No Yes No Yes No Yes No Yes No Yes No Hydraulics Electric Pneumatic Yes No Yes No Yes No Yes No Yes Date Contractor's Material & Test Certificate for Aboveground Piping PROCEDURE Upon completion of work, inspection and tests shall be made by the contractor's representative and wttnessed by an owner's representattve. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities. owners. and contractor. It ts understood the owner's representalive's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances. Property name Property address Accepted by approving authorities (names) Temperature rating Quality Orifice size Years of manufacture Model Maximum time to operate through test connection Seconds Minutes Model Make Serial no. Model Make Serial no. Model Alarm operated properly Time water reached test outlet Trip point air pressure Air pressure Water pressure No Yes Seconds Minutes psi psi Seconds Seconds Yes No Yes No Minutes Maximum time to operate release Does each circuit operate valve release? Does each circuit operate supervision loss alarm? Model Measured from time Inspector's test connectton is opened Make Is there an accessible factlity in each circuit for testing? If no, explain Does valve operate from the manual trip, remote, or both control stations? Detecting media supervtsed Piping supervised Operation If no, explain With Q.O.D Without Q.O.D Minutes Time to trip through test connection Make Q.O.D Dry valve Type Alarm device Make Supplies buildings 3. NFPA 25 2. Care and matntenance instructions 1. System components instructions Have copies of the followtng been left on the premises? Has person in charge of fire equipment been instructed as to location of control valves and care and maintenance of this new equipment? If no, explain? Address Installation conforms to accepted plans Equipment used is approved If no, explain deviations Plans Instructions Location of system Type of fittings Type of pipe Sprinklers Pipe and fittings Alarm valve or flow indicator Dry pipe operating test Deluge and preaction valves 335 Renfrew Drive. Suite 302. Markham. Ontario L3R 9S9 Tel: (905) 477-2270 Fax: (905) 477-3611 E-Mail: [email protected] www.casa-firesprinkler.org

Upload: nguyenduong

Post on 14-Aug-2018

299 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Contractor's Material & Test Certificate for Aboveground ...€¦ · Contractor's Material & Test Certificate for Aboveground Piping PROCEDURE ... piping Verified by copy of the Underground

NoYes

NoYes

NoYes

NoYes

NoYes

No

HydraulicsElectricPneumatic

Yes NoYes

NoYes

NoYes

NoYes

Date

Contractor's Material & Test Certificate for Aboveground PipingPROCEDUREUpon completion of work, inspection and tests shall be made by the contractor's representative and wttnessed by an owner's representattve. All defects shall be corrected and system left in service before contractor's personnel finally leave the job.A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities. owners. and contractor. It ts understood the owner's representalive's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances.

Property name

Property address

Accepted by approving authorities (names)

Temperature ratingQualityOrifice sizeYears of manufactureModel

Maximum time to operate through test connection

SecondsMinutesModelMake

Serial no.ModelMakeSerial no.Model

Alarm operatedproperly

Time waterreached test outlet

Trip pointair pressure

Airpressure

Waterpressure

NoYesSecondsMinutespsipsiSeconds

SecondsYes No Yes No Minutes

Maximum time to operate releaseDoes each circuit operatevalve release?

Does each circuit operatesupervision loss alarm?

Model

Measured from time Inspector's test connectton is opened

Make

Is there an accessible factlity in each circuit for testing?If no, explain

Does valve operate from the manual trip, remote, or both control stations?

Detecting media supervtsedPiping supervised

Operation

If no, explain

With Q.O.D

Without Q.O.D

Minutes

Time to tripthrough test connection

Make

Q.O.DDry valve

Type

Alarm device

Make

Supplies buildings

3. NFPA 25

2. Care and matntenance instructions

1. System components instructions

Have copies of the followtng been left on the premises?

Has person in charge of fire equipment been instructed as to location of control valves and care and maintenance of this new equipment?If no, explain?

Address

Installation conforms to accepted plans Equipment used is approved

If no, explain deviations

Plans

Instructions

Location ofsystem

Type of fittings

Type of pipe

Sprinklers

Pipe andfittings

Alarmvalve or

flowindicator

Dry pipeoperating

test

Deluge andpreaction

valves

335 Renfrew Drive. Suite 302. Markham. Ontario L3R 9S9 Tel: (905) 477-2270 Fax: (905) 477-3611E-Mail: [email protected] www.casa-firesprinkler.org

Page 2: Contractor's Material & Test Certificate for Aboveground ...€¦ · Contractor's Material & Test Certificate for Aboveground Piping PROCEDURE ... piping Verified by copy of the Underground

Pressurereducing

valve test

Testdescription

Tests

Welding

Blank testinggaskets

Cutouts(discs)

Hydraulicdata

nameplate

Remarks

Signatures

Location and floor

psi (bar) for hoursAll piping hydrostatically tested at

Dry piping pneumatically tested

Equipment operates properly

II no, state reason

Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives of sodium silicate, brine, or other corrosive chemicals were not used for testing systems or stopping leaks?

Underground mains and lead in connections to system risers flushed before connection made to sprinkler piping

Verified by copy of the Underground Form flushed by installer of underground sprinkler piping

Other

Explain

If powder-driven fasteners are used in concrete, has representative sample testing be satisfactorily completed?

If no, explain

Number used

Welding pipingIf yes...

Do you certify as the sprinkler contractor that welding procedures comply with the requirements of at least AWS 82. 1?

Do you certify that the welding was performed by welders qualified in compliance with the requirements of at least AWS 82.1?

Do you certify that the welding was earned out in compliance with a documented quality control procedure to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding residue are removed, and that the internal diameters of piping are not penetrated?

Do you certify that you have a control feature to ensure that all cutouts (discs) are retrieved?

Nameplate provided

If no. explain

Date left in service with all control valves open

Name of sprinkler contractor

For property owner (signed)

For sprinkler contractor (signed)

Additional explanations and notes

Title

Tests witnessed by

Date

Title & CASA Number Date

Locations Number removed

Draintest

Reading of gauge located near water supply test connection:psi ( bar)

Make and model Setting Static pressure

Inlet (psi)

HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for 2 hours or 50 psi (3.4 bar) above static pressure in excess ol 150 psi (10.2 bar) for 2 hours. Differential dry-pipe valve clappers shall be left open during the test to prevent damage. All aboveground piping leakage shall be stopped.PNEUMATIC: Establish 40 psi (2.7 bar) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours.

Outlet (psi) Inlet (psi) Outlet (psi) Flow (gpm)

Residual pressure (flowing) Flow rate

Residual pressure with valve in test connection open wide:psi ( bar)

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes

NoYes