Page 1: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

BimetalThermometers• 5 Year Limited Warranty• Gold Service Available

3505 Cadillac Ave - Bldg, E - Costa Mesa, CA. - 92626 - USA. Ph (714) 751 - 7512 Fax (714) 751 - 0213

www.flw.com

Page 2: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

WARNING:All bimetal thermometers shouldbe selected considering themedia and the ambient operatingconditions. Improper applicationcan be detrimental to the ther-mometer, cause failure and pos-sibly personal injury or propertydamage. Inaccuracies resultingfrom improper setting of theexternal adjustment by the usermay cause personal injury orproperty damage. Consult ASMEB40.3 for guidance in selectionand use of bimetal thermometers.

TEMPERATURE RANGESStandard Fahrenheit and Celsius ranges havebeen established to encompass all normaltemperature measurement requirements. Abimetal thermometer can be used at an oper-ating temperature anywhere throughout its dialrange. Provision should be made for extremetemperature conditions. No bimetal thermome-ter should be exposed continuously to processtemperatures over 800°F (425°C).

OPERATING CONDITIONSThe temperature of the case should be nomore than 200°F (95°C); liquid filled 150°F(65°C). Temperatures beyond this value maycause discoloration of the dial or result inincreased pressure inside the casing whichcould ultimately lead to the failure of thewindow.

THERMOWELLSThermowells must be used on any applicationwhere the stem of the bimetal thermometermay be exposed to pressure, corrosive fluidsor high velocity. Additionally, the use of a ther-mowell permits instrument interchange or cali-bration check without disturbing or closingdown the process.

POINTERSThe pointers are balanced to close tolerancesand the paint finishes are controlled to assurelong-term stability under adverse ultravioletconditions.

CASESThere are three case styles. The CI series hasno adjustment but is hermetically sealed. TheEI series has an external adjustment and ishermetically sealed. The EL series providesthe same features as the EI plus the addedbenefit of liquid filling. The instruments areleak tested to ensure the integrity of the joints.

COILSThe bimetallic coils are carefully wound andinspected. Each is heat treated for optimumstability and overtemperature capability.

BEARINGSThe bearings are made of Teflon or other lowfriction material.

SHAFTSShafts are made of specially drawn stainlesssteel wire with a very smooth finish.

DIALSThe dials are based on computer-calculatedtemperature deflection data and have theMaxivision® format to minimize parallax error.

WINDOWSThe standard windows are heavy-duty glass.Plastic and shatterproof glass are optional.

Product Selection Information

ProcessConnection

ExternalAdjustment

Stem

CoilShaft

CaseBushing

Bearing

Inner Dial

Dial Ring RingPointer

Window

ScrewsGearPinion

Gasket

Page 3: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

EI Case StyleThis series has a hermetically sealed

case and external adjustment.Connection locations are rear,

lower and Everyangle. Thehermetic seal prevents

entry of moisture intothe casing, minimizingthe possibility of icing

or fogging insidethe case.

CI Case StyleThis style is tam-per resistant and

hermetically sealed.Connection loca-

tions are rear andlower. The CI Series

was designed for applica-tions where external

adjustment or pointer reset are not desired. Hermetic sealing

reduces the problems created by moisture entering the case.

EL Case StyleThis series is liquid filled –

prolonging instrument life. Potential wear problems caused by excessive

vibration are minimized through dampening, and the liquid medium

improves readability. External adjustment is standard in the

rear of the case.

Everyangle CaseConnection

This design providesmaximum utility. The

entire dial face can berotated 360 degrees,

and angled 180degrees by position-

ing the harness on the back of the case.

The instrument can be installed almost anywhere and can be adjusted so that

the dial can be easily read.

Introduction

The complete line of Ashcroft industri-al bimetal thermometers and acces-sories provides quality choices for yourtemperature applications. There is along history of superior quality inengineering, manufacturingand customer service of theseproducts. Each Ashcroftindustrial bimetal thermome-ter is backed by a limitedfive year warranty.

Each instrument is man-ufactured to a standardaccuracy of 1% of span(ASME B40.3, Grade A)traceable to the NationalInstitute of Standards andTechnology (NIST). The bimetalcoils are heat treated for stability andovertemperature capability. A singlehelix is used to reduce lag time. Thebearings are made of a low-friction long-life material. The shafts are made of spe-cially drawn stainless steel with a verysmooth finish. All joints are welded, andthe weld between the stem and the out-let is located at the bottom of the threadsto eliminate the possibility of crevice corrosion.

Silicone dampening is included forimproved vibration resistance. TheAshcroft Maxivision® dial eliminatesparallax error by placing thepointer in the same plane asthe graduations. The dialcan be rotated 360degrees and can beangled 180 degrees withthe Everyangle™

connection.

