Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
1
Bus bars, bus duct, cable bus and cables
Bus bar
For very heavy currents in electrical apparatus, and for heavy currents distributed through a building, bus bars can be used. Each live conductor of such a system is a rigid piece of copper or aluminium, usually in flat bars.
In industrial applications, conductor bars are often pre-assembled with insulators in grounded enclosures. This assembly, known as bus duct or busway, can be used for connections to large switchgear or for bringing the main power feed into a building. A form of bus duct known as "plug-in bus" is used to distribute power down the length of a building; it is constructed to allow tap-off switches or motor controllers to be installed at designated places along the bus. The big advantage of this scheme is the ability to remove or add a branch circuit without removing voltage from the whole duct.
Busbars for distributing PE (ground)
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
2
Bus ducts may have all phase conductors in the same enclosure (non-isolated bus), or may have each conductor separated by a grounded barrier from the adjacent phases (segregated bus). For conducting large currents between devices, a cable bus is used.
Standard wire colours for fixed cable
European Union (EU) (IEC 60446) including UK from 31 March 2004 (BS 7671)
Table: 3-1
Phase1- Brown
Phase 2 - Black
Phase3- Gray
Neutral - Blue
Earth – Green yellow
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
3
UK prior to 31 March 2004 (BS 7671)
L1
L2
L3
Neutral wire
Earth wire
Space factor
Any cables installed into a trunking or duct should not use more than 45% of
the available space (cross-sectional area) within the trunking or duct. This is
called the space factor.
EXAMPLE 1 Calculate the amount of usable area within a trunking 50 mm by
75 mm.
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
4
Solution :
Cross-sectional area of trunking can be found 50 × 75 = 3750 mm
Space factor =
.
This is the amount of space that can be used. When calculating how many
cables can be installed in the trunking , it is important to take into account the
insulation around the cable as this counts as used space.
Table 3- 2 : Details of single core thermoplastic (pvc) cables
EXAMPLE 2 Calculate the maximum number of 10 mm2 cables that could be
installed in a 50 mm × 75 mm trunking allowing for space factor.
Find area of trunking 50 × 75 = 3750 mm2
Usable area 3750 × 45 % = 1687.50
or
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
5
From Table A, the diameter of a 10 mm
2 cable is 6.2 mm. The cross-sectional
area (csa) of one cable is
To calculate the number of cables that it would be permissible to install in the
trunking.
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
6
Electrical Power Cables Types of power cables:
Low Voltage Cables
Medium and High Voltage Cables
Control ,Signal and Instrumentation Cables
Cables are manufactured in single – core, 2-core, 3-core, 4-core and 5-
core.
1- Copper or aluminium conductor (stranded)
2- PVC insulation
3- PVC sheathed
1- Copper or aluminium conductor (stranded)
2- PVC insulation
3- Extruded jacket
4- PVC sheathed
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
7
Cables with voltage ratings more than 1000 V must be armoured
according to IEC regulation. A high voltage cable armoured with steel
wires and metal tape (double armoured) is shown in the following figure.
H.V. Armoured cable
Type of cables
The type of cable depends on its insulation type, generally, there are the
following insulations used to manufacture the cables:
PVC: Insulating compound based on polyvinyl chloride or
copolymer of vinyl chloride. الفنيل متعددبالستك كلوريد
PE: Insulating compound based on thermo plastic polyethylene. بالستك
متعدد االثلين
Butyl Rubber: Insulating compound based on ethylene propylene
rubber or similar. مطاط بيوتيل او مايشابهه
EPR: Insulating compound based on ethylene propylene rubber or
similar (EPM or EPDM). مركب اثلين بروبلين أو مايشابهه
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
8
XLPE: Insulating compound based on chemically cross-linked
polyethylene. ( التشابكي)متعدد االثلين المربوط بالتصالب
XLPO: Insulating compound based on chemically Cross-linked
polyolefin. (التشابكي)متعدد االولفين المربوط بالتصالب
Paper: Paper-insulating cable. ل بالورقالعز
Each type of cable can operate in its own temperature designed for. The
following table3 –3gives the limit or maximum operating temperature for
each type of cable.
Table : 3-3
Type of Insulation Maximum operating temperature
for the conductor in ⁰C.
PVC 07
XLPE 07
EPR and EPDM 07-07
XLPO 07
Butyl Rubber 077
Cable Rating (Current carrying
capacity)
An important part of any electrical design is the determination of the size of cables. The size of cable to be used in a given circuit is governed by the current which the circuit has to carry, so the design problem is to decide the size of cable needed to carry a known current. Tables have been prepared and published which list the maximum allowable current for each type and size of cable. The tables give a current rating for each type and size of cable for a particular method of installation and at a particular ambient temperature.
