J J J S3 S3 1,3(EDP) RELOCATED GENERATOR CT RELOCATED ATS GENERATOR OUTPUT FEEDER UTILITY TRANSFORMER UTILITY SECONDARY DUCTBANK. SEE RISER DIAGRAM S3 INSTALL POLE BASE IMMEDIATELY BEHIND CURB INSTALL POLE BASE IMMEDIATELY BEHIND CURB 3(P2R) 1(P2R) 11(P2R) PROVIDE BOLLARDS PER UTILITY STANDARDS S3 WIRE SIZE PER PANEL SCHEDULE 2#10, 1#10G, 1"C. GE WPG WPG WPG WPG 83(E2L) SIGN E10 2#10, 1#10G, 1"C. 2#10, 1#10G, 1"C. 2#10, 1#10G, 1"C. FUTURE SITE EQUIPMENT These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings. Client: Location: Project: Drawn by: Project No: Date: Professional Certification I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland. License No. 45534 Expiration Date 06-03-20 ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401 Maryland: MD Fax: (301) 261-8228 (410) 224-4443 Baltimore: (410) 841-6595 Annapolis: (410) 224-2727 Website www.bigwaha.com ARCHITECT CONTACT: GREG GILBERT, RA MICHAEL MATULA STRUCTURAL ENGINEER CENTURY ENGINEERING 10710 GILROY ROAD HUNT VALLEY, MD 21031 TEL: (443) 589 - 2400 CONTACT: RICHARD BEARD MECHANICAL, ELECTRICAL & PLUMBING ENGINEER CENTURY ENGINEERING 10710 GILROY ROAD HUNT VALLEY, MD 21031 TEL: (443) 589 - 2400 CONTACT: ANDREW JUN - MECHANICAL/PLUMBING MATT STEINER - ELECTRICAL BAY ENGINEERING INC. 2661 RIVA ROAD ANNAPOLIS, MD 21401 TEL: (410) 897 - 9290 CONTACT: NELSON AROCHO ANNIE LUTTRELL CIVIL ENGINEER CALVERT COUNTRY - GENERAL SERVICES DIVISION 450 SOLOMONS ISLAND ROAD PRINCE FREDERICK, MD 20678 PRINCE FREDERICK VOLUNTEER FIRE STATION E0.1 ELECTRICAL SITE PLAN 17032 1/25/19 BID / CONSTRUCTION SP 1/16" = 1'-0" 1 ELECTRICAL SITE PLAN 0 32 48 64 16 GRAPHIC SCALE : 1/16"=1'-0" PLAN NORTH TRUE NORTH Revision Schedule # Date Revision ELECTRICAL SPECIFIC NOTE LEGEND SPECIFIC NOTE VALUE SPECIFIC NOTE TEXT E10 PROVIDE 1" CONDUIT STUBBED UP AT FUTURE FLAGPOLE LOCATION. COORDINATE LOCATION WITH OWNER.

Upload: others

Post on 31-Jan-2020

27 views

Category:

Documents


0 download

TRANSCRIPT

  • J

    J

    J

    S3

    S3

    1,3(EDP)

    RELOCATED GENERATOR

    CT

    RELOCATED ATS

    GENERATOR OUTPUT FEEDER

    UTILITY TRANSFORMER

    UTILITY SECONDARY DUCTBANK. SEE RISER DIAGRAM

    S3

    INSTALL POLE BASE IMMEDIATELY BEHIND CURB

    INSTALL POLE BASE IMMEDIATELY BEHIND CURB

    3(P2R)

    1(P2R)

    11(P2R)

    PROVIDE BOLLARDS PER UTILITY STANDARDS

    S3

    WIRE SIZE PER PANEL SCHEDULE

    2#10, 1#10G, 1"C.

    GE

    WPG

    WPG

    WPG

    WPG

    83(E2L)

    SIGN

    E10

    2#10, 1#10G, 1"C.

    2#10, 1#10G, 1"C.

    2#10, 1#10G, 1"C.

    FUTURE SITE EQUIPMENT

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E0.1

    ELECTRICAL SITEPLAN

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    1/16" = 1'-0"1

    ELECTRICAL SITE PLAN

    0 32 48 6416

    GRAPHIC SCALE : 1/16"=1'-0"

    PLANNORTH

    TRUENORTH

    Revision Schedule

    # Date Revision

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E10 PROVIDE 1" CONDUIT STUBBED UP AT FUTURE FLAGPOLE LOCATION.COORDINATE LOCATION WITH OWNER.

  • DW

    ICE

    W

    DW D

    W

    D

    CS1CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    DL

    CS1

    DL

    CS1

    DL

    CS1

    DL

    CS1 CS1

    CS1 DLCS1

    CS1

    CS1

    CS1

    DIRTY SHOP

    125

    UTILITY ROOM

    124

    WOMEN

    STORAGE

    130

    MEN

    STAIR 1

    S11

    APPARATUSBAYS

    123

    OFFICE

    110

    CONF.

    115

    OFFICE

    109

    OFFICE

    107

    OFFICE

    106

    ELEV

    DAYROOM/LOUNGE / DINING

    117

    FITNESS

    116

    MUSEUM

    102

    CUST

    114

    OFFICE

    104

    OFFICE

    108

    OFFICE

    103

    WATCH DESK

    118

    MAIN LOBBY

    101

    STAIR 2

    S21

    SCBA

    126

    PANTRY

    120

    CORR

    C14

    COMM/ DATA

    111

    CORR

    C11

    POLE 2

    P21

    WASH BAY

    132

    TABLE / CHAIRSTORAGE

    127LAUNDRY

    128

    PPE GEAR

    131

    X

    X

    X2

    X

    X2

    XX

    X

    X2

    X2X2

    X2X2

    X2

    L2 L2

    L2 L2

    L2E

    L2 L2

    L2E

    L2E

    L2E

    L2

    L2

    L9 L9 L2

    L2 L2E L2

    NL

    NL

    NL

    NL

    L9 L9

    L9 L9

    L9 L9

    L9 L9

    L9 L9

    L9 L9

    L9L9

    L9 L9

    L2

    L2

    L8

    L8

    L8

    L8

    L8

    L8

    L8 L8 L8

    L12

    L13L13L12

    L12AL12A

    L12A L12A

    L13L13

    L12

    L3

    L4L3

    L3

    APPARATUS BAY LIGHTING SWITCHES (QTY. PER SEQUENCE OF OPS)

    APPARATUS BAY LIGHTING SWITCHES(QTY. PER SEQUENCE OF OPS)

    L17

    L12

    L12

    L12E

    L12

    L17

    L11

    L11

    L11

    L11

    L11

    L4

    L4

    L4

    L7 L7

    L6

    L6

    L6L6 L6

    L6

    L6

    EM2

    EM2

    EM2

    EM2

    EM2

    EM2

    EM2 EM2

    EM2 EM2

    EM2

    EM2

    L12AL12A

    L12E

    L12A

    EM

    3(E2LL)

    1(E2LL)

    42(E2R)

    UP

    UP

    L2

    EM

    L15

    L15 L15 L15 L15

    L15 L15 L15L15

    a

    a

    a

    a

    a

    b

    b

    b

    b

    b

    b

    b

    NL NL

    UP

    13(E2LL)

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1L1

    L1

    L1

    L1E

    L1

    L1 L1 L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1E

    2(E2LL)

    5(E2LL)

    4(E2LL)

    L1EL1L1

    L1

    L1

    L1L1

    L1E

    6(E2LL)

    L12 L12

    L12

    7(E2LL)

    L5L5 L5 L5

    L5

    L1 L1

    L1E

    L1

    L1 L1

    NL

    L1 L1

    9(E2LL)

    NL

    X

    X

    L12

    L12

    L12

    X

    L2E

    X

    L12

    L12A L12A L12A

    L12

    L12E

    X

    EMB

    EMB

    EMB

    L15

    L15

    L12 L12

    L12L12

    L12L12

    L12E

    L13A L13A

    L13A

    L15L15

    TOILET

    129

    CORR

    C13

    CORR

    C12

    TOILET (VOL)

    112

    TOILET(OFFICER)

    113

    VOL KITCHEN

    119A

    EVENT KITCHEN

    119B

    E3

    E3

    NL

    EM

    EM

    NL

    EM

    NL

    NL

    NL

    L2 L2E

    NL

    EM

    NL

    EM

    EM

    X

    X

    X

    X X

    39(E2R)

    L14L14L14L14L14

    L14L14L14L14L14

    L15

    L15L15

    26(E2LL)

    L10

    L10

    L15

    MDP EDP

    FOR LIGHTING IN PIT AND TOP OF SHAFT SEE DETAIL

    38(E2R)37(E2R)

    XR

    EM2

    XR

    XR

    XR XR

    XR

    XRXRXR

    EM2

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E1.1

    FIRST FLOOR PLAN -LIGHTING

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    1/8" = 1'-0"1

    FIRST FLOOR PLAN - LIGHTING

    PLANNORTH

    TRUENORTH

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E3 ACTUATION OF OCCUPANCY SENSOR AT EITHERLEVEL SHALL TURN ON LIGHTS AT BOTH LEVELS.

    Revision Schedule

    # Date Revision

  • RE

    F.

