community energy efficiency program final report · community energy efficiency program final...
TRANSCRIPT
Community Energy Efficiency Program Final Report Illawarra Catholic Club
Club Central Hurstville and Menai “Club Central is Sustainability Central, Innovative lighting project at Club Central sites”
Prepared for:
Prepared by:
Reference:
Date:
Department of Industry
Kevin Tu
CEEP2181
30 September 2014
“This activity received funding from the Australian Government”
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 2 of 22
Quality Control
Author Kevin Tu
Reviewer Dr Mirek Piechowski
Reference Number CEEP2181
Revision 1.0
Edition Date 30 September 2014
Print Date 30 September 2014
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 3 of 22
Contents
1. Executive Summary ................................................................................................................................. 4
2. Objectives and Benefits ........................................................................................................................... 5
2.1. Energy Efficiency outcomes .................................................................................................................. 7
2.1.1. Club Central Hurstville .................................................................................................................. 7
2.1.2. Club Central Menai ..................................................................................................................... 10
2.2. Financial outcomes ............................................................................................................................. 13
2.2.1. Project Budget ............................................................................................................................ 13
2.3. Social/Community outcomes .............................................................................................................. 14
2.4. Other outcomes .................................................................................................................................. 16
3. Project operation, mechanisms and processes ...................................................................................... 17
4. Conclusion ............................................................................................................................................. 18
Certification ................................................................................................................................................... 19
Appendix: Lighting equipment ....................................................................................................................... 20
Club Central Hurstville ...................................................................................................................................... 20
Club Central Menai ........................................................................................................................................... 22
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 4 of 22
1. Executive Summary
The overall result of the project is a successful reduction in the energy intensity of both Club Central Hurstville
and Club Central Menai. A total of 1947 lamps were replaced at both sites, comprising of a mixture of LED’s
and fluorescents.
In particular, the following energy efficiency objectives were achieved:
Club Central Hurstville: Decrease in energy intensity of 307.6 MJ/m2
Club Central Menai: Decrease in energy intensity of 30.82 MJ/m2
Overall, this was a 28.4% improvement over initial expected outcomes. A large contributing factor to this result
was that a large quantity of lighting equipment was installed at the site which was not originally scoped or
estimated in the initial stages.
The project was achieved within budget, though there were a number of amendments to the lighting
equipment supplied.
The total spend for the project was $290,069.50 ex GST; under the expected spend of $303,974 ex GST.
The expected savings for the project is estimated to be $118,200/year for Club Central Hurstville, and
$10,448/year for Club Central Menai, resulting in a 2.25 year payback.
To date, CEEP funding of $129,818 has been paid to date with a payment of $14,424 to be paid on completion
of the 5th
milestone report. The total funding following this payment will be $144,242.
Preliminary results of a community driven survey showed that the majority of staff and patrons were aware of
the clubs energy efficiency activities. Furthermore, the objectives of the project were generally accepted as an
important motivation for the clubs ongoing business.
Furthermore, Illawarra Catholic Club’s involvement with Energy Action Limited throughout this project has also
resulted in the installation of a 100kW Solar PV array at Club Central Menai. As such, the CEEP funded lighting
project has allowed for a broader uptake of energy efficiency and renewable energy generation initiatives.
Disclaimer:
“The views expressed herein are not necessarily the views of the Commonwealth of Australia, and the
Commonwealth does not accept responsibility for any information or advice contained herein.”
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 5 of 22
2. Objectives and Benefits
The objectives of the project were twofold:
1. Communicate the objectives of the program to staff and patrons of the clubs
2. Improve the energy efficiency of the following clubs:
a. Club Central Hurstville
b. Club Central Menai
These objectives were to be achieved through the implementation of the following:
Communication:
The objectives and outcomes of the project were to be communicated through the following methods:
1. Energy efficiency web posts on the club website
2. Implementation of a project banner outlining the project objectives
Energy Efficiency:
Club Central Hurstville and Menai were to undergo a complete lighting upgrade. This solution comprised of the
following technologies and recommendations:
Front of house
The front of house areas are primarily lit with 12V50W Halogen dichroic recessed fixtures. These fittings
consume approximately 50W per lamp and between 2 and 15W in losses in the transformer,
Solution
All of these fittings were replaced with either new lower wattage LED fixtures or LED replacement
lamps within the existing fixtures
This recommendation provides the following benefits to Club Central - Hurstville
These fittings will maintain the look and feel of a warm and welcoming environment for the club
This will also reduce the maximum of the lighting load from 50W per lamps to approximately 7 –
<15W per fixture, depending on the requirement. This will reduce the maximum consumption of the
fixture over the life of the installation significantly from 60W on Old Fixtures to a Maximum of 15W
with an energy saving in excess of 72% in the new fixtures
Due to the long life components and lamps of these fixtures, additional savings will also be realised
through a significant reduction in maintenance costs for many years.