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
9
For these basic conditions a cable must be chosen the rated current of which is at least equal to the working current. For other methods of installation and ambient temperatures the tables give various correction factors. The actual working current has to be divided by these to give a nominal current and a cable then selected such that its rated current is at least equal to this nominal current.
Wiring system installation methods (According to IEC
regulation)
the determination of the type and disposition of the installation circuits. Table -3-4 gives details of commonly installed wiring systems and cable types. Having made the choice of system and cable type, the next stage is to determine the design current. Symbols The symbols used in this context are generally aligned with those used in BS
7671 together with some additional symbols which have been found necessary.
C Correction symbols used infrequently are defined where they occur in
the text.
Ca factor for ambient temperature
Cd correction factor for type of overcurrent protective device
Cd = 1 for HBC fuses and mcbs
Cd = 0.725 for semi-enclosed fuses
Cg correction factor for grouping
Ci correction factor for conductors embedded in thermal insulation
Cr correction factor for grouping of ring circuits
l circuit route length, m
Ib design current of circuit, A
IΔn rated residual operating current of an rcd, mA or A
In nominal current of protective device, A
Ief earth fault current, A
Isc short circuit current, A
It required tabulated current-carrying capacity, A
Ita actual tabulated current-carrying capacity, A
Ix current used as a basis for calculating the required current-carrying
capacity of the live conductors, A
Iz effective current-carrying capacity, A
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
10
S conductor cross-sectional area, mm
ta actual or expected ambient temperature, ⁰C
to maximum permitted conductor temperature under overload
conditions, ⁰C
Note : The IEC standard uses letter K instead of C for correction
factors.
Table : 3-4 Wiring system installation methods (IEC Standard)
رمز
Method
Description
A1
Single – core cables embedded in conduits or pipes in walls
A2
Multi – core cable embedded in conduits or pipes in walls
B1
Single-core non-sheathed cables in electrical ducts or conduits
Laying on walls or under plaster.
(including ventilated floor ducts)
B2
Laying on walls
Multicore non-sheathed cables in electrical ducts or conduits
on the wall or floor
Electrical Installation Lecture No.3 Dr.Mohammed Tawfeeq
11
C
Direct wall fixing by cleats or staples or on cable trays
D
Direct buried in the ground
E
Laying exposed in air, i.e. thermal dissipation is ensured without hindrance
where the lines are installed > 0.3 d from the wall ,d = external diameter of
the line with lines installed above one another with a vertical spacing of a
minimum of twice the line diameter
F
Laying exposed in air, i.e. thermal dissipation is ensured without hindrance
with lines installed side by side spaced at a minimum of twice
the line diameter (as E above)
G
Laying exposed in air, i.e. thermal dissipation is ensured without hindrance
with lines installed above one another with a vertical or horizental spacing
of minimum of twice the line diameter.
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
1
Current carrying capacity tables of cables and wires
according to IEC standard (Arabian Code) عازل ( 3-4) سعات نقل التيار باألمبير حسب طريقة التركيب المحددة في الجدول( 5-3)الجدول
PVC 37: ، درجة الحرارة المحيطية مئوية 07: درجة حرارة الناقل محملين( موصلين) لناقلين نحاس أو ألمنيوم
مئوية في األرض 07مئوية في الهواء ،
واط \م . كلفن 0.2ة تحت االرض بتربة ذات مقاومية حرارية نبالنسبة للكيبالت مدفو
المقطع
االسمي
للناقل مم2
(43-)طرائق التركيب في الجدول
D C B2 B1 A2 A1
1 0 3 4 2 6 0
تحت االرض نحاس
1.2 14.2 14 10.2 16.2 1..2 00
0.2 1..2 1..2 04 03 00 0.
4 06 02 30 37 36 3.
6 34 30 41 3. 46 40
17 46 43 20 20 63 63
16 61 20 06 6. .2 .1
02 .7 02 171 .7 110 174
32 .. .0 102 111 13. 102
27 11. 117 121 133 16. 14.
07 121 13. 1.0 16. 013 1.3
.2 1.0 160 030 071 02. 016
107 017 1.0 06. 030 0.. 046
127 047 01. - -344 00.
1.2 003 04. - -3.0 310
047 301 0.1 - -461 361
377 360 334 - -237 47.
ألمنيوم
0.2 12 14.2 1..2 10.2 1..2 00
4 07 1..2 02 04 02 0.
6 06 02 30 37 30 36
17 36 33 44 41 44 4.