    CS1

    CS1CS1

    CS1

    CS1CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1 CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    CS1

    DL

    (3) BUNK

    207

    (1) BUNK

    206

    (2) BUNK

    212

    (3) BUNK

    215

    (2) BUNK

    214

    (2) BUNK

    213

    LAUNDRY

    224

    (2) BUNK

    225

    (2) BUNK

    210

    (2) BUNK

    209

    LOCKER ROOM

    221

    (2) BUNK

    226

    WOMEN

    204

    MEN

    205

    (2) BUNK

    208

    POLE 1

    P12

    POLE 2

    P22

    ELEC

    222

    COMPRESSOR RM

    229

    KITCHENETTE

    203

    X2

    X

    X

    X

    X

    X

    X

    XX

    X

    X

    X

    X

    X

    X

    L2 L2

    L2 L2

    L2E

    L2

    L2

    L2E

    L2 L2

    L2

    L2 L2 L2E

    L2

    L2 L2 L2

    NL

    NL

    L2

    NL

    L2

    L11

    L11

    L11

    L11

    L11 L11

    L11

    L11

    L11

    L11L11

    L11

    L11

    L11

    L11 L11

    L11

    L11

    L11

    L11 L11

    L11

    L11

    L11

    L11 L11

    L11

    L11

    L11

    L11

    NL

    NL

    NL

    L12

    L12

    L12

    L12

    L12 L12

    L9

    L9

    L9

    L9

    L9L9A

    L9A

    L9A

    L9A

    L9A

    L9A

    EM

    EMEM

    EM

    EM

    EM

    L17

    L17

    L9

    L17

    L17

    L13

    L13

    L13

    L13

    DAYLIGHT CONTROL ZONE

    L9B L9B

    L9B L9B

    L9BL9B

    L9B L9B

    a b c d e f

    fedcb

    a

    a

    a b

    b c

    c

    d

    d e

    ef

    f

    fedcba

    38(E2R) 37(E2R)

    L12

    L12L12

    L12

    L12

    L12

    L12L12

    11(E2LL)

    10(E2LL)

    40(E2R)

    41(E2R)

    DN

    DN

    DOWN TO SWITCHES

    DOWN TO SWITCHES

    DOWN TO SWITCH

    L1A

    L1A

    L1A

    L1E

    NL

    L1

    L1

    L1 L1

    L1 L1E

    L1

    L1E

    L1A

    L1

    NL

    NL

    NL

    L1E

    L1AL1A

    L1A

    L1

    L1

    L1

    L1A L1A

    L1

    L1E

    L1A

    L1E

    L1

    L1E

    L1

    L1

    L1

    L1

    L1E

    L1

    L1

    L1

    L1E

    L1A

    L1A

    L1A

    L1

    L1E

    L1

    L1E

    NL

    L12

    L12

    L12

    L12

    L12

    L12

    L12

    L12

    8(E2LL)

    LCRP

    LCRPX

    L12

    W1

    W1

    W2

    26,28(EDP)

    L14

    L14 L14 L14 L14 L14

    L14 L14 L14 L14

    L16 L16 L16 L16 L16 L16

    L16 L16 L16 L16E L16 L16

    L16 L16 L16E L16 L16 L16

    L16 L16L16

    L16 L16L16

    L12

    L12L12L12L12L12

    L12

    L12 L12

    L12

    L12

    L12

    L12E

    12(E2LL)74(E2R) 76(E2R)

    78(E2R)

    CORR

    C22

    CORR

    C23

    CORR

    C24

    CORR

    C25

    CORR

    C21

    MEETING 1

    201

    MEETING 2

    202

    STOR

    202A

    LOUNGE

    211

    STAIR 2

    S22

    STAIR 1

    S12

    ELEV

    271

    APPARATUS BAYS

    123

    TRAINING VERANDA

    231

    STORAGE PLATFORM

    230

    WASH BAY

    132

    ELEC

    227

    MECH

    228

    E3

    E3

    ADA TOILET

    216

    TOILET

    217

    TOILET

    218

    TOILET

    219

    TOILET

    220

    CUST

    223

    L2E

    NL

    L2E

    L2E

    NL

    X

    L12E

    E4

    E4

    E4

    L9A

    L9A L9A

    L9A L9A

    L9A

    L9A

    L9AL9A

    EM2

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E1.2

    SECOND FLOOR PLAN- LIGHTING

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    1/8" = 1'-0"1

    SECOND FLOOR PLAN - LIGHTING

    PLANNORTH

    TRUENORTH

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E3 ACTUATION OF OCCUPANCY SENSOR AT EITHERLEVEL SHALL TURN ON LIGHTS AT BOTH LEVELS.

    E4 OUTLINE OF ATTIC WALKWAY ABOVE. PROVIDE SIXPORCELAIN LAMPHOLDERS, EVENLY SPACED, WITH100W-EQUIVALENT LED LAMPS, CONTROLLED VIAPILOT-LIGHT SWITCH IN CUSTODIAN ROOM 223.

    Revision Schedule

    # Date Revision

  • DW

    ICE

    W

    DW D

    W

    D

    TV

    D D D DD

    D D D D D

    J

    D

    TV

    CR

    CR

    CR

    CR

    J

    J

    TV

    J

    J

    J

    J

    J

    J

    J

    J

    J

    J

    TV

    J J J J J

    J J J J J

    J

    J

    H

    H

    H

    J

    CD

    J

    DIRTY SHOP

    125

    UTILITY ROOM

    124

    WOMEN

    122

    STORAGE

    130

    MEN

    121

    STAIR 1

    S11

    APPARATUSBAYS

    123

    OFFICE

    110

    CONF.

    115

    OFFICE

    109

    OFFICE

    107

    OFFICE

    106

    ELEV

    DAYROOM/LOUNGE / DINING

    117

    FITNESS

    116

    MUSEUM

    102

    EVENT KITCHEN

    119B

    CUST

    114

    OFFICE

    104

    OFFICE

    108

    OFFICE

    103

    WATCH DESK

    118

    TOILET(OFFICER)

    113

    MAIN LOBBY

    101

    CORR

    CORR

    STAIR 2

    S21

    TOILET (VOL)

    112

    SCBA

    126

    PANTRY

    120

    CORR

    C14

    COMM/ DATA

    111

    CORR

    C11

    POLE 2

    P21

    WASH BAY

    132

    TABLE / CHAIRSTORAGE

    127

    LAUNDRY

    128

    PPE GEAR

    131

    G

    G

    G

    G

    G

    G

    G

    E2.1

    2

    14-30

    G

    WPG

    WPG

    WPG

    WPG

    FCU-4

    FCU-3

    FCU-2

    FCU-1

    FCU-5

    FCU-11

    FCU-12

    FCU-16

    FCU-6

    FCU-13

    FCU-15

    FCU-14

    FCU-10

    FCU-9

    FCU-8A

    FCU-7

    STATION ALERT RACK (RECEPTS TO PANEL E2L) +72"

    G

    G

    G

    FCU-17

    PROVIDE DUAL CHANNEL MULTI-OUTLET ASSEMBLY AT DESKTOP, OUTLETS 12" O.C., ALTERNATING CIRCUITS

    STEAMCLEANER

    CONNECT TO 3PH, 15HPSCBA STATION WITH STARTER, FURNISHED BY OWNER

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    26(E2L)

    10(E2L)14(E2L)

    28(E2L)

    27(E2L)

    25(E2L)

    8(E2L)

    18(E2L)

    15(E2L)

    12(E2L)

    22(E2LL)

    9(E2L)

    13(E2L)

    11(E2L)

    20(E2L)

    21(E2L)

    23(E2LL)

    16(E2L)

    2(E2R)

    3(E2R)

    WP

    9(E2R)

    EWH-2

    EWH-1

    BS-1

    UH-1

    FCU-8B

    BS-7BS-6

    BS-8 BS-9

    7(E2R)

    G

    5(E2R)

    22,24(P2R)

    FCU-18

    49(E2R)

    26(E2R)

    27(E2R)28(E2R)

    29(E2R)

    18,20(P2R)

    19,21,23(EDP)

    697173

    75

    30(E2R)

    35(E2R)

    33(E2R)

    31(E2R)16(P2L)

    VOL KITCHEN

    119A

    G77(E2L)

    79,81(E2L)

    ELEVATOR CONTROLLER (SEE DETAIL)

    WPG

    3(P2L)

    WPG

    4(P2L)

    WPG

    5(P2L)

    WPG

    6(P2L)

    7(P2L)

    PROVIDE JUNCTION BOX FOR BACKLIT SIGNAGE

    +72"

    8(P2L)

    +72"

    7(E2L)

    ALERT BOARD

    +36"+72"

    E6.2

    4

    WPG WPG

    5(P2R) 4(P2R)

    +108"

    ALERT BOARD

    +108"

    ALERT BOARD

    WPG

    6(P2R) WPG 8(P2R)

    WPG

    7(P2R)

    WPG10(P2R)

    34(E2R)

    +108"

    ALERT BOARD

    +72"

    15(P2L)

    DH-1

    43(E2R)

    44(E2R)

    45(E2R)

    46(E2R)

    14(E2LL)

    U

    U

    U

    U

    15(E2LL)

    16(E2LL)

    +96"

    +96"

    +96"

    +96"

    +96"

    +96"

    +96"

    +96"

    WPG

    14-3048,50(E2R)

    20(P2L)

    19(P2L)

    51(E2R)

    MULTI-OUTLET ASSEMBLY ABOVE COUNTER +42" , OUTLETS 24" O.C.

    17(E2L)M 19(E2LL)

    G20(E2LL)

    +72"

    24(E2L)

    21(P2L) 22(P2L)

    23(P2L)

    G

    G21(E2LL)

    G G G

    H

    H

    H

    H

    24(E2LL)

    G

    25(E2LL)

    14-50

    G

    G

    G

    M

    E1

    E1

    E1

    24,26,28(P2L)

    25,27(P2L)

    12(P2R)

    DRILL PRESS

    WPG

    WPG

    WPG

    9(P2R)

    G

    CONNECT TO GAS RANGE IGNITER

    E1

    31(P2L)

    CONNECT TO GAS SOLENOID SHUTOFF VALVE

    GENERATOR REMOTE ANNUNCIATOR PANEL

    33(P2L)

    RANGE HOOD CONTROL PANEL

    E8

    WPG

    CT

    RELOCATED ATS

    M27(E2LL)G

    m 28(E2LL)

    +72"

    m m m m m

    m m m m m

    83(E2R)81(E2R)

    29(E2LL)

    30(E2LL)

    31(E2LL)

    32(E2LL)33(E2LL)34(E2LL)35(E2LL)

    36(E2LL)

    EWH-3

    E13

    E13

    E14

    E14

    E15E15E15E15E15

    E15 E15E15 E15 E15

    TOILET

    129

    L14-30

    WPG

    400A ECB

    EF-1

    5(E2RR)

    3(E2RR)

    4(E2R)

    PROVIDE JUNCTION BOX FOR CONNECTION OF DESTRATIFICATION FANS CONTROL PANEL

    PROVIDE JUNCTION BOX FOR CONNECTION OF VEHICLE EXHAUST CONTROL PANEL

    FCU-35

    BF-1

    FACP FABP

    MDP EDP

    LTG CONT.

    SPACE RESERVED FOR MISC ELEC EQUIPMENT

    UTILITY ROOM

    124

    6(E2RR)

    PROVIDE JUNCTION BOX FOR CONNECTION OF DRY PIPE SPRINKLER COMPRESSOR.

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E2.1

    FIRST FLOOR PLAN -POWER

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    1/8" = 1'-0"1

    FIRST FLOOR PLAN - POWER

    PLANNORTH

    TRUENORTH

    0 8 12 164

    GRAPHIC SCALE : 1/4"=1'-0"

    1/4" = 1'-0"2

    PART PLAN - UTILITY ROOM

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E1 PROVIDE CONNECTION TO HANDS-FREE SENSORS. COORDINATE WITHDIVISION 20.