Back of house
These areas are mainly lit by 2 x 36W Fluorescent Fixtures c/w diffusers. As well as some smaller wattage
fixtures
Solution
Fluorescent fixtures be retrofitted with LED tubes at approximately 20W per 1.2mtr Tube and 11
watts per 600mm tube and in some cases be replaced with 2 x 28W and 2 x 14W T5 Fixtures
Dock
This area is lit with 150W Metal Halide Low bays and fluorescent fittings fitted with maintained emergency
packs to activate if power is lost to the area
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 6 of 22
Solution
These 150W Fixtures and the 400W Lowbay fixtures in the driveway to the car park should be
changed to 100W LED highbays, providing a better quality of light and a lower wattage. The
maintained Emergency fittings will be replaced with LED Maintained emergency fixtures
Car Park
The carpark is lit with 2 x 36W Fluorescent Fixtures with wire guards a large percentage of these have
Maintained emergency to enable them to operate in the event of a power outage
Solution
These fittings were replaced with a LED fixtures of a much reduced wattage that can operate in a
standby mode, only coming to full brightness when someone is in the area. This is beneficial for
lowering consumption and for safety in the carpark environment.
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 7 of 22
2.1. Energy Efficiency outcomes
2.1.1. Club Central Hurstville
From the available electricity data, a clear decline in energy consumption is observed from the date of project
completion circa June 2014. Therefore, the post project period is taken to be June 2014 – August 2014.
In order to verify the savings from the lighting project, the following has been taken into account:
Seasonal variations in site activity
Post-project period should be taken as 1st
June 2014 – 30th
August 2014
Pre-project baseline is taken as the 2012 annual consumption
The pre-project period is assumed to remain as the annual 2012 consumption figure.
0
50,000
100,000
150,000
200,000
250,000
300,000
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Co
nsu
mp
tio
n (
kWh
)
Month
Club Central Hurstville
2012
2013
2014
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 8 of 22
The following table shows the monthly consumption from 2012 – 2014.
Month 2012 2013 2014
Jan 247,605 223,402 225,627
Feb 221,848 204,486 196,792
Mar 219,757 221,115 214,942
Apr 195,701 197,955 190,215
May 184,378 183,452 180,423
Jun 164,805 157,074 162,116
Jul 161,914 175,276 150,156
Aug 174,345 180,717 146,580
Sep 176,309 196,481
Oct 183,147 211,203
Nov 204,951 198,755
Dec 218,341 222,985
Total 2,353,099 2,372,903
Savings have been calculated on a linear extrapolation from the measured daily energy consumption to 365
days annual consumption.
Pre-Project Post-Project
Start Date 1/01/2012 1/06/2014
End Date 31/12/2012 30/08/2014
Annual consumption (kWh/year) 2,353,099 458,852
Daily consumption (kWh/day) 6,429 5,042
Daily savings (kWh/day)
1,387
Annual savings (kWh/year)
506,221
Average elec. Cost (c/kWh) 18.11
Annual cost savings ($/year) $91,677
Annual maintenance savings ($/year)
$26,523
Total Annual cost savings ($/year)
$118,200
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 9 of 22
Name of site Club Central Hurstville
Location (address) 2 Crofts Ave Hurstville NSW 2220
Type of site Club facility
Activity Type and Measure Upgrade of lighting system
Energy Efficiency Estimate Method Energy usage and savings determined from the specified wattage of the equipment and its associated losses
Baseline Energy Usage 2,353,099 kWh / year
Baseline Energy Efficiency 2,353,099 kWh / year x 3.6 MJ/kWh / 6000 m2 = 1411.86MJ/m2
Energy Efficiency Improvement Reduction 506,221 kWh / year x 3.6 MJ/kWh / 6000 m2 = 307.59 MJ/m2
Reporting Data (Measuring Energy Efficiency and Additional Data)
A total area of 6000 m2
Hourly operation of various lighting equipment determined from typical business operational assumptions
Lights operate from 1820 – 8736 hours / year depending on location, purpose, etc.