16 4. 44 67 24 2. 60
02 63 2. 0. 01 03 .7
32 00 01 .0 .6 .7 .6
27 .3 .6 11. 174 117 113
07 11. 17. 127 131 147 147
.2 140 137 1.1 120 107 166
107 164 127 017 1.1 1.0 1..
127 1.. 100 - -000 013
1.2 012 1.2 - -02. 047
047 020 00. - -372 000
377 0.. 063 - -321 313
مم 16متوافقة مع الكيبالت ذات النواقل الدائرية حتى المقطع 0و 6و 2و 3األعمدة : مالحظة 2أما .
.المقاسات األكبر فهي للكيبالت غير الدائرية ويمكن تطبيقها على النواقل الدائرية
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
2
عزل ( 3-4) سعات نقل التيار باألمبير حسب طريقة التركيب المحددة في الجدول( 6-3)الجدول
EPR وأ XLPE نحاس أو ألمنيوم ،محملين( موصلين) لناقلين
مئوية في األرض 29مئوية في الهواء ، 39: مئوية ، درجة الحرارة المحيطية 09: درجة حرارة الناقل
واط \م . كلفن 0.2ة تحت االرض بتربة ذات مقاومية حرارية نبالنسبة للكيبالت مدفو
المقطع
االسمي
للناقل مم2
(43-)طرائق التركيب في الجدول
D C B2 B1 A2 A1
1 0 3 4 2 6 0
تحت االرض نحاس
1.2 1. 1..2 33 00 04 06
0.2 06 02 31 37 33 34
4 32 33 40 47 42 44
6 42 40 24 21 2. 26
17 61 20 02 6. .7 03
16 .1 06 177 .1 170 .2
02 176 .. 133 11. 13. 101
32 131 101 164 146 101 146
27 12. 142 1.. 102 07. 103
07 077 1.3 032 001 06. 013
.2 041 007 376 062 30. 020
107 00. 023 342 372 3.0 0.0
127 31. 0.7 - -441 304
1.2 306 30. - -276 363
047 404 3.6 - -2.. 41.
377 4.6 440 - -6.3 404
المنيوم
0.2 07 1..2 02 03 06 06
4 00 06 33 31 32 34
6 32 33 43 47 42 40
17 4. 42 2. 24 60 26
16 64 67 0. 00 .4 03
02 .4 0. 172 .4 171 .3
32 173 .6 137 112 106 110
27 102 112 120 1.3 124 130
07 12. 142 077 102 1.. 163
.2 1.1 102 040 017 041 1.3
107 007 071 0.1 040 0.7 007
127 023 037 - -304 04.
1.2 00. 060 - -301 00.
047 33. 370 - -43. 300
377 3.0 320 - -27. 364
مم 16ل الدائرية حتى المقطع متوافقة مع الكيبالت ذات النواق 0و 6و 2و 3األعمدة : مالحظة 2
ما أ.
.المقاسات األكبر فهي للكيبالت غير الدائرية ويمكن تطبيقها على النواقل الدائرية
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
3
عزل( 3-4) سعات نقل التيار باألمبير حسب طريقة التركيب المحددة في الجدول( 7-3)الجدول
PVC نحاس أو ألمنيوم ، محملة (موصالت) ثالثة نواقل
مئوية في األرض 29مئوية في الهواء ، 39: مئوية ، درجة الحرارة المحيطية 09: درجة حرارة الناقل
.
واط \م . كلفن 0.2ة تحت االرض بتربة ذات مقاومية حرارية نبالنسبة للكيبالت مدفو المقطع
االسمي
للناقل مم2
(4-3)طرائق التركيب في الجدول
D C B2 B1 A2 A1
1 2 3 4 5 6 0
تحت االرض نحاس
1.5 13.5 13 15.5 15 10.5 11
2.5 11 10.5 21 29 24 24
4 24 23 21 20 32 31
6 31 20 36 43 41 30
19 42 30 59 46 50 52
16 56 52 61 62 06 60
25 03 61 10 19 06 16
35 10 13 119 00 110 193
59 191 00 134 111 144 122
09 136 125 101 140 114 151
05 164 159 290 100 223 100
129 111 102 230 296 250 293
159 216 106 - - 300 239
115 245 223 - - 341 251
249 216 261 - - 493 200
399 321 201 - - 464 336
ألمنيوم
2.5 14 13.5 16.5 15.5 11.5 11.5
4 11.5 10.5 22 21 25 24
6 24 23 21 20 32 39
19 32 31 30 36 44 49
16 43 41 53 41 50 52
25 50 53 09 62 03 66
35 09 65 16 00 09 19
59 14 01 194 02 119 04
09 190 01 133 116 149 110
05 120 111 161 130 109 131
129 140 135 116 169 100 150
159 109 155 - - 220 101
115 104 106 - - 250 299
249 220 290 - - 395 239
399 216 230 - - 351 269
مم 16متوافقة مع الكيبالت ذات النواقل الدائرية حتى المقطع 3،5،6،0األعمدة : مالحظة 2أما المقاسات .