To meet your emer-gency delivery require-ments, Dresser InstrumentDivision offers the GoldServicesm delivery program.Ashcroft industrial bimetal thermometers can be shipped in 2 to 5 working days fromour Stratford, Connecticut,USA, manufacturing plant. We also have an extensive stocking distributornetwork throughout the United Statesand international locations.

Everyangle™ EL

CI EI

Page 4: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

How to Order

To specify the exact thermometer desired, select entriesfrom appropriate charts as shown in the example below.

30 EI 60 R 040 XNH 0/200°F1 2 3 4 5 6 7

1 CASE SIZE 2 STYLE 3 CONNECTION 4 CONN. LOCATION 5 STEM LENGTH

Dia. Code Code Conn. Code Location Code “S” Length Code

Plain 40

2˝ 20 CI Pointed 50 Rear REI Plain1⁄4 NPT 60

CIEI 1⁄2 NPT 60 Rear REL

3˝ 30 CIEI

1⁄2 NPT 60 Lower L

1⁄2 NPT 601⁄2 NPT 42

Everyangle EEI UnionCIEI 1⁄2 NPT 60 Rear REL

5˝ 50 CIEI

1⁄2 NPT 60 Lower L

1⁄2 NPT 60EI 1⁄2 NPT 42

Everyangle EEL Union

7A EI & CI SERIES TEMPERATURE RANGES, SINGLE SCALE

Figure Figure°F °/Div. Interval °C °/Div. Interval

–80/120 2 20 –50/50 1 10–20/1201 2 20 –20/120 2 2030/1301 1 10 0/501 1 50/200 2 20 0/100 1 100/250 2 50 10/150 2 20

50/300 2 50 0/200 2 2050/400 5 50 0/300 5 5050/550 5 50 50/4502,3 5 50

200/7002 5 50 100/5002,3 5 50100/8002 10 100200/10002,3 10 100

6 OPTIONS

Code Description

XCS Dual scale4

XDM Service markingprinted on dial

XNH Stainless steel tagXNN Paper tagXPD Plastic windowXSG Shatterproof glassX3B 3⁄8˝ stem diameter

with 1⁄2 NPT conn.

21⁄2˝ 025

4˝ 040

6˝ 060

9˝ 090

12˝ 120

15˝ 150

18˝ 180

24˝ 240

7B EL SERIES TEMPERATURE RANGES, SINGLE SCALE

Figure Figure°F °/Div. Interval °C °/Div. Interval

–40/160 2 20 –20/120 2 20–20/1201 2 20 –10/110 2 1030/1301 1 10 0/501 1 50/200 2 20 0/100 1 100/250 2 50 10/150 2 20

50/300 2 50 0/300 5 5050/550 5 50

NOTES1 Minimum stem length for lower connection and Everyangle is 4.̋2 Minimum stem length for these ranges is 4.̋3 Satisfactory for continuous service up to 800°F or 425°C. Can be

used for intermittent service from 800° to 1000°F, or 425° to 500°C.4 Dual scale ranges are available on 3˝ and 5˝ case only.

See table 7C.

Page 5: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

Case Styles and Features

7C DUAL SCALES(XCS) are available in 3˝ and 5˝ dial sizes in the following ranges

(where applicable):

Inner °F Outer °F

–80/120 –60/50–40/120 –40/50–40/160 –40/70–20/1201 –30/501

0/200 –20/900/250 –20/120

30/1301 0/551

50/300 10/15050/400 10/20050/550 10/290

100/800 50/400200/7002 100/3702

200/10002,3 100/5502,3

EI & CI SERIESOVERTEMPERATURE LIMITS

Top of Maximum ProcessRange °F Overtemperature

Up to 250 100% of Span250/550 50% of Span550/1000 800°F3

EL SERIESOVERTEMPERATURE LIMITS

Top of Maximum ProcessRange °F Overtemperature

Up to 160 100% of Span160/300°F 300°F300/550°F 550°F

• Maximum ambient temperature forEI and CI Series is 200°F or 95°C.

• Maximum ambient temperature forEL Series is 150°F or 65°C.

• Use Ashcroft Duratemp® thermome-ter for ranges above and belowthose listed in the range charts.

EI Standard Specifications

• Hermetic seal

• External adjustment

• Maxivision dial

• 1% full-span accuracy

• All-welded stainless steel construction

• Silicone on the coil provides vibrationdampening and superior response time

• Heavy-duty glass is standard; plastic orshatterproof glass is optional

CI Standard Specifications

• Hermetic seal

• Tamper resistant, no adjustment

• Maxivision dial

• 1% full-span accuracy

• All-welded stainless steel construction

• Silicone on the coil provides vibrationdampening and superior response time

• Heavy-duty glass is standard; plastic orshatterproof glass is optional

EL Standard Specifications

• Silicone liquid filled

• External adjustment

• Durable polycarbonate window

• Maxivision dial

• 1% full-span accuracy

• All-welded stainless steel construction

Everyangle – Case Connection

The Ashcroft Everyangle industrial bimetalthermometer dial face with Maxivision dialcan be rotated 360 degrees and angled 180degrees. It is available in the EI and EL (5˝only) series with either a threaded orcompression type union connection.