    E8 PROVIDE INTERCONNECTING WIRING AS REQUIRED BY RANGE HOODVENDOR DRAWINGS.

    E13 PROVIDE JUNCTION BOX FOR CONNECTION OF DOOR OPERATOR.

    E14 PROVIDE JUNCTION BOX FOR CONNECTION OF HAND DRYER.

    E15 PROVIDE JUNCTION BOX FOR CONNECTION OF GARAGE DOOR OPENER.

    Revision Schedule

    # Date Revision1 2/12/19 PERMIT REVISION #1

    1

  • RE

    F.

    FD

    C

    TV

    J

    J

    J

    J

    J

    J

    J J

    J J

    J

    H

    H

    (3) BUNK

    207

    ELEV

    STAIR 1

    S12

    STAIR 2

    S22

    (1) BUNK

    206

    MEETING 1

    201

    STOR

    202A

    MEETING 2

    202

    (2) BUNK

    212

    (3) BUNK

    215

    (2) BUNK

    214

    (2) BUNK

    213

    LAUNDRY

    224

    (2) BUNK

    210

    (2) BUNK

    209

    LOCKER ROOM

    221

    (2) BUNK

    226

    WOMEN

    204

    MEN

    205

    CORR

    CORR

    (2) BUNK

    208

    POLE 1

    P12

    POLE 2

    P22

    ELEC

    222

    TRAININGVERANDA

    231

    STORAGEPLATFORM

    230

    ELEC

    227

    MECH

    228

    COMPRESSOR RM

    229

    KITCHENETTE

    203

    G

    G

    G G G G G

    P2R

    E2R

    G

    M

    14-30G

    E2L

    P2L

    FCU-24 FCU-25 FCU-26

    FCU-23

    FCU-34

    FCU-33

    FCU-19

    FCU-21

    FCU-20

    FCU-22

    FCU-32

    FCU-31

    FCU-30

    FCU-29

    FCU-27

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    D.8

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    G

    30(E2L)

    22(E2L)

    23(E2L)

    29(E2L)

    UH-2 UH-3

    UH-4

    UH-5

    BS-5

    BS-2

    BS-4

    BS-3

    (2) BUNK

    225

    LOUNGE

    211

    31(E2L)

    33(E2L)

    32(E2L)

    35(E2L)

    34(E2L)37(E2L)

    36(E2L)

    38(E2L)

    67(E2L)

    13(E2R)

    14(E2R)

    CP-1

    B-1

    39(E2L)

    FCU-28

    DF-2

    DF-3

    DF-4

    DF-8DF-7DF-6DF-5

    29(P2L)

    30,32(P2L)

    66(E2L)

    68(E2L)

    19(E2L)

    G40(E2L)

    ADA TOILET

    216

    TOILET

    217

    TOILET

    218

    TOILET

    219

    TOILET

    220

    WPG

    WPG

    WPG

    WPG

    WPG

    WPG

    WPG

    WPG

    WPG

    32(E2R)

    2(P2R)

    PROVIDE JUNCTION BOX FOR BACKLIT SIGNAGE

    1(P2L)

    PROVIDE JUNCTION BOX FOR BACKLIT SIGNAGE

    2(P2L)

    PROVIDE JUNCTION BOX FOR BACKLIT SIGNAGE

    14-50

    9,11(P2L)

    LCRP

    E2LL LCRP

    47(E2R)

    17(E2LL)

    +72"

    18(E2LL)

    18(P2L)

    17(P2L)

    AF-1

    AF-2AF-3 AF-4

    AF-5

    AF-6

    AF-7

    AF-8

    AF-9

    AF-10

    E1

    E1E1

    E1

    CUST

    223

    APPARATUSBAYS

    123

    WASH BAY

    132

    G

    G

    HOIST 11(E2R)C

    WPG

    79(E2R)

    WPG

    E11

    WPGE11

    13(P2R)

    E7

    E12

    E2RR

    CP-2

    AC-1

    FCU-36

    PROVIDE CONNECTION TO OWNER PROVIDED AIR COMPRESSOR. VERIFY CIRCUIT REQUIREMENTS WITH DEVICE

    EF-2

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E2.2

    SECOND FLOOR PLAN- POWER

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    1/8" = 1'-0"1

    SECOND FLOOR PLAN - POWER

    PLANNORTH

    TRUENORTH

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E1 PROVIDE CONNECTION TO HANDS-FREE SENSORS.COORDINATE WITH DIVISION 20.

    E7 PROVIDE CONNECTION TO HEAT TRACE FORDOMESTIC WATER PIPING. COORDINATE WITH DIV. 20.

    E11 PROVIDE WEATHERPROOF GFI RECEPTACLE IN SOFFITFOR SEASONAL LIGHTING. COORDINATE LOCATIONWITH OWNER.

    E12 PROVIDE JUNCTION BOX FOR CONNECTION OFGARBAGE DISPOSAL.

    Revision Schedule

    # Date Revision

  • E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    D.8

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    DOAS-1

    RTU-1

    HRU-1

    WPG

    WPG

    WPG

    1(E2R)

    CU-1

    WPG

    52(E2R)

    L5-20R L5-20RWP

    WP

    75(E2R) 77(E2R)

    WPG E11

    WPG

    E11

    13(P2R)

    WPG

    E11

    WPG

    E11

    WPG

    E11

    WPG

    E11

    34(P2L)

    KEF-1

    MAU-1

    WPG

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E2.3

    ROOF PLAN - POWER

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    1/8" = 1'-0"1

    ROOF PLAN - POWER

    PLANNORTH

    TRUENORTH

    Revision Schedule

    # Date Revision

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E11 PROVIDE WEATHERPROOF GFI RECEPTACLE IN SOFFIT FOR SEASONALLIGHTING. COORDINATE LOCATION WITH OWNER.

  • DW

    ICE

    W

    DW D

    W

    D

    FF FF

    FF FF

    FFFF

    F

    FF

    F

    F

    FF

    FF

    FFF

    FF

    SD

    FSTS

    F

    FF

    F

    FF F

    FF

    CD

    F

    FF

    F

    FF

    FF

    F

    FF

    F

    F

    FF

    FF

    F

    F

    F

    FF

    F F

    FF FS

    TS

    F

    F

    PS

    TS

    DIRTY SHOP

    125

    UTILITY ROOM

    124

    WOMEN

    122

    STORAGE

    130

    MEN

    121

    STAIR 1

    S11

    APPARATUS BAYS

    123

    OFFICE

    110

    CONF.

    115

    OFFICE

    109

    OFFICE

    107

    OFFICE

    106

    ELEV

    260

    DAYROOM/ LOUNGE /DINING

    117

    FITNESS

    116

    MUSEUM

    102

    EVENT KITCHEN

    119BCUST

    114

    OFFICE

    104

    OFFICE

    108

    OFFICE

    103

    WATCH DESK

    118

    TOILET(OFFICER)

    113

    MAIN LOBBY

    101

    CORR

    C12

    CORR

    C13

    STAIR 2

    S21

    TOILET (VOL)

    112

    SCBA

    126

    PANTRY

    120

    CORR

    C14

    COMM/ DATA

    111

    CORR

    C11

    POLE 2

    P21

    WASH BAY

    132

    TABLE / CHAIRSTORAGE

    127

    LAUNDRY

    128

    PPE GEAR

    131

    15

    30

    30

    15

    15

    15

    75

    75

    30

    30

    15

    15

    15

    75 75

    75

    75

    7575

    30

    75

    75

    15

    15

    FAAP

    FABP

    BOTTOM OF PIT

    30

    15

    15

    15

    WP WP

    WP

    WP

    WPWP

    15

    WP

    WP

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    CORR

    C15

    TOILET

    129

    VOL KITCHEN

    119A

    POLE 1

    P11

    75

    FACP

    15

    E2

    15

    E6E6

    E9

    VALVE ROOM

    133

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E3.1

    FIRST FLOOR PLAN -FIRE ALARM

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    1/8" = 1'-0"1

    FIRST FLOOR PLAN - FIRE ALARM

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    PLANNORTH

    TRUENORTH

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E2 PROVIDE FIRE ALARM INTERFACE FOR RANGE HOODPER MANUFACTURER'S INSTRUCTIONS.

    E6 CONFIRM QUANTITY AND LOCATION WITH DIV. 20.

    E9 PROVIDE FIRE ALARM INTERFACE FOR OVERHEADCOILING DOOR. DOOR SHALL RELEASE UPONBUILDING ALARM ACTIVATION.

    Revision Schedule

    # Date Revision

  • RE

    F.

    FFFF F

    FF

    FF

    FF

    FF

    F

    F

    F

    F

    F

    F F

    F

    FF

    FF

    FF

    F

    FF

    FF

    FF

    FF

    FF

    F

    F

    SD

    TS FS

    SD SD

    FF

    F

    F

    F

    F

    F

    CO

    CO CO

    CO

    CO

    CO

    CO

    CO

    CO

    CO

    CO

    F

    FF

    F

    SD

    SD

    SD

    SD SD

    SD

    SD

    SD SD SD

    SD

    SD

    DD

    DD

    DD

    DD

    F

    F

    FF

    FF

    (3) BUNK

    207

    ELEV

    271

    STAIR 1

    S12

    STAIR 2

    S22

    (1) BUNK

    206

    LOUNGE

    211

    MEETING 1

    201

    STOR

    202A

    MEETING 2

    202

    (2) BUNK

    212

    (3) BUNK

    215

    (2) BUNK

    214

    (2) BUNK

    213

    LAUNDRY

    224

    (2) BUNK

    225

    (2) BUNK

    210

    (2) BUNK

    209

    LOCKER ROOM

    221 (2) BUNK

    226

    WOMEN

    204

    MEN

    205

    CORR

    C22

    CORR

    C25

    (2) BUNK

    208

    POLE 1

    P12

    POLE 2

    P22

    ELEC

    222

    TRAINING VERANDA

    231

    STORAGE PLATFORM

    230

    ELEC

    227

    MECH

    228

    COMPRESSOR RM

    229

    KITCHENETTE

    203

    30

    15

    15

    15

    15

    75

    75 15

    15

    1515

    1515 15

    15

    15

    15

    15

    15

    30

    WP

    15

    TOP OF SHAFT

    75

    15

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    D.8

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    30

    WP

    WP

    WPWP

    WPWP WP PROVIDE 120V CIRCUIT TO DETECTORS,

    PER PANEL SCHEDULE (TYP.)

    INTERCONNECT DETECTORS AS SHOWN (TYP.)