األكبر فهي للكيبالت غير الدائرية ويمكن تطبيقها على النواقل الدائرية
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
4
EPRأو XLPE عزل (3-4) سعات نقل التيار باألمبير حسب طريقة التركيب المحددة في الجدول( 8-3)الجدول
محملة ، نحاس أو ألمنيوم (موصالت) ،ثالثة نواقل
مئوية في درجة 07 ،مئوية في الهواء درجة37: حرارة المحيطية المئوية ، درجة درجة 7.:درجة حرارة الناقل
. األرض
واط \م . كلفن 0.2تربة ذات مقاومية حرارية ال ، ة تحت االرضنمدفوالبالنسبة للكيبالت
المقطع األساسي
للناقل مم0
4-3 ) )طرائق التركيب في الجدول
A1 A2 B1 B2 C D
تحت االرض
1 0 3 4 2 6 0
النحاس
1.5 10 16.5 29 10.5 22 22
2.5 23 22 21 26 39 20
4 31 39 30 35 49 30
6 49 31 41 44 52 46
19 54 51 66 69 01 61
16 03 61 11 19 06 00
25 05 10 110 195 110 191
35 110 190 144 121 140 122
59 141 139 105 154 100 144
09 100 164 222 104 220 101
05 216 100 260 233 201 211
129 240 220 312 261 322 249
159 215 250 - - 301 201
115 324 205 - - 424 394
249 319 346 - - 599 351
399 435 306 - - 506 306
ألمنيوم
2.5 10 11 22 21 24 22
4 25 24 20 21 32 20
6 32 31 31 35 41 36
19 44 41 52 41 50 40
16 51 55 01 64 06 61
25 06 01 03 14 09 01
35 04 10 116 193 112 04
59 113 194 149 124 136 112
09 142 131 100 156 104 131
05 101 150 210 111 211 164
129 100 119 251 216 245 116
159 226 296 - - 213 219
115 256 233 - - 323 236
249 399 203 - - 312 202
399 344 313 - - 449 391
ملم 16ذات النواقل حتى المقطع الكيبالتمتوافقة مع 3، 5،6،0 أألعمدة : مالحظة 2 أما المقاسات األكبر.
.فهي للكيبالت غير الدائرية و يمكن تطبيقها على النواقل الدائرية
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
5
في الجدول ( الكيبالت ممدودة في الهواء) Cسعات نقل التيار باألمبير لطريقة التركيب ( -03)الجدول
. فولت PVC 699/ 1999نحاسية مغلفة ب (موصالت) نواقل (4-3)
.مئوية درجة 39:مئوية ، درجة الحرارة المحيطية المرجعية درجة 09:درجة حرارة الناقل
المقطع
األساسي
للناقل مم2
(3-4)في الجدول C الطريقة -ها يبكو طريقة ترالنواقل عدد
كيبل
وحيد
الناقل
ثالثة نواقل محملة
كيبل متعدد
النواقل في
تشكيلة ثالثية أو
رباعية
كيبالت
وحيدة الناقل
في تشكيلة
ثالثية
كيبالت وحيدة الناقل
في تشكيلة
مستقيمة
1 2 3 4 5
1.5
2.5
4
6
19
16
25
35
59
09
05
129
159
115
249
399
499
599
20
35
40
50
11
190
144
106
214
209
334
310
446
516
611
010
143
004
10
25
34
43
50
00
196
120
150
100
246
215
326
304
445
511
500
660
21
21
30
41
65
16
114
130
160
290
264
390
320
301
445
521
646
040
23
31
41
52
09
02
129
140
111
221
264
393
346
302
460
569
669
009
تاألغلفة لكل دائرة مع بعضها في كلوحيدة الناقل يجب ربط ا لكيبالت: 1مالحظة
.النهايتين
. 9.0 ـبالنسبة للنواقل العارية المعرضة للمس يجب ضرب القيم ب: 2مالحظة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
6
في الجدول ( الكيبالت ممدودة في الهواء) Cسعات نقل التيار باألمبير لطريقة التركيب ( 10-3)الجدول
. فولت XLPE699/ 1999 نحاسية مغلفة ب (موصالت) نواقل (4-3)
.مئوية درجة 39:مئوية ، درجة الحرارة المحيطية المرجعية درجة 09: درجة حرارة الناقل
المقطع األساسي
مم للناقل2
(3-4)في الجدول C الطريقة -ها يبكعدد النواقل و طريقة تر
كيبل وحيد
الناقل
ثالثة نوااقل محملة
كيبل متعدد النواقل
في تشكيلة ثالثية أو
رباعية
كيبالت وحيدة الناقل
في تشكيلة ثالثية
1 2 3 4
1.5
2.5
4
6
19
16