Club Trading Hours: Sun - Thurs 10am - 2am Fri & Sat 10am - 4am
Building construction date: 1970
Cost of Activity $223,592.40
Estimated Cost Savings $118,200 / year
The savings shown here are significantly higher than the expected outcomes of the project. The original
estimate of annual energy savings was expected to be: 347,215kWh/year.
Several factors may have contributed to this figure:
Difference in actual operating hours vs. Estimated operating hours
Changes to the clubs activity levels
A replacement of 165x 50W halogen down lights with 7W LED down lights in addition to the original
estimate
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 10 of 22
2.1.2. Club Central Menai
There were two energy related projects that occurred at this site:
1. 100kW Solar PV Rooftop array
2. CEEP Funded lighting project
The completion of the lighting project occurred in prior to December 2013, and the Solar PV array was
commissioned and fully functioning by the start of January 2014.
Therefore, in order to verify the savings from the lighting project, the following must be taken into account:
Seasonal variations in site activity
Post-project period should be taken as 1st
January 2014 – 30th
August 2014
Pre-project baseline should be taken as the 2013 annual consumption (discussed further below)
Solar PV generated power must be measured and accounted for during the post project period
As can be seen from the above graph the energy consumption in 2014 is trending below the 2013 levels, with
an exception of July-August period. This may be attributed to an increased activities on the site and is unlikely
to be an indication of failed energy efficiency objectives. It can be clearly seen that the 2012/2013
consumption is fairly consistent, and the energy savings from both the Solar PV project and the lighting project
are clearly visible.
Regardless, the energy consumption of the full 8 month period from 1st
January 2014 – 30th
August 2014 has
been taken into account.
0
20,000
40,000
60,000
80,000
100,000
120,000
140,000
160,000
180,000
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Co
nsu
mp
tio
n (
kWh
)
Month
Club Central Menai
2012
2013
2014
2014 No PV
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 11 of 22
It should be noted that there was an increase in energy consumption from 2012 – 2013 which was unrelated
to the project objectives and is likely due to increased activity at the club. As a result, measuring the improved
performance from the original 2012 baseline imposes a 57,461kWh penalty, understating the savings from the
project.
Therefore, it is proposed here that the baseline be measured from the 2013 annual consumption.
The following table shows the monthly consumption from 2012 – 2014. The output of the PV array has been
added back to the utility measured consumption for 2014 to determine the true energy consumption of the
site. This consumption value has been used to determine the subsequent savings of the lighting project.
Month 2012 2013 2014 2014 No PV
Jan 155,836 153,999 120,221 130,878
Feb 130,235 127,842 105,460 115,612
Mar 125,475 131,165 115,470 126,202
Apr 111,843 117,278 100,175 109,225
May 114,489 131,562 109,938 117,281
Jun 126,390 140,265 125,634 132,652
Jul 138,171 143,601 139,416 148,213
Aug 123,993 134,437 135,435 145,197
Sep 112,374 121,271
Oct 118,271 126,893
Nov 128,516 124,978
Dec 141,834 131,595
Total 1,527,425 1,584,886 951,748 1,025,261
Savings have been calculated on a linear extrapolation from the measured daily energy consumption to 365
days annual consumption.
Pre-Project Post-Project
Start Date 1/01/2013 1/01/2014
End Date 31/12/2013 30/08/2014
Annual consumption (kWh/year) 1,584,886 1,025,261
Daily consumption (kWh/day) 4,342 4,237
Daily savings (kWh/day) 106
Annual savings (kWh/year) 38,521
Average elec. Cost (c/kWh) 18.97
Annual cost savings ($/year) $7,307
Annual maintenance savings ($/year)
$3,141
Total Annual cost savings ($/year)
$10,448
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 12 of 22
Name of site Club Central Menai
Location (address) 44-60 Allison Crescent Menai NSW 2234
Type of site Club facility
Activity Type and Measure Upgrade of lighting system
Energy Efficiency Estimate Method Energy usage and savings determined from the specified wattage of the equipment and its associated losses
Baseline Energy Usage 1,584,886 kWh / year
Baseline Energy Efficiency 1,584,886 kWh / year x 3.6 MJ/kWh / 4500 m2 = 1267.91 MJ/m2
Energy Efficiency Improvement Reduction 38,521 kWh / year x 3.6 MJ/kWh / 4500 m2 = 30.82 MJ/m2
Reporting Data (Measuring Energy Efficiency and Additional Data)
A total area of 4500 m2
Hourly operation of various lighting equipment determined from typical business operational assumptions
Lights operate from 1820 – 8736 hours / year depending on location, purpose, etc.