    FA

    BP

    E5

    E5E5

    15

    C

    1515

    E5

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E3.2

    SECOND FLOOR PLAN- FIRE ALARM

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    1/8" = 1'-0"1

    SECOND FLOOR PLAN - FIRE ALARM

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    PLANNORTH

    TRUENORTH

    ELECTRICAL SPECIFIC NOTE LEGEND

    SPECIFICNOTE VALUE SPECIFIC NOTE TEXT

    E5 PROVIDE DUCT SMOKE DETECTOR FOR UNIT ABOVE.DETECTOR SHALL BE FURNISHED BY DIV. 26,INSTALLED IN DUCT BY DIV. 20, AND TIED TO FIREALARM SYSTEM BY DIV. 26.

    Revision Schedule

    # Date Revision

  • DW

    ICE

    W

    DW D

    W

    D

    v

    s ss

    s

    SW

    s

    s

    s

    s

    s

    s

    s

    s s

    s s

    s

    s

    s

    v

    DB

    DB

    v v

    v

    ss

    s

    s sSL

    vv

    vv

    v

    M/A

    M/A

    SL

    SL

    s

    s

    s

    HS

    HS

    HS

    HS

    DB

    DIRTY SHOP

    125

    UTILITY ROOM

    124

    WOMEN

    122

    STORAGE

    130

    MEN

    121

    STAIR 1

    S11

    APPARATUSBAYS

    123

    OFFICE

    110

    CONF.

    115

    OFFICE

    109

    OFFICE

    107

    OFFICE

    106

    DAYROOM/LOUNGE / DINING

    117

    FITNESS

    116

    MUSEUM

    102

    VOL KITCHEN

    119A

    MAIN LOBBY

    101

    STAIR 2

    S21

    PANTRY

    120

    WASH BAY

    132

    TABLE / CHAIRSTORAGE

    127

    PPE GEAR

    131OFFICE

    104

    OFFICE

    103 POLE 1

    P11

    CORR

    C11

    CUST

    114

    TOILET(OFFICER)

    113

    TOILET (VOL)

    112

    CORR

    C13

    COMM/ DATA

    111

    WATCH DESK

    118

    POLE 2

    P21

    EVENT KITCHEN

    119B

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    CORR

    C15

    LAUNDRY

    128 TOILET

    129

    AMP

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E4.1

    FIRST FLOOR PLAN -STATION ALERT

    SYSTEM

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    1/8" = 1'-0"1

    FIRST FLOOR PLAN - STATION ALERT SYSTEM

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    Revision Schedule

    # Date Revision

  • RE

    F.

    FD

    s

    s s s s

    vvvv

    SLHVR

    SW

    SL

    HVR

    SW

    SL

    SW

    HVR

    HVR

    s

    SL

    v

    SW

    HVR

    s

    SL

    vSW

    s

    s

    s

    s

    s

    s

    s s

    s

    s s s s s

    s

    s s

    s

    s

    s

    s

    s

    s

    s

    SW vSW

    vSL SL

    HVR HVR

    HVR

    SL

    SL

    HVR

    v

    SW

    v

    SW HVR

    SL

    SL

    SW

    M/A

    SW

    M/A

    v

    SW

    SL

    HVR

    HS

    s s

    SWv

    s

    (2) BUNK

    212

    (3) BUNK

    215

    (2) BUNK

    214

    (2) BUNK

    213

    LAUNDRY

    224

    LOCKER ROOM

    221 (2) BUNK

    226

    WOMEN

    204

    MEN

    205

    POLE 1

    P12

    POLE 2

    P22

    ELEC

    222

    COMPRESSOR RM

    229

    KITCHENETTE

    203

    CORR

    C21MEETING 1

    201

    MEETING 2

    202

    CORR

    C25

    ADA TOILET

    216

    TOILET

    217

    TOILET

    218

    TOILET

    219

    TOILET

    220

    CORR

    C22

    STOR

    202A

    (1) BUNK

    206

    (3) BUNK

    207

    STAIR 2

    S22

    (2) BUNK

    208

    (2) BUNK

    209

    (2) BUNK

    210

    LOUNGE

    211

    ELEC

    227

    MECH

    228

    STORAGEPLATFORM

    230

    TRAININGVERANDA

    231

    E F

    G H

    I

    CA

    10

    7.8

    7

    6.1

    6

    5

    4

    3

    1

    B

    PONMLKJ

    9

    I.2 M.8

    7.6

    C.9C.3

    2

    D

    H.1

    4.4

    4.9

    5.5

    D.8

    I.1

    8.7

    F.2E.9

    1.2

    I.1A N.9

    9.2

    8

    9.3

    (2) BUNK

    225

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E4.2

    SECOND FLOOR PLAN- STATION ALERT

    SYSTEM

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    1/8" = 1'-0"1

    SECOND FLOOR PLAN - STATION ALERT SYSTEM

    0 16 24 328

    GRAPHIC SCALE : 1/8"=1'-0"

    Revision Schedule

    # Date Revision

  • Y

    DIALER

    SD

    FS

    TS

    F F

    FAAP

    MM

    MM

    DIALER

    F

    IN UTILITY ROOM

    ON PLAN. ZONE AS REQUIREDCONNECT TO SMOKE DETECTORS INDICATED

    CONNECT TO FLOW SWITCHESZONE AS REQUIRED

    ZONE AS REQUIREDCONNECT TO TAMPER SWITCHES

    CONNECT TO VISUAL AND AUDIBLE/VISUALDEVICES INDICATED ON PLAN.

    CONNECT TO MANUAL DEVICES INDICATED ONPLANS. ZONE AS REQUIRED.

    AT BUILDING

    BATT

    FACP

    ENTRANCE LOBBY

    MANUFACTURERS RECOMMENDATIONS.

    FIRE ALARM SYSTEM EQUIPMENT IS SHOWN ON THE RISER. HOWEVER,WIRING IS NOT SHOWN. WIRING VARIES BETWEEN MANUFACTURERS.THE WIRING AND CONDUIT SHALL BE INSTALLED IN ACCORDANCE WITH

    1.

    NOTES:

    2.

    3.

    4.

    120V

    25(EDP)LEVEL 1

    LEVEL 2

    RISER DIAGRAM - POWER

    FIRE ALARM RISER DIAGRAM

    GENERAL TWO-WAY COMMS SYSTEM NOTES:

    TWO-WAY COMMUNICATION SYSTEM RISER DIAGRAM

    TELECOMMUNICATIONS RISER

    NOT TO SCALE

    ADDRESSABLE IDC LOOP

    NOT TO SCALE

    PROVIDE SMOKE DETECTOR AT FIRE ALARM CONTROL PANEL LOCATION.

    COORDINATE FINAL LOCATION OF ANNUNCIATOR WITH LOCAL FIREMARSHAL.

    PROVIDE (1) 4PAIR CAT3 TELEPHONE CABLE IN 3/4" CONDUITFROM FIRE ALARM DIGITAL COMMUNICATOR (DACT) TO MAINTELEPHONE BACKBOARD LOCATION.

    1. PROVIDE A TWO-WAY COMMUNICATION SYSTEM AT ALL ELEVATOR LOBBIES

    ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE, PER THE REQUIREMENTS

    OF 2009 IBC 1007.8.

    2. PROVIDE AN AUTOMATIC DIALER TO A CENTRAL, SUPERVISED LOCATION, AS

    APPROVED BY AHJ.

    3. PROVIDE A PLACARD ADJACENT TO EACH CALL STATION WITH INSTRUCTIONS

    ON SYSTEM USE.

    4. BASIS OF DESIGN SYSTEM IS BY CORNELL COMMUNICATIONS.

    5. ALL WIRING, CONDUIT SIZES AND QUANTITIES SHALL BE IN ACCORDANCE WITH

    THE SYSTEM MANUFACTURER'S RECOMMENDATIONS.

    6. THE DEVICES AND EQUIPMENT SHOWN ON THE DRAWINGS ARE FOR A MINIMUM

    REQUIREMENT. PROVIDE ADDITIONAL DEVICES AND/OR EQUIPMENT AS

    REQUIRED, AND ANY OTHER REQUIREMENTS OF THE DCRA/FIRE PROTECTION

    DIVISION, AT NO ADDITIONAL COST TO THE OWNER.

    SYSTEMANNUNCIATOR

    PANEL

    CALLSTATION

    ELEVATOR LOBBY

    POWERSUPPLY

    NOT TO SCALE

    AUDIO CABLING & VISIBLE SIGNAL

    CABLING (TYP.)

    NOT TO SCALE

    2nd FLOOR

    ROOF

    TERMINALBOARD

    COMM/DATA RM 111

    (2) 4" RACEWAY

    CAT 5ECABLE (TYP.)

    MINIMUM 36° RADIUS(TYPICAL)

    TELEPHONE SERVICE TOPROPERTY LINE -COORDINATE WITHUTILITY COMPANYREQUIREMENTS

    FA DACT

    FA DACT

    REFER TO FLOOR PLANFOR OUTLET LOCATIONAND QUANTITY

    SPECIAL NOTES:1. FOR ADDITIONAL OUTLETS, REFER TO PLANS.2. PROVIDE MINIMUM 36" RADIUS 90° ELBOWS FOR CAT 5E RISER CABLE.

    3/4" PLYWOODTERMINAL BOARD

    1ST FLOOR

    REFER TO FLOOR PLANFOR OUTLET LOCATIONAND QUANTITY

    SECURITY

    TWO-WAY COMMS

    ELEVATOR

    (1) 4" RACEWAY

    CABLE TV SERVICE TOPROPERTY LINE -COORDINATE WITHUTILITY COMPANYREQUIREMENTS

    TV

    TV

    RG6 (TYP.)

    REFER TO FLOOR PLANFOR OUTLET LOCATIONAND QUANTITY

    EN

    FIRST FLOOR

    SECOND FLOOR

    ROOF

    PANELEDP208/120V3PH, 4W

    UTLITY XFMR208/120V 3PH4W SECONDARY

    GRADE

    600A

    EX. RELOCATED 150KW

    NATURAL GAS

    GENERATOR

    GENERAC SG150

    208/120V 3PH 4W

    UTILITY PRIMARY

    UTILITYMETER

    RELOCATE EX. ATSEATON ATC-300208/120V 3PH 4W, 3P SN600ASE-RATED

    PANELMDP208/120V3PH, 4W

    PANELE2L208/120V3PH, 4W

    PANEL P2L208/120V3PH, 4W

    PANELE2R208/120V3PH, 4W

    PANEL P2R208/120V3PH, 4W

    2 SETS (4-350KCMIL IN 2-1/2" C)

    2 SETS (4-350KCMIL, 1#1 G IN 2-1/2" C)

    2 SETS (4-350KCMIL, 1#1 G IN 2-1/2" C)

    SPDSPD

    1200A

    UTILITY-APPROVED

    CT CABINET

    PANELE2LL208/120V3PH, 4W

    LIGHTINGCONTROLRELAYPANEL

    LIGHTINGCONTROLRELAYPANEL

    24" MIN.