25
35
59
09
05
129
159
115
249
399
499
599
33
43
50
02
00
131
100
210
265
336
415
415
550
646
004
091
1969
1252
24
32
42
54
04
01
133
162
100
259
391
350
412
450
564
640
061
166
26
34
44
56
00
192
131
109
290
263
325
319
430
590
694
606
111
049
وحيدة الناقل يجب ربط األغلفة لكل دائرة مع بعضها في كلتا لكيبالت: 1مالحظة
.النهايتين
. 9.0 ـبالنسبة للنواقل العارية المعرضة للمس يجب ضرب القيم ب: 2مالحظة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
0
عزل معدني( 3-4)من الجدول E، F ،Gسعات نقل التيار باألمبير لطرائق التركيب ( -113)جدول
فولت PVC 699/ 1999نحاسية مغلفة ب (موصالت) ، نواقل(مسلحة)
مئوية 397:مئوية، درجة الحرارة المحيطة المرجعية 097: درجة حرارة الناقل
المقطع
األساسي
للناقل مم2
(3-4)في الجدول E,G,F الطرق -ها يبكو طريقة ترالنواقل عدد
ناقالن محمالن
مزدوجان أو وحيد
أو E الناقل طريقة
F
اقل محملةثالثة نو
و وحيد أمتعدد
الناقل في تشكيلة
E ثالثية طريقة
Fوأ
وحيد الناقل
متالمس طريقة
F
وحيد الناقل
متباعد شاقوليا
Gطريقة
وحيد الناقل
متباعدا أفقيا
Gطريقة
1 2 3 4 5 6
1.5
2.5
4
6
19
16
25
35
59
09
05
129
159
115
249
26
36
40
69
12
190
142
104
215
264
310
364
414
402
552
22
39
49
51
60
02
129
140
112
223
260
391
352
300
466
26
34
45
50
00
192
132
161
101
241
210
331
300
426
406
21
30
40
62
14
119
142
103
213
256
390
353
499
446
400
32
43
56
01
05
125
162
100
242
204
351
492
454
590
565
.النهايتين تاألغلفة لكل دائرة مع بعضها في كلوحيدة الناقل يجب ربط ا لكيبالت :1مالحظة
. 9.0 ـبالنسبة للنواقل العارية المعرضة للمس يجب ضرب القيم ب: 2مالحظة
. كيبلالقطر الخارجي لل =dd: 3مالحظة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
1
عزل معدني( 3-4)من الجدول E، F ،Gسعات نقل التيار باألمبير لطرائق التركيب ( -123)جدول
09 :درجة حرارة الناقل ، فولت XLPE 699/ 1999 ـنحاسية مغلفة ب(موصالت)، نواقل (مسلحة)
.مئوية درجة 39:مئوية، درجة الحرارة المحيطة المرجعية درجة
المقطع
األساسي
للناقل
مم2
(3-0)في الجدول E,G,F الطرق -ها يبكعدد النواقل و طريقة تر
ناقالن محمالن
مزدوجان أو
وحيد الناقل
Fأو E طريقة
ثالثة نوااقل محملة
متعدد أو وحيد
الناقل في تشكيلة
E ثالثية طريقة
Fوأ
وحيد الناقل
متالمس طريقة
F
وحيد الناقل
متباعد
شاقوليا
Gطريقة
وحيد الناقل
متباعدا أفقيا
Gطريقة
1 2 3 4 5 6
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
33
43
57
72
99
131
177
217
265
336
415
485
557
646
774
24
32
42
53
74
98
133
162
197
250
308
359
412
475
564
32
38
51
65
90
118
160
197
238
302
373
437
500
581
697
34
44
59
74
101
132
177
215
262
325
402
470
540
626
750
40
51
68
85
115
150
200
246
298
374
460
536
610
694
792
.دائرة مع بعضها في كال النهايتين وحيدة الناقل يجب ربط األغلفة لكل لكيبالت :1مالحظة
. 9.0ـ بالنسبة للنواقل العارية المعرضة للمس يجب ضرب القيم ب: 2مالحظة
. كيبلالقطر الخارجي لل =dd: 3مالحظة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
0
يطبق . قلاكيبل مفردالن أكثر من دارة أو على جل المجموعات التي تحتويأعوامل تخفيض من ( 13-3)الجدول
. (12-3)إلى ( 5-3)على سعات نقل التيار للجداول من هذا الجدول
الترتيب
كيبالت)
(متالمسة
يستعمل 07 16 10 . . 0 2 4 0 1
مع سعة
نقل التيار
المرجعية
محزوم على 1
السطح أو
ضمن
مجرى أو
قناة
أو مدفون
في الجدران
1.7 7.. 7.62 7.67 7.24 7.20 7.27 7.42 7.41 7.3.