Club Trading Hours: Sun - Thurs 10am - 2am Fri & Sat 10am - 4am
Building construction date: 1997
Cost of Activity $72,477.10
Estimated Cost Savings $10,448 / year
While the savings shown here are lower than the expected outcomes of the project, several factors may have
contributed to this outcome:
Difference in actual operating hours vs. estimated operating hours
Changes to the clubs activity levels
In particular, as mentioned previously, there appears to be a substantial increase in club activity from June
2014 onwards.
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 13 of 22
2.2. Financial outcomes
2.2.1. Project Budget
The original budget expected that Illawarra Catholic Club would co-contribute $159,732 ex GST, whilst
receiving funding of $144,242. As such, the total expected spend was $303,974 ex GST.
CEEP funding of $129,818 has been paid to date with a payment of $14,424 to be paid on completion of the 5th
milestone report. The total funding following this payment will be $144,242.
CEEP Illawarra Catholic Club Other
Contribution $129,818.00 $159,732.00 $0.00
Expenditure $129,818.00 $166,251.50 $0.00
Total $129,818.00 $166,251.50 $0.00
Balance $7,904.50
The total expenses for the project amounted to $296,069.50 ex GST.
Therefore, the total project cost has come under budget by $7,904.50 ex GST.
There were several changes to the budget of the project over the period. In particular, there were some
technologies which were deemed not fit for purpose, resulting in returned equipment. Furthermore, the
expectations of the project were that the majority of the clubs lighting would be fitted with new LED lamps.
Shortfalls in the initial light count resulted in a further supply of several lights.
As project progressed changes to the budget and associated costs were addressed on a case by case basis, as
agreed between Energy Action Limited and Illawarra Catholic Club. The reasons for this are summarised as
follows:
Changes to recommended technologies
Inclusions/exclusions with respect to the initial light count
Delays in supply of some product
Specifically, the following amendments were made to the budget:
Amendment Value (ex GST)
Supply of extra 165x 7W LED Lamps $9,075
Supply of SAR Lighting upgrade kits $6,400
Credit for returned lights at Hurstville -$18,700
Credit for returned lights at Menai -$12,440
Extra Lighting @ 2 Crofts Avenue Hurstville $1,396
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 14 of 22
2.3. Social/Community outcomes
Energy efficiency continues to play a key role at Club Central Menai and Hurstville. The key stakeholders were
both the Club Central staff and patrons. A short survey was provided to club members to determine the
community’s general opinion and awareness of energy efficiency.
From these preliminary results, the following generalised opinions can be summarised as:
1. Energy efficiency should be prioritised for businesses
2. Solar PV and lighting technologies are generally viewed to be viable
3. Though the community is fairly aware of the energy efficiency activities occurring at the club, there is
still room to improve and to further promote these measures.
The survey results are shown in the table below:
Question Strongly Disagree
Disagree Neutral Agree Strongly Agree
Total
1. Club Central is committed to energy efficiency and sustainability 1 1 15 54 40 111
2. LED lighting is a viable alternative to fluorescent/halogen lighting 0 4 16 40 54 114
3. Business’s should find more ways to be energy efficient 0 0 5 40 65 110
4. Sustainability and reducing your carbon footprint is important to you 0 1 21 32 58 112
5. Solar power is a viable technology 0 0 9 41 61 111
6. I am aware of Club Central’s current energy efficiency projects 1 7 25 42 36 111
Approximately 112 participants were involved in the survey. The proportion of overall responses is shown in
the figures below. The distribution is heavily weighted
0
20
40
60
80
100
120
Q1 Q2 Q3 Q4 Q5 Q6
No
. re
spo
nse
s
Question
Strongly Agree
Agree
Neutral
Disagree
Strongly Disagree
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 15 of 22
Furthermore, Illawarra Catholic Club implemented two other publicity measures that aided in communicating
the clubs energy efficiency activities.