    PROVIDE SECONDARY CONDUIT IN

    CONCRETE-ENCASED DUCT BANK, (3)

    4" SCH. 40 PVC, PER UTILITY

    STANDARDS. WIRE FURNISHED &

    INSTALLED BY UTILITY.

    36" RADIUS (TYP.)

    PROVIDE XFMR PAD

    & GROUNDING PER

    UTILITY STANDARDS

    RELOCATE EXISTING GENERATOR.PROVIDE NEW CONDUIT STUBS,GROUNDING, AUXILIARY CONTACTS,ETC. AS REQUIRED FOR ACOMPLETE SYSTEM

    PROVIDE 1"C. AND ALARM WIRING TO RAP/FIRE ALARM SYSTEM

    PROVIDE 1"C. AND CONTROL WIRING TO ATS

    PROVIDE 1"C. AND WIRING FOR BATTERY CHARGER AND BLOCK HEATER, PER PANEL SCHEDULE

    RELOCATE EXISTING ATS

    2 SETS (4-350KCMIL IN 2-1/2" C)

    600A ECB, 22KAIC, NEMA 3R, SE RATED

    PANELE2RR208/120V3PH, 4W

    2 SETS (4-350KCMIL, 1#1 G IN 2-1/2" C)

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E6.1

    ELECTRICAL DETAILS

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    Revision Schedule

    # Date Revision

  • PIT/HOISTWAY

    CONTACTOR SCHEDULE - C1P

    1

    2

    3

    4

    REMARKS: MECHANICALLY HELD, ELECTRICALLY OPERATED CONTACTOR IN

    NEMA 1 ENCLOSURE WITH 2 WIRE CONTROL AND 120V COIL

    CIRCUIT 30A CONTACTS

    NO

    1

    1

    1

    1

    NC

    REMARKS

    PHOTOCELL ON/TIMECLOCK OFF

    5

    6

    1

    -

    EXTERIOR BUILDING LIGHTING26,28(EDP)

    2(P2R)

    7

    8

    1

    1

    SPARE

    SPARE

    CONTACTOR SCHEDULE - C2P

    1

    2

    3

    4

    REMARKS: MECHANICALLY HELD, ELECTRICALLY OPERATED CONTACTOR IN

    NEMA 1 ENCLOSURE WITH 2 WIRE CONTROL AND 120V COIL

    CIRCUIT 30A CONTACTS

    NO

    1

    1

    1

    1

    NC

    REMARKS

    PHOTOCELL ON/TIMECLOCK OFF

    5

    6

    1

    1

    BUILDING SIGNAGE1(P2L)

    SPARE

    SPARE

    2(P2L)

    7(P2L)

    BUILDING SIGNAGE

    BUILDING SIGNAGE

    -

    SITE LIGHTING1,3(EDP)

    BUILDING SIGNAGE

    13(E2LL) EXTERIOR BUILDING LIGHTING

    1SPARE

    FA

    FA

    SDHD

    SD

    SD

    HD

    SD

    GENERAL ELEVATOR NOTES:

    1.

    2.

    3.

    4.

    PROVIDE SHUNT-TRIP TYPE CIRCUIT BREAKER(S) FOR ELEVATORFEEDER(S). REFER TO PANEL SCHEDULES AND POWER RISERDIAGRAM FOR FEEDER CIRCUIT BREAKER AND CONFIGURATIONALLOWANCES. COORDINATE OVERCURRENT PROTECTION DEVICES& WIRING W/ELEVATOR MOTOR/EQUIP. NAMEPLATE DATA. FIELDLOCATE EQUIPMENT AS NECESSARY FOR A COMPLETE ANDSATISFACTORY SYSTEM, MEETING THE REQUIREMENTS OF THEAUTHORITY HAVING JURISDICTION AND ELEVATOR INSTALLER.

    CONNECT HEAT DETECTORS IN ELEVATOR PIT(S), MACHINE ROOM(S)AND SHAFT(S) TO SHUNT-TRIP DEVICE SO THAT UPON ACTIVATIONTHE SHUNT-TRIP BREAKER SHUTS DOWN POWER TO THEELEVATOR(S) PER ASME-17.1, 102.2c.

    PROVIDE A HEAT DETECTOR WITHIN 18" OF EACH SPRINKLER HEADLOCATED IN THE ELEVATOR PIT, MACHINE ROOM OR SHAFT.

    PROVIDE 2 PAIR OF CAT 3 CABLE FROM ELEVATOR CONTROLLER TOMAIN TELEPHONE BACKBOARD. TERMINATE AT BACKBOARD ON 110BLOCK.

    5.

    6.

    REFER TO DIVISION 20 FOR FLOW AND TAMPER SWITCHREQUIREMENTS RELATED TO ELEVATOR(S).

    SUMP

    PIT

    LOWER LEVEL

    UPPER LEVEL

    TYPICAL ELEVATOR SHAFT

    ROOF

    FA

    EC

    EC

    FA

    EC

    FA

    EC

    EC

    ELEVATOR PIT

    TO ELEVATORCONTROLLERSYSTEM TYP.

    TO FIRE ALARMSYSTEM TYP.

    FA

    TO FIREALARMSYSTEM TYP.

    ECWPG

    S3WP

    LTG FIXTURE TYPE L9A, ON EACHWALL OF PIT, WET LOCATION LISTED

    PROVIDE AUXILIARY CONTACTS IN DISCONNECT SWITCH SERVINGELEVATOR.

    HEAT DETECTOR NOTREQUIRED WHEN TOP OFHOISTWAY IS NOTSPRINKLERED. COORDINATEWITH DIVISION 20 INSTALLER.

    HEAT DETECTOR NOT REQUIREDWHEN SPRINKLER HEADINSTALLED WITHIN 24 INCHES OFPIT FLOOR. COORDINATE WITHDIVISION 20 INSTALLER.

    2P30A FSS F@20A FORELEVATOR CABLIGHTING AND POWER

    3P-200A FSS F@125AFOR ELEVATORCONTROLLER

    S3WP

    L9A

    7. BASIS OF DESIGN ELEVATOR = OTIS HYDROFIT 2100# MRL, 20HP, 72FLA

    WPG

    L9A

    L9A

    7,9,11(MDP)

    10(P2L)

    12(P2L)

    13(P2L)

    14(P2L)

    DETAIL - GROUNDING ELECTRODE SYSTEM

    CONTROL DIAGRAM - EXTERIOR LIGHTING

    DETAIL - ELEVATOR PIT/HOISTWAY AND CONTROL SPACE

    C2

    PC

    TC

    C1

    TYPICAL SERVICE EQUIPMENT

    GROUND ROD3/4" x 10'

    BUILDING STEELBAR

    EQUIPMENTGROUNDING

    MAIN UNDERGROUND

    ENCLOSURE(TYP)NEUTRAL

    BUS

    EXTERIOR

    WALL

    CONNECT TORE-BAR INWALL FOOTING

    NOT TO SCALE

    METAL WATER PIPE

    BONDING JUMPER, SIZEPER NEC BASED ONUNGROUNDEDCONDUCTORS

    #4 AWGCOPPER

    #6 AWGCOPPER

    O

    A

    H

    CONTROL WIRING SHALL CONSIST OF #12'S IN 3/4" CONDUIT.

    NO SCALE

    NOTE:

    PCLIGHTING CONTACTOR

    N

    PHOTOCELL

    TIMECLOCK

    TC

    NOT TO SCALE

    EXOTHERMIC WELD

    1/4" x 2" x 12" LONG MEDIUM DRAWN,98% CONDUCTIVITY, COPPER GROUND BAR

    INSULATING-TYPE STAND OFFS. (TYP.)

    STAND-OFFSSECURE TO WALLSAS REQUIRED. (TYP.)

    BRASS HEX BOLTS W/BRONZEWASHERS. (TYP.)

    DRILLED HOLES FOR USEW/CONN(S) OF GND WIRESUSING BARREL-TYPE LUGS.QUANTITIES AND SIZESSHALL BE AS REQUIRED PERINTENDED USE.

    GROUNDING RISERUP/DOWN TO NEXTGROUND BAR, PERGROUNDING RISERDIAGRAM

    6' MIN.

    #6 AWGCOPPER

    #3/0 AWGCOPPER

    O

    A

    H

    PCLIGHTING CONTACTOR

    TC

    CONC.

    STRANDED GROUND

    1#6 BARE COPPER

    CADWELD CONNECTION

    GROUND ROD - 3/4"X10'-0"

    2'-0"

    30"

    6'-6

    " M

    IN.

    #3 TIES AT 10"O.C.

    VERTICAL REINFORCEMENT

    CONCRETE WITH (8) #7 REBAR

    (MIN.) DIA 2'-0"

    PVC COND. (TYP.)

    STEEL ANCHOR BOLTS

    QUANT., LENGTH, DIA.

    FINISHED GRADE/PAVEMENT

    RECOMMENDATIONS

    CONC. PER MANUFACTURER'S

    AND PROJECTION FROM

    30

    " M

    IN.

    4"MIN.