(3-5 )
إلى
(3-12 )
Aللطرق
Fحتى
طبقة واحدة 0
على الجدار،
األرضية أو
على حامل
( صينية)
غير مثقب
1.7 7..2 7.02 7.03 7.00 7.01 7.07
عامل ال ضرورة الستخدام
تخفيض ألكثر من تسعة دارات
أو كابالت متعددة النواقل
(3-9 )
حتى
(3-10 )
للطريقة
C
طبقة واحدة 3
مثبتة
مباشرة
فوق سقف
خشبي
7..2 7..1 7.6. 7.66 7.63 7.60 7.61
(3-11 )
حتى
(3-12 )
للطرق
EوF
طبقة واحدة 4
على حامل
مثقب أفقي
أو شاقولي
1.77 7... 7.00 7.02 7.03 7.00 7.00
طبقة واحدة 2
على سلم أو
دعائم
وغيرها
1.77 7..0 7..7 7..7 7.0. 7.0. 7.0.
عندما .تعتبر التمديدات متجاورة إذا كان التباعد بين الكيبلين أقل من ضعف قطر الكيبل األكبر: ة مالحظ
:التالية العوامليضرب ب ه يجب أنيتم مد الكيبالت على أكثر من طبقة فإن عامل التصحيح أعال
0.70: أربع أو خمس طبقات 0.73: ثالث طبقات 0.8: طبقتان
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
19
ممدودة في الهواء( مفردة)ة الناقل لمجموعات لكيبالت وحيدا ألجل عوامل التخفيض( 14-3)الجدول
.ABBشركة نشرات منظومات ثالثية الطور حسبلل ومتباعدة
1 2 3 4 5
في االتجاه الدارات عدد عدد الرفوف التركيب بشكل مستوي
االفقي باالتجاه بتباعد يساوي قطر الكيبل
3 2 1الشاقولي ( d) نفسه تقريبا
0.88 0.89 0.92 1 كيبالت ممدودة
على االرضية
0.88 0.89 0.92 1 حامالت كيبل
83 .0 0.84 0.87 2 غير مثقبة
3 0.84 0.82 0.81
6 0.82 0.80 0.79
0.90 0.93 1.00 1 حامالت كيبل مثقبة
2 0.97 0.89 0. 85
3 0.96 0.88 0.82
6 0.94 0.85 0.80
0.96 0.97 1.00 1 مساند كيبالت
Cable Racks 2 0.97 0.94 0.93
3 0.96 0.93 0.92
6 0.94 0.91 0.90
على مساند كيبالت
1 0.94 0.91 0.89
أو على الجدار
0.86 0.90 0.94 2 أو على حامالت كيبل
شاقوليا مثقبة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
11
ممدودة في الهواء ( مفردة)ة الناقل لمجموعات لكيبالت وحيدا ألجل التخفيض عوامل (15-3)الجدول
.ABBشركة نشرات في المنظومات ثالثية الطور حسب ( Trefoil)على شكل مجاميع ثالثية
1 2 3 4 5
في االتجاه الدارات التركيب بشكل مثلثي عدد الرفوف عدد
االفقي بتباعد يساوي قطر الكيبل باالتجاه
3 2 1الشاقولي ( d) نفسه تقريبا
0.94 0.96 0.98 1كيبالت ممدودة
على االرضية
0.94 0.96 0.98 1 حامالت كيبل
0.87 0.91 0.95 2 غير مثقبة
3 0.94 0.90 0.85
6 0.93 0.88 0.82
0.96 0.98 1.00 1 حامالت كيبل مثقبة
2 0.97 0.93 0. 89
3 0.96 0.92 0.85
6 0.94 0.90 0.83
0.96 0.97 1.00 1 مساند كيبالت
Cable Racks 2 0.97 0.95 0.93
3 0.96 0.94 0.90
6 0.95 0.93 0.87
على مساند كيبالت
1 1.00 0.91 0.89
أو على الجدار
0.86 0.90 1.00 2 أو على حامالت كيبل
شاقوليا مثقبة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
12
متباعدة -لمجموعات لكيبالت ثالثية الطور ممدودة في الهواءا ألجل عوامل التخفيض( 16-3)الجدول
. ABBشركة نشرات حسب
1 2 3 4 5 6 7
