218 DPX-H 250 250 900 - 2500 253 56 CTX-2 250 A RTX-2 175 - 280 294 87 50 440150 244 DPX-H 630 250 900 - 2500 253 56 CTX-2 310 A RTX-2 175 - 280 294 87 50 440
-
24
CTX-1 contactorsdimensions
NDimensions
Size 1 contactors
Size 2 contactors
45
85
7.5
35
4.5
735081
4.5 7.5
40
45
55 98
87 50 60 79
Size 3 contactors
4.5 7.5
40
45
55 98
87 50 60 79
Size 4 contactors
66
116
9
56
60
117.
5
90
5.5
Size 5 contactors
126
75
117.
5
56
9
90
5.5
Auxiliary contactsCat.Nos 297 12/13
Cat.Nos 297 14/15
Interlocking accessories
11 85
29
44.5
10.3
851.4 11
78
-
25
CTX-2 contactorsdimensions
NDimensions
Size 1 contactors
45 18 4106.8
2
148.
5
164
160 1
5.5
178
112112
102
613.511.5
961 18
M8
38 38
165.5
Size 2 contactors
165
180
105
120 25 5
150
150 208
48 48 12
60
200
187
307
212
==
8
9 7
M10
11.5
Interlocking accessoriesCat.No 297 61
55
Cat.No 297 62
51
350
Auxiliary contactsCat.Nos 297 14/15
29
44.5
10.3
-
26
RTX-2 thermal relaysdimensions
NDimensions
Size 1 thermal relays
108
42
M640
137
82.7
5
86
70
36.5
104
40.5
38 38
18
9 15 M83
Size 2 thermal relays
135
22.5 22.5
48 48 55
10 4
235
130
130
177
7
M10
RTX-1 thermal relaysdimensions
NDimensions
Size 1 thermal relays
8.85 5.792.5
13.5
64
34.5
Size 2 thermal relays
8.85
5779.7
40
109.7
-
27
CTX-C contactors12.5 kVar to 70 kVar three-pole contactors for connectingcapacitor banks
Technical characteristics (p. 28)Dimensions (p. 29)
Three-pole contactors equipped with prefabricated auxiliary contactsand discharge resistors for connecting three-phase capacitor banksConform to standards: IEC/EN 60947-1, IEC/EN 60947-4-1,IEC/EN 60947-5-1
CTX-C contactorsreplacement coils
Technical characteristics (p. 28)
Pack Cat.Nos CTX-C contactors
Three-pole contactorsMax. reactive power calculated for an ambienttemperature 55 C12.5 kVAR/25 AMax. reactivepower kVAR Control Voltage
Integratedauxiliary contact Dimensions
1 296 02 12.5 110 VA 1 NO + 1 NC Size 11 296 04 12.5 230 VA 1 NO + 1 NC Size 11 296 05 12.5 440 VA 1 NO + 1 NC Size 1
16.7 kVAR/32 A1 296 12 16.7 110 VA 1 NO + 1 NC Size 11 296 14 16.7 230 VA 1 NO + 1 NC Size 11 296 15 16.7 440 VA 1 NO + 1 NC Size 1
20 kVAR/45 A1 296 22 20 110 VA 1 NO + 1 NC Size 21 296 24 20 230 VA 1 NO + 1 NC Size 21 296 25 20 440 VA 1 NO + 1 NC Size 2
30 kVAR/60 A1 296 32 30 110 VA 1 NO + 1 NC Size 31 296 34 30 230 VA 1 NO + 1 NC Size 31 296 35 30 440 VA 1 NO + 1 NC Size 3
45 kVAR/90 A1 296 42 45 110 VA 1 NO + 1 NC Size 41 296 44 45 230 VA 1 NO + 1 NC Size 41 296 45 45 440 VA 1 NO + 1 NC Size 4
55 kVAR/110 A1 296 52 55 110 VA 1 NO + 1 NC Size 41 296 54 55 230 VA 1 NO + 1 NC Size 41 296 55 55 440 VA 1 NO + 1 NC Size 4
70 kVAR/140 A1 296 62 70 110 VA 1 NO + 1 NC Size 51 296 64 70 230 VA 1 NO + 1 NC Size 51 296 65 70 440 VA 1 NO + 1 NC Size 5
Pack Cat.Nos Replacement coils for CTX-C contactors
For contactors 12.5 kVAR to 20 kVARControl Voltage(50/60 Hz)
5 297 01 110 VA5 297 02 230 VA5 297 80 440 VA
For contactors 30 kVAR5 297 05 110 VA5 297 06 230 VA5 297 81 440 VA
For contactors 45 kVAR to 70 kVAR5 297 09 110 VA5 297 10 230 VA5 297 82 440 VA
297 02
296 04 296 64
-
28
CTX-C contactorstechnical characteristics
NStandards
Conform to standards:
- IEC/EN 60947-4-1
- IEC/EN 60947-5-1
NAmbient conditions
Storage temperature: - 50 C to 80 COperating temperature - 25 C to 55 C (with no reduction)Working altitude up to 3000 m: with no change in characteristics
NMounting position
Vertical mounting +/- 30
NPower circuit and control circuit characteristics
25 A 32 A 45 A 60 A 90 A 110 A 140 A
POWER CIRCUIT (POLES)
Nominal Voltage (V) 690 690 690 690 690 690 690
Nominal insulation Voltagesaccording to IEC 947 (V) 1000 1000 1000 1000 1000 1000 1000
Thermal current (A) 25 32 45 60 90 110 140
Max. operating power at 55C
230/240V (kVar) 7.5 10 12.5 20 25 35 45
380/400V (kVar) 12.5 16.7 20 30 45 55 70
660/690V (kVar) 15 20 25 35 55 65 85
Electrical endurance (operations) 280.000 280.000 280.000 200.000 150.000 120.000 90.000
Max. operations/hour (operations/hour) 350 350 350 240 150 150 150
CONTROL CIRCUIT
Standard Voltages50 Hz (V) 24-690 24-690 24-690 24-690 24-690 24-690 24-690
60 Hz (V) 24-600 24-600 24-600 24-600 24-600 24-600 24-600
Consumption
Frequencycircuit open (VA) 45 45 48 88 191 191 198
circuit closed (VA) 6 6 7 9 15.5 15.5 17
Dual frequency 50 Hzcircuit open (VA) 54 54 58 125 245 245 250
circuit closed (VA) 7 7 8 11.5 20 20 23
Dual frequency 60 Hzcircuit open (VA) 35 35 39 110 215 215 220
circuit closed (VA) 5 5 6 11 15 15 19
INSTANTANEOUS AUXILIARY CONTACT BLOCKS
Nominal insulation Voltage Ui (V) 100
Thermal current Ith (A) 10
-
CTX-C contactorsdimensions
NDimensions
Size 1 contactors
Size 2 contactors
82.5
45
7350
35
4.5 131
137.5
7.5
85.5
7350
35 45
564.5 133
139.5
7.5
Size 3 contactors
60
90.5
79 50
40
4.5
45
66 144
150.5
55 7.5
Size 4 contactors
Size 5 contactors
118.
5
90
56
60
77 162
168.5
66 9
5.5
90
128.
5
56 86 172
178.5
75 9
5.5
-
World Headquarters andInternational Department28, av. du Marchal-de-Lattre-de-Tassigny87045 Limoges Cedex - France : + 33 5 55 06 87 87Fax : + 33 5 55 06 74 55www.legrandgroup.com
EX21
0016
-Ja
nuar
y20