1. Energy Efficiency web post on the club’s website
2. An energy efficiency brochure was handed out to club patrons
These two methods of communicating the clubs initiatives are reflected in the results of the survey.
Additionally, frequent patrons and staff of the club would be able to see the transformation of the clubs
lighting as the project progressed towards completion.
2, 0% 13, 2%
91, 14%
249, 37%
314, 47% Strongly Disagree
Disagree
Neutral
Agree
Strongly Agree
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 16 of 22
2.4. Other outcomes
Some of the other outcomes that were achieved include:
Improved lighting quality across the site
Improved awareness of energy efficiency amongst staff and club patrons
Reduced maintenance costs
The project provides improved quality of service for the staff and club patrons of Club Central Hurstville and
Menai. Furthermore, a reduction in operating costs for the site frees up resources to be invested into
improved facilities, functions and events at the club.
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 17 of 22
3. Project operation, mechanisms and processes
The lighting upgrade project grant was managed by a representative from Energy Action Limited. In this
capacity, Energy Action acted as both the project manager and lighting consultant.
The responsibilities were as follows:
Carry out the lighting audit and propose recommendations
Organise the supply of recommended technologies
Assist in managing the CEEP grant reporting requirements
Verify the savings from the project
Three key representatives from Illawarra Catholic Club assisted in managing the project from the clients
perspective. These representatives included:
Mike Walker – CEO
Andrew Brookfield – Facilities Manager (Menai)
Tim Williams – Maintenance Supervisor (Hurstville)
The responsibilities of the facilities managers and supervisors were to manage the installation of the lighting
equipment, as well as to provide site specific information from a building and operations perspective.
The role of the CEO was to manage the progress of the overall project, project finances, and funding related
activities.
In general, this stakeholder structure worked well. However, some stages of the project could have been
managed more efficiently, particularly in relation to managing the selection and approval process of various
lighting solutions.
In addition, changes to key staff posed challenges in communication between project stakeholders.
Some improvements to this structure may include:
Formalised lines of communication in relation to managing timelines and expectations to mitigate
risks
Consistent progress reporting adhering to key milestone dates
More efficient management of the above aspects of the projectwould likely have prevented the majority of
the issues faced throughout the project period.
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 18 of 22
4. Conclusion
The objectives of the project were achieved upon completion of the relevant milestones. The overall
performance of the lighting upgrade has been better than expected.
In general, the proposed lighting solution met the requirements of both sites. It should be noted that in
particular, formal approval process of any new equipment plays an important role in determining whether a
particular technology meets client requirements.
In terms of lessons learnt we would make the following comments:
Scope of works should be clearly defined before commencement
Project timelines should be maintained throughout the project
Any changes to the scope or timelines should be clearly communicated
Proposed solutions should be formally reviewed and approved before implementation
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 20 of 22
Appendix: Lighting equipment
Club Central Hurstville
Location Product Code Final Solution Qty
Club Down Lights D5 Double Square