عدد الرفوف عدد الكيبالت في االتجاه التركيب
بتباعد يساوي قطر الكيبل باالتجاه االفقي
6 4 3 2 1الشاقولي ( d) نفسه تقريبا
0.71 0.75 0.78 0.85 0.97 1كيبالت ممدودة
على االرضية
0.90 0.93 0.94 0.96 0.97 1 حامالت
0.86 0.90 92 .0 0.95 0.97 2 كيبل غير
0.84 0.89 0.91 0.94 0.97 3 مثقبة
6 0.97 0.93 0.90 0.88 0.83
حامالت كيبل مثقبة
1 1.00 1.00 0.98 0.95 0.91
2 1.00 0.99 0.96 0.92 0.87
3 1.00 0.98 0.95 0.91 0.85
6 1.00 0.97 0.94 0.90 0.84
1.00 1.00 1.00 1.00 1.00 1 مساند كيبالت
Cable Racks 2 1.00 0.99 0.98 0.97 0.96
3 1.00 0.98 0.97 0.96 0.93
6 1.00 0.97 0.96 0.94 0.91
على مساند كيبالت
1 1.00 0.91 0.89 0.88 0.87
أو على الجدار
0.85 0.87 0.88 0.91 1.00 2 أو على حامالت كيبل
شاقوليا مثقبة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
13
متجاورة - لكيبالت ثالثية الطور ممدودة في الهواءلمجموعات ا ألجل عوامل التخفيض( 10-3)الجدول
. ABBشركة نشرات حسب
1 2 3 4 5 6 7 8
عدد الكيبالت في االتجاه عدد الرفوف التركيب
االفقي باالتجاه متجاورة ومتالصقة
9 6 4 3 2 1الشاقولي
0.68 0.90 0.93 0.94 0.96 0.97 1كيبالت ممدودة
على االرضية
0.68 0.71 0.75 0.78 0.85 0.97 1 حامالت
0.63 0.68 0.73 0.76 0.84 0.97 2 كيبل غير
0.63 0.66 0.72 0.75 0.83 0.97 3 مثقبة
6 0.97 0.81 0.73 0.69 0.63 0.58
حامالت كيبل مثقبة
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
6 1.00 0.84 0.77 0.73 0.68 0.64
مساند كيبالت
Cable Racks 1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
3 1.00 0.85 0.79 0.76 0.73 0.70
6 1.00 0.83 0.76 0.73 0.69 0.66
على مساند
0.72 0.73 80.7 0.82 0.88 1.00 1 كيبالت
أو على الجدار
0.70 0.71 0.76 0.81 0.88 1.00 2 ل أو على حامالت كيب
شاقوليا مثقبة
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
14
39عوامل التصحيح من أجل درجات حرارة الهواء المحيط المختلفة عن ( 11-3)الجدول °تطبق مئوية
.على سعات نقل التيار للكيبالت في الهواء
درجة حرارة
المحيط مئوية
زلـــــــــــــــــــــالع
PVC EPR أو XLPE
*معدني
أو عاري معرض للمس PVC ـمغطى ب
377
مئوية
19 1.22 1.15 1.26
15 1.10 1.12 1.29
29 1.12 1.91 1.14
25 1.96 1.94 1.90
35 9.04 9.06 9.03
49 9.10 9.01 9.15
45 9.00 9.10 9.00
59 9.01 9.12 9.60
55 9.61 9.06 9.50
69 9.59 9.01 9.45
65 - 9.65 -
09 - 9.51 -
05 - 9.59 -
19 - 9.41 -
15 - - -
09 - - -
05 - - -
ةالصانع الشركة بالنسبة لدرجات حرارة الجو األعلى من ذلك يجب استشارة*
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
15
أوالموضوعة Direct in ground تحت األرضعامل عمق الدفن للكيبالت المطمورة ( 10 -3)الجدول
. Direct in ductsمباشرة في خنادق
وفقا للتباعد Direct in ground عامل المجموعات للكيبالت المطمورة تحت األرض (29-3)الجدول
Spacing بالمتر.