    CONDUIT STUB-UPS

    HANDHOLE W/ COVER

    BOLT COVER

    1" CHAMFER ALL AROUND

    GROUND LUGPOLE

    GFCI RECEPTACLE WITH WP COVER

    2 DETAIL - TELECOM GROUND BAR

    DETAIL - POLE BASE

    MAIN WATER SERVICESHUT OFF VALVE

    BONDING JUMPERAROUND VALVE

    HOA SWITCH IN ENCLOSURECOVER

    NOT TO SCALE

    HOA SWITCH IN ENCLOSURECOVER

    NOT TO SCALE

    These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E6.2

    ELECTRICAL DETAILS

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    Revision Schedule

    # Date Revision

  • These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E8.1

    ELECTRICALSCHEDULES

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    Notes:

    Electric Dryer 5000 VA 100.00% 5000 VA

    Water Heating 1200 VA 100.00% 1200 VA

    Heating 600 VA 100.00% 600 VA

    Receptacle 54500 VA 59.17% 32250 VA

    Power 28300 VA 100.00% 28300 VA Total Est. Demand Current: 592 A

    Other 17488 VA 100.00% 17488 VA Total Conn. Current: 644 A

    Motor 27721 VA 100.00% 27721 VA Total Est. Demand: 213381 VA

    Lighting 14101 VA 125.00% 17626 VA Total Conn. Load: 232102 VA

    HVAC 79512 VA 100.00% 79512 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 657 A 650 A 633 A

    Total... 78516 VA 77720 VA 75903 VA

    41 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 42

    39 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 40

    37 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 38

    35 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 36

    33 Space -- -- 0.0 kVA 0.0 kVA 1 20 A Spare 34

    31 Space -- -- 0.0 kVA 0.0 kVA 1 20 A Spare 32

    29 FACP 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.0 kVA 1 20 A Spare 30

    27 FACP 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.3 kVA -- -- -- -- -- 28

    25 TWO WAY CALL... 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.3 kVA 3/4" 2#12, 1#12G 2 20 A Wall Packs 26

    23 -- -- -- -- -- 5.8 kVA 24.8... -- -- -- -- -- 24

    21 -- -- -- -- -- 5.8 kVA 24.8... -- -- -- -- -- 22

    19 Ex. SCBA Station 100 A 3 3#3, 1#8G 1-1/4" 5.8 kVA 24.3... 2-1/2" 4#250KCMIL, 1#4G 3 250 A Panel E2R 20

    17 -- -- -- -- -- 3.9 kVA 22.5... -- -- -- -- -- 18

    15 -- -- -- -- -- 3.9 kVA 23.2... -- -- -- -- -- 16

    13 Garage Vehicle EF 60 A 3 3#6, 1#10G 1" 3.9 kVA 24.8... 2-1/2" 4#250KCMIL, 1#4G 3 250 A Panel E2L 14

    11 -- -- -- -- -- 4.6 kVA 5.6 kVA -- -- -- -- -- 12

    9 -- -- -- -- -- 4.6 kVA 5.6 kVA -- -- -- -- -- 10

    7 HRU-1 (CKT 1) 50 A 3 3#8, 1#10G 3/4" 4.6 kVA 5.6 kVA 1" 3#4, 1#8G 3 70 A HRU-1 (CKT 2) 8

    5 Space -- -- 0.0 kVA 8.3 kVA -- -- -- -- -- 6

    3 -- -- -- -- -- 0.8 kVA 8.3 kVA -- -- -- -- -- 4

    1 Site Lighting 20 A 2 2#8, 1#8G 1" 0.8 kVA 8.3 kVA 1-1/4" 3#3, 1#8G 3 100 A DOAS-1 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating: 600 A

    Mounting: Surface Wires: 4 Mains Rating: 600 A

    Supply From: Phases: 3 Mains Type: MCB

    Location: UTILITY ROOM 124 Volts: 120/208 Wye A.I.C. Rating: 22K

    Branch Panel: EDP

    (1) MATCH SIZE OF EXISTING CIRCUIT.(2) PROVIDE SHUNT TRIP CIRCUIT BREAKER. BREAKER SIZE SHOWN FOR BID PURPOSES ONLY. VERIFY WITH ELEVATOR SHOP DRAWINGS.

    Notes:

    Electric Dryer 10000 VA 100.00% 10000 VA

    Receptacle 7380 VA 100.00% 7380 VA Total Est. Demand Current: 416 A

    Power 48700 VA 100.00% 48700 VA Total Conn. Current: 414 A

    Motor 26650 VA 100.00% 26650 VA Total Est. Demand: 149881 VA

    Lighting 3100 VA 125.00% 3875 VA Total Conn. Load: 149107 VA

    HVAC 53306 VA 100.00% 53306 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 403 A 428 A 415 A

    Total... 48329 VA 51209 VA 49577 VA

    41 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 42

    39 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 40

    37 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 38

    35 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 36

    33 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 34

    31 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 32

    29 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 30

    27 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 28

    25 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 26

    23 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 24

    21 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 22

    19 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 20

    17 -- -- -- -- -- 1.0 kVA 0.0 kVA 1 20 A Spare 18

    15 Genset Block Heater (1) 20 A 2 2#12, 1#12G 1" 1.0 kVA 0.0 kVA 1 20 A Spare 16

    13 Genset Battery Charger (1) 20 A 1 2#12, 1#12G 1" 0.5 kVA 0.0 kVA 1 20 A Spare 14

    11 -- -- -- -- -- 8.6 kVA 9.4 kVA -- -- -- -- -- 12

    9 -- -- -- -- -- 8.6 kVA 10.2... -- -- -- -- -- 10

    7 Elevator (2) 150 A 3 3#1/0, 1#6G 1-1/2" 8.6 kVA 8.9 kVA 2" 4#3/0, 1#6G 3 200 A Panel P2R 8

    5 -- -- -- -- -- 14.6... 15.9... -- -- -- -- -- 6

    3 -- -- -- -- -- 14.6... 16.7... -- -- -- -- -- 4

    1 RTU-1 175 A 3 3#2/0, 1#6G 2" 14.6... 15.7... 2" 4#3/0, 1#6G 3 200 A Panel P2L 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating: 600 A

    Mounting: Surface Wires: 4 Mains Rating: 600 A

    Supply From: Phases: 3 Mains Type: MCB

    Location: UTILITY ROOM 124 Volts: 120/208 Wye A.I.C. Rating: 22K

    Branch Panel: MDP

    Notes:

    Receptacle 41240 VA 62.12% 25620 VA

    Power 8700 VA 100.00% 8700 VA Total Est. Demand Current: 156 A

    Other 0 VA 0.00% 0 VA Total Conn. Current: 196 A

    Motor 1656 VA 100.00% 1656 VA Total Est. Demand: 56260 VA

    Lighting 5476 VA 125.00% 6845 VA Total Conn. Load: 70484 VA

    HVAC 10773 VA 100.00% 10773 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 208 A 195 A 187 A

    Total... 24783 VA 23232 VA 22469 VA

    83 Outdoor Sign 20 A 1 2#12, 1#12G 1" 0.5 kVA 8.4 kVA -- -- -- -- -- 84

    81 -- -- -- -- -- 0.8 kVA 7.2 kVA -- -- -- -- -- 82

    79 Plugmold Watchdesk 20 A 2 2#12, 1#12G 3/4" 0.8 kVA 8.5 kVA 1-1/4" 4#3, 1#8G 3 100 A Panel E2LL 80

    77 Dishwasher 119A 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.3 kVA -- -- -- -- -- 78

    75 Recept Station Alert 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.3 kVA 3/4" 2#12, 1#12G 2 15 A FCU-28,29,30,31 76

    73 Recept Station Alert 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.6 kVA -- -- -- -- -- 74

    71 Recept Station Alert 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.6 kVA -- -- -- -- -- 72

    69 Recept Station Alert 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.6 kVA 3/4" 3#12, 1#12G 3 15 A ESP-1 70

    67 Refrig 203 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.4 kVA 3/4" 2#12, 1#12G 1 20 A GFI Recepts 68

    65 -- -- -- -- -- 0.8 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A GFI Recepts 66

    63 EWH-1 20 A 2 2#12, 1#12G 3/4" 0.8 kVA 0.8 kVA -- -- -- -- -- 64

    61 -- -- -- -- -- 0.1 kVA 0.8 kVA 3/4" 2#12, 1#12G 2 20 A EWH-2 62

    59 FCU-11,12 15 A 2 2#12, 1#12G 3/4" 0.1 kVA 0.3 kVA -- -- -- -- -- 60

    57 -- -- -- -- -- 0.6 kVA 0.3 kVA 3/4" 2#12, 1#12G 2 15 A FCU-14,15 58

    55 FCU-2,16 & BS-6,7 15 A 2 2#12, 1#12G 3/4" 0.6 kVA 0.5 kVA -- -- -- -- -- 56

    53 -- -- -- -- -- 0.4 kVA 0.5 kVA 3/4" 2#12, 1#12G 2 15 A FCU-9,10,13,35, BS-8,9 54

    51 FCU-5,6,7,8A,8B 15 A 2 2#12, 1#12G 3/4" 0.4 kVA 0.3 kVA -- -- -- -- -- 52

    49 -- -- -- -- -- 0.4 kVA 0.3 kVA 3/4" 2#12, 1#12G 2 15 A FCU-1,3,4 50

    47 FCU-24,25,26,33,34 15 A 2 2#12, 1#12G 3/4" 0.4 kVA 0.2 kVA -- -- -- -- -- 48

    45 -- -- -- -- -- 0.5 kVA 0.2 kVA 3/4" 2#12, 1#12G 2 15 A FCU-27,28,29,30,31 46

    43 FCU-19,21 & BS-2,4,5 15 A 2 2#12, 1#12G 3/4" 0.5 kVA 0.5 kVA -- -- -- -- -- 44

    41 Smoke Detectors 20 A 1 2#12, 1#12G 3/4" 0.0 kVA 0.5 kVA 3/4" 2#12, 1#12G 2 15 A FCU-20,22,23,32,36,... 42

    39 Water Cooler 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.4 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Kitchenette 40

    37 Floor Boxes Mtg 1 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.2 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Bathrooms 38

    35 Floor Boxes Mtg 2 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Mtg 1 36

    33 Recepts Hall 20 A 1 2#12, 1#12G 3/4" 0.9 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Floor Boxes Mtg 1 34

    31 Recepts Bunks 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Floor Boxes Mtg 2 32

    29 Recepts Hall/Bunks 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 1.1 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Bunks 30

    27 Recepts 107/108 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 1.3 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Lounge 28

    25 Recepts 106/107 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Recepts 110 26

    23 Recepts Bunks 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Recepts 109 24

    21 Freezer 119B 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Lounge/Bunks 22

    19 Microwave 203 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Refrig 119B 20

    17 Recepts 119B 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Fitness 18

    15 Recepts Fitness 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Recepts App Bay 16

    13 Recepts 119A 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.4 kVA 3/4" 2#12, 1#12G 1 20 A Recept Comm/Data 14

    11 Recepts 119A 20 A 1 2#12, 1#12G 3/4" 0.4 kVA 1.2 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Bathrooms 12

    9 Refrig 119A 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Recept Comm/Data 10

    7 Recepts Lounge 20 A 1 2#12, 1#12G 3/4" 1.3 kVA 1.3 kVA 3/4" 2#12, 1#12G 1 20 A Recepts 103/104 8

    5 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 6

    3 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 4

    1 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating:

    Mounting: Surface Wires: 4 Mains Rating: 250 A

    Supply From: EDP Phases: 3 Mains Type: MLO

    Location: ELEC 222 Volts: 120/208 Wye A.I.C. Rating: 10K

    Branch Panel: E2L

    (1) PROVIDE GFCI BREAKER.(2) PROVIDE GFEP BREAKER.

