Use of Online Monitoring and Data Optimisation Drives Condition Assessment on ServiceAged Generator Step Up (GSU) Transformers Ami Singh, Ian Thompson, John Twiddle; SSE – Engineering Centre Brent DuderFindlay, Dynamic Ratings 

Upload: vuongtuong

Post on 13-Aug-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Use of Online Monitoring and Data Optimisation Drives Condition Assessment on Service‐Aged Generator Step Up (GSU) Transformers

Ami Singh, Ian Thompson, John Twiddle; SSE – Engineering Centre Brent Duder‐Findlay, Dynamic Ratings 

Page 2: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

CCGT Site – 735MW

Page 3: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

SLD – Site Commissioned in 1995 

Page 4: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

22 Year Asset(s) – 290MVA, 420/15kV 

Page 5: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Asset History 

Page 6: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Applying Loading Guide – Temperature Based Only 

Loss of Life (Days)  

HV  LV

Tx 1  1.21  2.2Tx 2    1.14  1.77Tx 3  1.32  2.92

Based on 1 Year Data       (Oct 2015‐Oct 2016)   

For Asset Life – Lost of Life 

Page 7: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Average DP From Furans 

Page 8: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

CO2/CO Ratio 

Page 9: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Acidity of Oil 

Page 10: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

O2/N2 Ratio 

Page 11: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

BDV and Moisture in Oil 

Page 12: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Installation of Additional Monitoring 

Page 13: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Equipment Details 

Processing Unit HV Bushing Monitoring PD Monitoring 

Page 14: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Equipment Details 

LV Couplers Tap Changer Monitoring Multi Gas Analyser (9 gas unit) 

Page 15: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Equipment Details 

Temperature Monitoring Additional Temperature Probes

Cooling System Monitoring

Page 16: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Equipment Details 

Calibrations Bus Voltages, Power etc. Commissioning 

Page 17: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Harvesting the

  2014 – System Commissioned 

2016 – Post Review 

Digital/per Tx  56 275Analogue/ per Tx  42 527Total   294 2406

Page 18: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Block System of Predictive Analytical Tool 

Page 19: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Traditional Monitoring vs Predictive Analytical Tool 

Page 20: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

System in Action 

Page 21: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

System in Action 

Page 22: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

High Level Interface 

Page 23: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,
Page 24: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,
Page 25: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,
Page 26: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Maintenance History – Preventative or Corrective 

1404 14171419

495 526279

0%10%20%30%40%50%60%70%80%90%

100%

CT1 CT2 ST

PM CM

Page 27: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,

Conclusions 

• The 3 GSU transformers have experienced significant ageing to date.  

• Asset owner has taken/is taking proactive steps to slow the ageing process.  

• A health index tool is providing transparency on asset integrity.