10w Dichroic LED Lamp 10W Phillips LED 88
Club Down Lights D8 Suspended
10w Dichroic LED Lamp 10W Phillips LED 30
Club Down Lights W1 Up / Down
10w Dichroic LED Lamp 10W Phillips LED 70
Lifts 10w Dichroic LED Lamp 10W Phillips LED 46
Driveway BY619P LED100/CW PSU NB/911401578201
100w Philips NB Highbay 11
Back Of House 1 FL36/865 replacement 36w Lamp 5
Back Of House 1 FL36/865 replacement 36w Lamp 4
Loading Dock FL36/865 replacement 36w Lamp 6
Club Down Lights D6 Entry Awnings 8"
LED7V5DK 7w LED KIT 22
Club Down Lights D9 8" Awnings
LED7V5DK 7w LED KIT 9
Back Of House 2 CIT-06-08W-FR65-R 600mm Fluorescent tube 18
Back Of House 3 Staff Room
CIT-06-08W-FR65-R 600mm Fluorescent tube 36
Change Rooms CIT-06-08W-FR65-R 600mm Fluorescent tube 26
Fire Stairs Middle CIT-06-08W-FR65-R 600mm Fluorescent tube 2
Kitchen 3 CIT-06-08W-FR65-R 600mm Fluorescent tube 6
Kitchen 3 CIT-06-08W-FR65-R 600mm Fluorescent tube 4
Cleaners Lights Gaming Area
CIT-12-17W-FR65-R 1200mm Fluorescent tube 28
Driveway CIT-12-17W-FR65-R 1200mm Fluorescent tube 8
Function Kitchen CIT-12-17W-FR65-R 1200mm Fluorescent tube 12
Function Kitchen CIT-12-17W-FR65-R 1200mm Fluorescent tube 4
Function Store Room CIT-12-17W-FR65-R 1200mm Fluorescent tube 4
Kitchen 3 CIT-12-17W-FR65-R 1200mm Fluorescent tube 56
Kitchen 3 CIT-12-17W-FR65-R 1200mm Fluorescent tube 6
Loading Dock CIT-12-17W-FR65-R 1200mm Fluorescent tube 4
Meeting Room CIT-12-17W-FR65-R 1200mm Fluorescent tube 54
Stage Lights CIT-12-17W-FR65-R 1200mm Fluorescent tube 5
Club Down Lights D11 LED7V5DK-WW 7w LED KIT Dimmable 43
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 21 of 22
Recess
Club Down Lights D3 Round
LED7V5DK-WW 7w LED KIT Dimmable 52
Club Down Lights D7 LED7V5DK-WW 7w LED KIT Dimmable 28
Meeting Room LED7V5DK-WW 7w LED KIT Dimmable 618
Stage Lights LSMLBD228E 2 x 28W Smart Light 2
Cleaners Lights Gaming Area
LSMLBD228E 2 x 28W Smart Light 6
Driveway LSMLBD228E 2 x 28W Smart Light 4
Car Parks SN450MFL-100-P-E Chamaeleon 10 Emergency Perm On 5
Loading Dock SN450MFL-102-E Chamaeleon 12 Sensor Emergency 76
Car Parks SN450MFL-102-S Chamaeleon 10 Sensor 115
Car Parks SN450MFL-102-S Chamaeleon 10 Sensor 12
Loading Dock SN450MFL-102-S Chamaeleon 10 Sensor 10
Plant Room SN450MFL-102-S Chamaeleon 10 Sensor 17
Plant Room SN450MFL-102-S Chamaeleon 10 Sensor 5
Car Parks SN450MFL-122-E Chamaeleon 10 Sensor Emergency 4
Fire Stairs Back SN450MFL-122-E Chamaeleon 10 Sensor Emergency 23
Fire Stairs Middle SN450MFL-122-E Chamaeleon 10 Sensor Emergency 4
Fire Stairs North 1 SN450MFL-122-E Chamaeleon 10 Sensor Emergency 11
Fire Stairs North 2 SN450MFL-122-E Chamaeleon 10 Sensor Emergency 23
Fire Stairs South 1 SN450MFL-122-E Chamaeleon 10 Sensor Emergency 11
Fire Stairs South 2 SN450MFL-122-E Chamaeleon 10 Sensor Emergency 23
Loading Dock SN450MFL-122-E Chamaeleon 10 Sensor Emergency 2
Plant Room SN450MFL-122-E Chamaeleon 10 Sensor Emergency 5
Plant Room SN450MFL-122-E Chamaeleon 10 Sensor Emergency 5
Total 1668
Community Energy Efficiency Program Final Report Illawarra Catholic Club
CEEP2181
Revision 1.0 Page 22 of 22
Club Central Menai
Location Product Code Final Solution Qty
Car Park SN450MFL-102-S Chamaeleon 10 Sensor 86
Car Park SN450MFL-102-S Chamaeleon 10 Sensor 23
Car Park SN450MFL-102-P-E Chamaeleon 10 Emergency Perm On 3
Car Park SN450MFL-102-P-E Chamaeleon 10 Emergency Perm On 20
Car Park SN450MFL-102-S Chamaeleon 10 Sensor 12
Exterior Flood Lights ZY80 80W Induction Flood Light 28
Stairs LDRA616-WW3000K 16W LED Down Light 2
Offices & BOH CIT-12-17W-FR65-R 18W LED Tube Clear 25
Offices & BOH CIT-06-08W-FR65-R 11W LED Tube Clear, 2ft 6
Offices & BOH CIT-06-08W-FR65-R 11W LED Tube Clear, 2ft 4
Offices & BOH CIT-12-17W-FR65-R 18W LED Tube Clear 1
Offices & BOH CIT-12-17W-FR65-R 18W LED Tube Clear 7
Down Lights Club 12w LED 3000K Downlight 10W LED Down Light 4" 62
Total 279