    Notes:

    Electric Dryer 5000 VA 100.00% 5000 VA

    Water Heating 1200 VA 100.00% 1200 VA

    Heating 600 VA 100.00% 600 VA

    Receptacle 13260 VA 87.71% 11630 VA

    Power 19400 VA 100.00% 19400 VA Total Est. Demand Current: 205 A

    Other 100 VA 100.00% 100 VA Total Conn. Current: 205 A

    Motor 26065 VA 100.00% 26065 VA Total Est. Demand: 73921 VA

    Lighting 6449 VA 125.00% 8061 VA Total Conn. Load: 73939 VA

    HVAC 2000 VA 100.00% 2000 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 203 A 207 A 207 A

    Total... 24336 VA 24782 VA 24824 VA

    83 Garage Door Opener 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.8 kVA -- -- -- -- -- 84

    81 Garage Door Opener 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.8 kVA -- -- -- -- -- 82

    79 Heat Trace (2) 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 1-1/4" 4#3, 1#8G 3 100 A Panel E2RR 80

    77 Roof L5-20 Receptacle (1) 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Lighting Bays 78

    75 Roof L5-20 Receptacle (1) 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Lighting Bays 76

    73 DH-1 15 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Lighting Bays 74

    71 -- -- -- -- -- 1.0 kVA 1.0 kVA -- -- -- -- -- 72

    69 AF-9 15 A 2 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 15 A AF-10 70

    67 -- -- -- -- -- 1.0 kVA 1.0 kVA -- -- -- -- -- 68

    65 AF-7 15 A 2 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 15 A AF-8 66

    63 -- -- -- -- -- 1.0 kVA 1.0 kVA -- -- -- -- -- 64

    61 AF-5 15 A 2 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 15 A AF-6 62

    59 -- -- -- -- -- 1.0 kVA 1.0 kVA -- -- -- -- -- 60

    57 AF-3 15 A 2 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 15 A AF-4 58

    55 -- -- -- -- -- 1.0 kVA 1.0 kVA -- -- -- -- -- 56

    53 AF-1 15 A 2 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 15 A AF-2 54

    51 Wiremold Dirty Shop 20 A 1 2#12, 1#12G 3/4" 0.9 kVA 0.2 kVA 3/4" 2#12, 1#12G 1 20 A Roof Recept 52

    49 Recepts Utility/Dirty 20 A 1 2#12, 1#12G 3/4" 0.9 kVA 2.5 kVA -- -- -- -- 50

    47 Recepts Training Veranda 20 A 1 2#12, 1#12G 3/4" 0.4 kVA 2.5 kVA 3/4" 3#10, 1#10G 2 30 A Electric Dryer 48

    45 Recepts Pipe Gear 20 A 1 2#12, 1#12G 3/4" 0.7 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Pipe Gear 46

    43 Recepts Pipe Gear 20 A 1 2#10, 1#10G 3/4" 0.7 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Pipe Gear 44

    41 Lighting Wash Bay 20 A 1 2#12, 1#12G 3/4" 0.6 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Lighting Utility Area 42

    39 Ltg - App Bay Red Lts 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.7 kVA 3/4" 2#12, 1#12G 1 20 A Lighting Storage Area 40

    37 Ltg - Apparatus Bay East 20 A 1 2#12, 1#12G 3/4" 0.4 kVA 0.4 kVA 3/4" 2#12, 1#12G 1 20 A Ltg - Apparatus Bay West 38

    35 Drop Cord 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.1 kVA 3/4" 2#12, 1#12G 1 20 A FACP 36

    33 Drop Cord 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Drop Cord 34

    31 Drop Cord 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Air Compressor 32

    29 Drop Cord 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Drop Cord 30

    27 Drop Cord 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Drop Cord 28

    25 DF-5 THRU 8 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Drop Cord 26

    23 DF-1 THRU 4 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.3 kVA -- -- -- -- -- 24

    21 WH-2 20 A 1 2#12, 1#12G 3/4" 0.6 kVA 0.3 kVA 3/4" 2#12, 1#12G 2 15 A FCU-17,18 & BS-1 22

    19 WH-1 20 A 1 2#12, 1#12G 3/4" 0.6 kVA 1.0 kVA -- -- -- -- -- 20

    17 PMP-1 15 A 1 2#12, 1#12G 3/4" 0.1 kVA 1.0 kVA 3/4" 2#12, 1#12G 2 20 A CP-1 18

    15 UH-1,2,3,4,5 15 A 1 2#12, 1#12G 3/4" 0.6 kVA 1.2 kVA 3/4" 2#12, 1#12G 1 20 A B-1 16

    13 Recepts 230 20 A 1 2#12, 1#12G 3/4" 0.9 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Recepts 230 14

    11 Hoist Wash Bay 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.0 kVA 1 20 A Spare 12

    9 Recepts Wash Bay 20 A 1 2#12, 1#12G 3/4" 1.4 kVA 0.0 kVA 1 20 A Spare 10

    7 Washer 128 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 0.0 kVA 1 20 A Spare 8

    5 Washer 128 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 1.2 kVA 3/4" 2#10, 1#10G 1 15 A EF-2 6

    3 Drop Cord 20 A 1 2#10, 1#10G 3/4" 1.0 kVA 1.3 kVA 3/4" 2#10, 1#10G 1 20 A General Recepts 4

    1 Roof Recepts 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Drop Cord 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating:

    Mounting: Surface Wires: 4 Mains Rating: 250 A

    Supply From: EDP Phases: 3 Mains Type: MLO

    Location: ELEC 227 Volts: 120/208 Wye A.I.C. Rating: 22K

    Branch Panel: E2R

    Revision Schedule

    # Date Revision

  • These drawings are the property of the Architect. Bignell Watkins Hasser Architects P.C. Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by fullest extent of the law. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and this office must be notified of any variation from the dimensions and conditions shown by these drawings.

    Client:

    Location:

    Project:

    Drawn by:

    Project No: Date:

    Professional CertificationI hereby certify that these documents were prepared or approved by me, and that I am a duly licensed engineer under the laws of the State of Maryland.License No. 45534 Expiration Date 06-03-20

    ONE PARK PLACE SUITE 250 ANNAPOLIS, MARYLAND 21401

    Maryland:MD Fax:

    (301) 261-8228(410) 224-4443

    Baltimore: (410) 841-6595Annapolis: (410) 224-2727

    Website www.bigwaha.com

    ARCHITECTCONTACT: GREG GILBERT, RA

    MICHAEL MATULA

    STRUCTURAL ENGINEERCENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT: RICHARD BEARD

    MECHANICAL, ELECTRICAL& PLUMBING ENGINEER

    CENTURY ENGINEERING

    10710 GILROY ROADHUNT VALLEY, MD 21031

    TEL: (443) 589-2400CONTACT:

    ANDREW JUN - MECHANICAL/PLUMBINGMATT STEINER - ELECTRICAL

    BAY ENGINEERING INC.