This design provides maximum utility. Sincethe entire case can be rotated and angled,the instrument can be installed almost any-where and adjusted so that the dial face canbe easily read.

Page 6: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

Case Dimensions

Weight in ounces3

S – 21⁄2˝Case Series

Case Dial ConnectionSeries Size Location

A B C D E G H S NPT Hex CI EI EL

CI, EI 2˝ Rear 23⁄32 3⁄8 5⁄16 – – – – –2 – 11⁄16 41⁄2 41⁄2 –(Plain) (53) (10) (8)

CI, EI 2˝ Rear (Plain, 23⁄32 3⁄8 5⁄16 – – – – –2 – 11⁄16 41⁄2 41⁄2 –pointed stem) (53) (10) (8)

CI, EI 2˝ Rear 23⁄32 3⁄8 5⁄16 – – – – –2 1⁄4 11⁄16 41⁄2 41⁄2 –(Threaded) (53) (10) (8)

CI, EI, EL 3˝ Rear 35⁄32 19⁄32 5⁄16 – – – – –2 1⁄2 7⁄8 7 7 8(80) (15) (8)

CI, EI 3˝ Lower 35⁄32 127⁄32 – 25⁄8 1⁄4 – – –2 1⁄2 7⁄8 11 11 –(80) (47) (67) (6)

EI 3˝ Everyangle 35⁄32 19⁄32 – – – 121⁄32 37⁄16 –2 1⁄2 7⁄8 – 10 –(80) (15) (42) (87)

CI, EI, EL 5˝ Rear 51⁄32 23⁄32 5⁄16 – – – – –2 1⁄2 7⁄8 15 16 18(128) (18) (8)

CI, EI 5˝ Lower 51⁄32 115⁄16 – 35⁄8 1⁄4 – – –2 1⁄2 7⁄8 24 26 –(128) (49) (92) (6)

EI, EL 5˝ Everyangle 51⁄16 23⁄32 – – – 17⁄8 39⁄16 –2 1⁄2 7⁄8 – 25 28(128) (18) (48) (91)

NOTES1 Figures in parenthesis ( ) are in millimeters. All other dimensions are in inches.2 Standard “S” dimensions are 21⁄2, 4, 6, 9, 12, 15, 18 and 24 inches.

Standard stem diameter is 1⁄4 inch.3 Add 1 oz. for every 2 inches of stem length.

S

CB

A

20CI60R20EI60R

S

CB

A

20CI40R20EI40R

S

CB

A

20CI50R20EI50R

S

CB

A

30CI60R30EI60R30EL60R

S

A

C

B

50CI60R50EI60R50EL60R

G

B

H

S

A

30EI60E50EI60E50EL60E

G B

H

S

A

1.00"30EI42E50EI42E50EL42E

A

B

D

E

S

30CI60L30EI60L

B

D

A

E

S

50CI60L50EI60L

Page 7: Bimetal Thermometers - ashcroft-usa. · PDF fileal bimetal thermometers and acces- ... helix is used to reduce lag time. The bearings are made of a low-friction long- ... 18˝ 180

Thermowells

Thermowells must be used whenever anAshcroft bimetal thermometer is installed ona pressurized application or where pressure,high velocity or corrosive media are present. STANDARD CONFIGURATION LAGGING EXTENSION

Type: Uniform (straight) shank, threadedBore Size: 0.385Process Connection: 3⁄4, 1 NPTMaterials: Brass, carbon steel

304 stainless steel316 stainless steel

Type: Stepped shank, threadedBore Size: 0.260Process Connection: 1⁄2, 3⁄4, 1 NPTMaterials: Brass, carbon steel

304 stainless steel316 stainless steel

Type: Tapered shank, threadedBore Size: 0.260, 0.385Process Connection: 1⁄2, 3⁄4, 1 NPTMaterials: Brass, carbon steel

304 stainless steel316 stainless steel

Type: Tapered shank, socket weldBore Size: 0.260, 0.385Process Connection: 3⁄4,̋ 1˝ pipeMaterials: Carbon steel

304 stainless steel316 stainless steel

Type: Tapered shank, Van StoneBore Size: 0.260, 0.385Process Connection: 1,̋ 11⁄2˝ pipeMaterials: 304 stainless steel

316 stainless steel

Type: Tapered shank, weld-inBore Size: 0.260, 0.385Process Connection: 11⁄2˝ diameterMaterials: 304 stainless steel

316 stainless steel

Type: Tapered shank, flangedBore Size: 0.260, 0.385Process Connection: 1,̋ 11⁄2,̋ 2˝ pipeMaterials: 304 stainless steel

316 stainless steel