موضوعة بشكل أفقي ضمن منظومات ثالثية الطور( مفردة)كيبالت وحيدة الناقل
تباعد الدارات بالمتر عدد الدارات التباعد
0.6 0.45 0.30 0.15
0.89 0.87 0.84 0.80 2
----------------------------------------------------------------------------------------------------
0.82 0.79 0.75 0.69 3
0.79 0.75 0.70 0.63 4
0.76 0.72 0.66 0.59 5
0.74 0.70 0.64 0.56 6
0.73 0.68 0.62 0.53 7
0.72 0.67 0.60 0.52 8
0.71 0.66 0.59 0.50 9
0.71 0.65 0.58 0.49 10
0.70 0.65 0.57 0.48 11
0.70 0.64 0.57 0.47 12
كيبالت ممدودة مباشرة في األرض كيبالت ممدودة داخل خنادق
عامل التقنين لحد (متر)عمق الدفن
ملم 3770
ألعلى التقنينعامل
ملم 377من 0
عامل التقنين
( ناقل واحد )
عامل التقنين
( ثالثة نواقل)
0.80 1.0 1.0 1.0 1.0
1.0 0.98 0.97 0.98 0.99
1.25 0.96 0.95 0.95 0.97
1.50 0.95 0.93 0.94 0.96
1.75 0.94 0.91 0.92 0.96
2 0.92 0.89 0.91 0.95
2.5 0.91 088 0.89 0.94
3 0.90 0.86 0.88 0.93
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
16
للتباعد وفقا Direct in ground عامل المجموعات للكيبالت المطمورة تحت األرض (21-3)الجدول
Spacing بالمتر
(مفردة)كيبالت وحيدة الناقل
Trefoilموضوعة بشكل مثلثي
أو بشكل أفقي متالسقة ثالثية الطور
التباعد التباعد
متر -تباعد الدارات
0.15 0.30 0.45 0.60( Laid flatمد أفقي ) 0( Trefoilمثلثي ) 0
0.91 0.89 0.86 0.82 0.80 0.78
0.83 0.80 0.77 0.71 0.68 0.66
0.80 0.77 0.78 0.65 0.62 0.59
078 0.74 0.68 0.61 0.58 0.55
0.76 0.72 0.66 0.58 0.55 0.52
0.75 0.70 0.64 0.56 0.52 0.49
0.74 0.69 0.63 0.54 0.50 0.47
0.74 0.68 0.61 0.52 0.48 0.45
0.73 0.68 0.61 0.51 0.47 0.44
0.73 0.67 0.0.6 0.50 0.46 0.43
0.72 0.67 0.59 0.49 0.45 0.41
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
10
.عامل المجموعات للكيبالت المطمورة تحت األرض وفقا لمسافة تباعدها بالمتر( 22-3)الجدول
األرض بصورة أفقية ممدودة مباشرة تحت Three Core Cablesكيبالت ثالثية الناقل
عدالتبا
عدد الكيبالت
في المجموعة مسافة التباعد بالمتر
0.6 0.45 0.30 0.15 0.00
0.93 0.91 0.89 0.85 0.80 2
0.87 0.84 0.81 0.76 0.68 3
0.84 0.81 0.77 0.71 0.62 4
0.82 0.78 0.73 0.66 0.57 5
0.81 0.77 0.71 0.64 0.54 6
0.79 0.75 0.69 0.61 0.51 7
0.79 0.74 0.68 0.59 0.49 8
078 0.73 0.67 0.58 0.47 9
0.78 0.73 0.66 0.57 0.45 10
0.77 0.72 0.65 0.55 0.44 11
0.77 0.77 0.64 0.54 0.43 12
Electrical Installation Lecture No.3(continued) Dr.Mohammed Tawfeeq Al-Zuhairi
11
Electrical properties for cables Table: 3-23
Electrical properties for cablesالخواص الكهربائية للكيبالت
بالملمتر قياس الكيبل
المربع
هبوط الفولتية كيلومتر /الممانعة أوم
متر/ أمبير / ملي فولت
أعلى تيار قصر دورة
Isc (kA) متماثل
Cable size (mm2) Impedance
( Ω/km)
Volt drop
(mV/A/m)
Short circuit
rating (kA)Isc
1.5 14.48 25.080 0.17
2.5 8.87 15.363 0.28
4 5.52 9.561 0.46
6 3.69 6.391 0.69
10 2.19 3.793 1.15
16 1.38 2.390 1.84
25 0.8749 1.515 2.87
35 0.6335 1.097 4.02
50 0.4718 0.817 5.75
70 0.3325 0.576 8.05
95 0.2460 0.427 10.92
120 0.2012 0.348 13.80
150 0.1698 0.294 17.25
185 0.1445 0.250 21.60
240 0.1220 0.211 27.60
300 0.1090 0.140 34.50
ذ.مئوية 39محسوبا لدرجة حرارة PVCوضع هذا الجدول للكيبالت النحاسية بعزل : مالحظة