    2661 RIVA ROAD ANNAPOLIS, MD 21401

    TEL: (410) 897-9290CONTACT: NELSON AROCHO

    ANNIE LUTTRELL

    CIVIL ENGINEER

    CALVERT COUNTRY - GENERALSERVICES DIVISION

    450 SOLOMONS ISLAND ROADPRINCE FREDERICK, MD 20678

    PRINCE FREDERICK VOLUNTEERFIRE STATION

    E8.2

    ELECTRICALSCHEDULES

    17032 1/25/19

    BID /CONSTRUCTION

    SP

    MECHANICAL EQUIPMENT CONNECTION SCHEDULE

    DESIGNATION VOLTAGE PH LOAD FDS POLES FDS Size FDS FUSE (A) STARTER CIRCUIT # PANEL COMMENTS

    AC-1 208 V 14,16 P2R

    AF-1 208 V 1 1.9 kVA 2 30 15 53,55 E2R

    AF-2 208 V 1 1.9 kVA 2 30 15 54,56 E2R

    AF-3 208 V 1 1.9 kVA 2 30 15 57,59 E2R

    AF-4 208 V 1 1.9 kVA 2 30 15 58,60 E2R

    AF-5 208 V 1 1.9 kVA 2 30 15 61,63 E2R

    AF-6 208 V 1 1.9 kVA 2 30 15 62,64 E2R

    AF-7 208 V 1 1.9 kVA 2 30 15 65,67 E2R

    AF-8 208 V 1 1.9 kVA 2 30 15 66,68 E2R

    AF-9 208 V 1 1.9 kVA 2 30 15 69,71 E2R

    AF-10 208 V 1 1.9 kVA 2 30 15 70,72 E2R

    B-1 120 V 1 1.2 kVA TMS 16 E2R

    BF-1 120 V 1 0.1 kVA TMS 21 P2R

    BS-1 208 V 1 0.1 kVA TMS 22,24 E2R

    BS-2 208 V 1 0.1 kVA TMS 43,45 E2L

    BS-3 208 V 1 0.1 kVA TMS 42,44 E2L

    BS-4 208 V 1 0.1 kVA TMS 43,45 E2L

    BS-5 208 V 1 0.1 kVA TMS 43,45 E2L

    BS-6 208 V 1 0.1 kVA TMS 55,57 E2L

    BS-7 208 V 1 0.1 kVA TMS 55,57 E2L

    BS-8 208 V 1 0.1 kVA TMS 54,56 E2L

    BS-9 208 V 1 0.1 kVA TMS 54,56 E2L

    CP-1 208 V 1 1.9 kVA 2 30 NF 18,20 E2R

    CP-2 208 V 1 1.9 kVA 2 30 NF 2,4 E2RR

    CU-1 208 V 1 3.5 kVA 2 30 NF 14,16 P2R

    DF-2 120 V 1 0.1 kVA TMS 23 E2R

    DF-3 120 V 1 0.1 kVA TMS 23 E2R

    DF-4 120 V 1 0.1 kVA TMS 23 E2R

    DF-5 120 V 1 0.1 kVA TMS 25 E2R

    DF-6 120 V 1 0.1 kVA TMS 25 E2R

    DF-7 120 V 1 0.1 kVA TMS 25 E2R

    DF-8 120 V 1 0.1 kVA TMS 25 E2R

    DH-1 120 V 1 0.8 kVA 73 E2R

    DOAS-1 208 V 3 24.8 kVA 3 100 NF 2,4,6 EDP

    EF-1 120 V 1 1 E2RR

    EF-2 120 V 1 6 E2R

    ESP-1 208 V 3 1.7 kVA 3 30 15 70,72,74 E2L

    EWH-1 208 V 1 1.5 kVA 63,65 E2L

    EWH-2 208 V 1 1.5 kVA 62,64 E2L

    EWH-3 208 V 1 1.5 kVA 35,37 P2L

    FCU-1 208 V 1 0.3 kVA TMS 50,52 E2L

    FCU-2 208 V 1 0.7 kVA TMS 55,57 E2L

    FCU-3 208 V 1 0.2 kVA TMS 50,52 E2L

    FCU-4 208 V 1 0.2 kVA TMS 50,52 E2L

    FCU-5 208 V 1 0.2 kVA TMS 51,53 E2L

    FCU-6 208 V 1 0.2 kVA TMS 51,53 E2L

    FCU-7 208 V 1 0.2 kVA TMS 51,53 E2L

    FCU-8A 208 V 1 0.2 kVA TMS 51,53 E2L

    FCU-8B 208 V 1 0.2 kVA TMS 51,53 E2L

    FCU-9 208 V 1 0.2 kVA TMS 54,56 E2L

    FCU-10 208 V 1 0.2 kVA TMS 54,56 E2L

    FCU-11 208 V 1 0.1 kVA TMS 59,61 E2L

    FCU-12 208 V 1 0.1 kVA TMS 59,61 E2L

    FCU-13 208 V 1 0.3 kVA TMS 54,56 E2L

    FCU-14 208 V 1 0.2 kVA TMS 58,60 E2L

    FCU-15 208 V 1 0.4 kVA TMS 58,60 E2L

    FCU-16 208 V 1 0.3 kVA TMS 55,57 E2L

    FCU-17 208 V 1 0.3 kVA TMS 22,24 E2R

    FCU-18 208 V 1 0.1 kVA TMS 22,24 E2R

    FCU-19 208 V 1 0.6 kVA TMS 43,45 E2L

    FCU-20 208 V 1 0.4 kVA TMS 42,44 E2L

    FCU-21 208 V 1 0.1 kVA TMS 43,45 E2L

    FCU-22 208 V 1 0.2 kVA TMS 42,44 E2L

    FCU-23 208 V 1 0.2 kVA TMS 42,44 E2L

    FCU-24 208 V 1 0.2 kVA TMS 47,49 E2L

    FCU-25 208 V 1 0.2 kVA TMS 47,49 E2L

    FCU-26 208 V 1 0.2 kVA TMS 47,49 E2L

    FCU-27 208 V 1 0.3 kVA TMS 46,48 E2L

    FCU-28 208 V 1 0.2 kVA TMS 76,78 E2L

    FCU-29 208 V 1 0.2 kVA TMS 76,78 E2L

    FCU-30 208 V 1 0.2 kVA TMS 76,78 E2L

    FCU-31 208 V 1 0.2 kVA TMS 76,78 E2L

    FCU-32 208 V 1 0.1 kVA TMS 42,44 E2L

    FCU-33 208 V 1 0.2 kVA TMS 47,49 E2L

    FCU-34 208 V 1 0.2 kVA TMS 47,49 E2L

    FCU-35 208 V 1 0.2 kVA TMS 54,56 E2L

    FCU-36 208 V 1 0.2 kVA TMS 42,44 E2L

    GEF 208 V 3 11.6 kVA 3 60 NF 13,15,17 EDP

    HRU-1 208 V 3 13.8 kVA 3 60 50 7,9,11 EDP

    HRU-1 (CKT 2) 208 V 3 16.8 kVA 3 100 70 8,10,12 EDP

    KEF-1 208 V 3 1.7 kVA 00 36,38,40 P2L PROVIDE COMBINATION STARTER/DISCONNECT SWITCH,NEMA 3R ENCL

    MUA-1 208 V 3 3.2 kVA 00 15,17,19 P2R PROVIDE COMBINATION STARTER/DISCONNECT SWITCH,NEMA 3R ENCL

    PMP-1 120 V 1 0.1 kVA TMS 17 E2R

    RTU-1 208 V 3 43.9 kVA 3 200 175 1,3,5 MDP

    UH-1 120 V 1 0.1 kVA TMS 15 E2R

    UH-2 120 V 1 0.1 kVA TMS 15 E2R

    UH-3 120 V 1 0.1 kVA TMS 15 E2R

    UH-4 120 V 1 0.1 kVA TMS 15 E2R

    UH-5 120 V 1 0.1 kVA TMS 15 E2R

    WH-1 120 V 1 0.6 kVA TOGGLE 19 E2R

    WH-2 120 V 1 0.6 kVA TOGGLE 21 E2R

    Notes:

    Electric Dryer 5000 VA 100.00% 5000 VA

    Receptacle 4940 VA 100.00% 4940 VA Total Est. Demand Current: 136 A

    Power 32000 VA 100.00% 32000 VA Total Conn. Current: 134 A

    Motor 600 VA 100.00% 600 VA Total Est. Demand: 48990 VA

    Lighting 2600 VA 125.00% 3250 VA Total Conn. Load: 48340 VA

    HVAC 3200 VA 100.00% 3200 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 131 A 140 A 133 A

    Total... 15677 VA 16747 VA 15917 VA

    53 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 54

    51 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 52

    49 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 50

    47 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 48

    45 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 46

    43 0.0 kVA 1 20 A Spare 44

    41 42

    39 0.6 kVA -- -- -- -- -- 40

    37 -- -- -- -- 0.8 kVA 0.6 kVA -- -- -- -- -- 38

    35 EWH-3 20 A 2 2#12, 1#12G 3/4" 0.8 kVA 0.6 kVA 3/4" 3#12, 1#12G 3 15 A KEF-1 36

    33 Range Hood Control Pnl 20 A 1 2#12, 1#12G 3/4" 0.2 kVA 0.9 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Soffit Recepts 34

    31 Door Operators 20 A 1 2#12, 1#12G 3/4" 0.4 kVA 2.5 kVA -- -- -- -- -- 32

    29 Washer 224 20 A 1 2#12, 1#12G 3/4" 1.5 kVA 2.5 kVA 3/4" 3#10, 1#10G 2 30 A Dryer 224 30

    27 -- -- -- -- -- 4.0 kVA 1.9 kVA -- -- -- -- -- 28

    25 Range 50 A 2 3#8, 1#10G 3/4" 4.0 kVA 1.9 kVA -- -- -- -- -- 26

    23 Vending Machine 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.9 kVA 3/4" 3#10, 1#10G 3 25 A Dishwasher 24

    21 Soda Machine 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Soda Machine 22

    19 Hand Dryer 121 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Hand Dryer 122 20

    17 Hand Dryer 204 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Hand Dryer 205 18

    15 Recepts Museum 20 A 1 2#12, 1#12G 3/4" 1.1 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Copier 16

    13 Elev Sump Controller 20 A 1 2#12, 1#12G 3/4" 0.6 kVA 0.2 kVA 3/4" 2#12, 1#12G 1 20 A EMR Recept 14

    11 -- -- -- -- 4.0 kVA 0.6 kVA 3/4" 2#12, 1#12G 1 20 A Elev Shaft Ltg/Rec 12

    9 Oven 50 A 2 3#8, 1#10G 3/4" 4.0 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 15 A Elev Cab Ltg/Pwr 10

    7 Backlit Signage 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 1.3 kVA 3/4" 2#12, 1#12G 1 20 A Recepts Fitness/Hall 8

    5 Exterior Recept 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 6

    3 Exterior Recept 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 4

    1 Backlit Signage 20 A 1 2#12, 1#12G 3/4" 0.5 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Backlit Signage 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating:

    Mounting: Surface Wires: 4 Mains Rating: 250 A

    Supply From: MDP Phases: 3 Mains Type: MLO

    Location: ELEC 222 Volts: 120/208 Wye A.I.C. Rating: 10K

    Branch Panel: P2L

    Notes:

    Electric Dryer 5000 VA 100.00% 5000 VA

    Receptacle 2440 VA 100.00% 2440 VA Total Est. Demand Current: 79 A

    Power 14200 VA 100.00% 14200 VA Total Conn. Current: 79 A

    Motor 130 VA 100.00% 130 VA Total Est. Demand: 28641 VA

    Lighting 500 VA 125.00% 625 VA Total Conn. Load: 28517 VA

    HVAC 6548 VA 100.00% 6548 VA

    Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

    Total... 74 A 86 A 79 A

    Total... 8936 VA 10237 VA 9387 VA

    41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42

    39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40

    37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38

    35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36

    33 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 34

    31 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 32

    29 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 30

    27 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 28

    25 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 26

    23 Spare 20 A 1 0.0 kVA 2.5 kVA -- -- -- -- -- 24

    21 BF-1 15 A 1 2#12, 1#12G 3/4" 0.1 kVA 2.5 kVA 3/4" 3#10, 1#10G 2 30 A Dryer 128 22

    19 -- -- -- -- -- 1.1 kVA 2.5 kVA -- -- -- -- -- 20

    17 -- -- -- -- -- 1.1 kVA 2.5 kVA 3/4" 3#10, 1#10G 2 30 A Steam Cleaner 18

    15 MUA-1 15 A 3 3#12, 1#12G 3/4" 1.1 kVA 1.9 kVA -- -- -- -- -- 16

    13 Exterior Soffit Recepts 20 A 1 2#12, 1#12G 3/4" 0.7 kVA 1.9 kVA 3/4" 2#12, 1#12G 2 20 A CU-1 14

    11 Site Pole Recepts 20 A 1 2#8, 1#8G 3/4" 0.7 kVA 1.0 kVA 3/4" 2#12, 1#12G 1 20 A Recept: Drill Press 12

    9 Exterior Recepts 20 A 1 2#12, 1#12G 3/4" 2.4 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 10

    7 Exterior Recept 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 8

    5 Exterior Recept 20 A 1 2#12, 1#12G 3/4" 0.8 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 6

    3 Future Site Equipment 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.8 kVA 3/4" 2#12, 1#12G 1 20 A Exterior Recept 4

    1 Future Site Equipment 20 A 1 2#12, 1#12G 3/4" 1.0 kVA 0.5 kVA 3/4" 2#12, 1#12G 1 20 A Backlit Signage 2

    CKT Circuit Description Notes Trip Poles Wire Size C. A B C C. Wire Size Poles Trip Notes Circuit Description CKT

    Notes:

    Enclosure: Type 1 MCB Rating:

    Mounting: Surface Wires: 4 Mains Rating: 250 A

    Supply From: MDP Phases: 3 Mains Type: MLO

    Location: ELEC 227 Volts: 120/208 Wye A.I.C. Rating: 22K

    Branch Panel: P2R

    (1) PROVIDE GFCI CIRCUIT BREAKER.