41
Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Upload: landon-peevey

Post on 15-Jan-2016

253 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

EE4503Electrical Systems Design

Raceways

1

Page 2: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Topics

• Introduction to Raceways

• Conduits

• Conduit Installations

• Wireways, Auxiliary Gutters, Cable Trays

• Fittings

2

Page 3: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Raceways

• Damage e.g. physical, chemical

• Human Contact

• Easy Wiring e.g. wiring, maintenance

• Grounding for Metal Conduit

• Limit the scope of damage e.g. fire, short circuit

3

Page 4: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – RMC, IMC, EMT

Catalog of Panasoics

4

Page 5: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – RMCRigid Metal Conduit

• Strongest conduit (except concrete :p)

• (Usually) Galvanized

• Usage: All weather, all terrain

• Standard: ” – 6” (15mm – 150mm) and 3m length

5

Page 6: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – IMCIntermediate Metal Conduit

• Thinner than RMC

• (Usually) Galvanized

• Usage: All weather, all terrain

• Standard: ” – 4” (15mm – 100mm) and 3m in length

6

Page 7: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – EMTElectrical Metallic Tubing

• Thinner than IMC & RMC

• Not allow to have thread

• Usage: Only in building (not under ground, not for high voltage)

• Standard: ” – 4” (15mm – 100mm) and 3m in length

7

Page 8: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – FMC

http://www.delikon.com/brass.htm

8

Page 9: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – FMCFlexible Metal Conduit

• Metal conduit with the high flexibility

• Usage: Vibration or Need Bending

• Standard: ” – 3” (15mm – 80mm)

• Installation: Need support every 1.5m and 0.3m

(in case of termination point / junction box)

9

Page 10: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – RNCRigid Nonmetallic Conduit

• Built from nonmetallic material: e.g. PVC

• Disadvantage: Not as strong as metal and limit

temperature usage

• Advantage: Sustain to erosion, humidity, impact

• Usage: Exposed, Conceal, Wet & Himid or underground (usually using “duct bank”)

10

Page 11: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – RNCDuct Bank

http://www.chana.egat.co.th/newweb/gallery/?level=picture&id=28http://www.iowaconcrete.com/node/707

11

Page 12: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits – Comparison

http://www.mc2-ice.com/services/estref/popular_conversion_files/electrical/conduit_weight.html

12

Page 13: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation: RMC, IMC

http://www.mikeholt.com/instructor2/img/product/pdf/1259687476sample.pdf

13

Wet Location: accessories needed to be specified as

“Raintight” or “Wet locations”

Page 14: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation: RMC, IMC

Electrical Systems Design: ประสิ�ทธิ์�� พิ�ทยพิ�ฒน์�14

Cinder Fill: In corrosive area (e.g. under

permanently moist), required at least 2” concrete

Page 15: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation: RMC, IMC

http://www.electrix.co.uk/view_product_options.php?id=1117http://ecmweb.com/site-files/ecmweb.com/files/archive/ecmweb.com/images/112ecmCBfig1.jpg

15

Box: Where conduit reaching the box, “bushing” is

required to protect the cable’s

Page 16: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation: RMC, IMC

Electrical Systems Design: ประสิ�ทธิ์�� พิ�ทยพิ�ฒน์�http://www.tpub.com/ceb/71.htm

16

Bend: Number of bends in one run should <= 360o

Page 17: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation - Supports

Electrical Systems Design: ประสิ�ทธิ์�� พิ�ทยพิ�ฒน์�http://www.ci.oceanside.ca.us/civica/filebank/blobdload.asp?BlobID=22230

17

Page 18: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation: RMC, IMC

Splices and Taps: only inside the box

18

http://www.diyadvice.com/diy/electrical/fans-heat/whole-house-ventilating-fan/http://www.familyhandyman.com/DIY-Projects/Lighting/Kitchen-Lighting/how-to-install-under-cabinet-lighting-in-your-kitchen/View-All

Page 19: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation - # of Cables

• Need space inside conduit:

– Heat Ventilation

– Cable’s insulator will not be damaged.

19

http://www.simpullsolutions.com/documents/SIMpullTHHNInstallationandApplicationGuide8-15-07.pdf

Page 20: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation - # of Cablestable

20

http://www.telepart.net/ตารางการต�ดต��งสิายไฟใน์ท�อWire-Conduit-Table.html

Page 21: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Conduits Installation - # of Cablescalculation

21

Calculate directly from the cable’s outer diameter () and conduit’s inner diameter () and is the number of cables.

Page 22: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Wireways

22

http://www.indochinaengineering.co.th/product.php?id_product=30

Page 23: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Wireways• Raceways are folded from sheet metal.

• General usage in open area. If outside building, specify “Raintight”

• Not use when risk of severe physical damage.

• Height: 50, 75, 100, 150, 200 mm

• Width: 50, 75, 100, 150, 200, 250, 300 mm23

Page 24: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Wireways

• Use current rated for the metal conduit.

• Use reduction factor, if > 30 cables.

• Need supports for every 1.5m.

• Cannot use through the wall or floor.

• Cannot use as grounding cable.

• Use no more than 20% fill.24

Page 25: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Auxiliary Gutters

• Similar to wireways

• Collect the cable before distribute.

25

http://www.contractortalk.com/f32/some-recent-work-34277/

Page 26: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays

26

http://www.indochinaengineering.co.th/product.php?id_product=32

Page 27: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays• Cable Tray is not Raceways, but is

commonly used in industry to support cable.

• Cheap and easy to use.

• Only for specific cable types, e.g. multi-core cables

27

Page 28: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays – Ladder TypeFor heavy-duty power distribution

28

http://www.shreemahalaxmisteel.com/cable-trays.htmlhttp://www.ezziengineering.com/images/Cable_Tray_Catalogue.pdf

Page 29: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays – Perforated TypeFor power cables, small cables and control cables

29

http://www.shreemahalaxmisteel.com/cable-trays.htmlhttp://www.ezziengineering.com/images/Cable_Tray_Catalogue.pdf

Page 30: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays – Solid Bottom TypeFor small cables.

30

http://www.ezziengineering.com/images/Cable_Tray_Catalogue.pdf

Page 31: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Cable Trays – Comparison

http://www.cooperindustries.com/content/dam/public/bline/Resources/Library/catalogs/cable_tray_systems/all_products/CTManual.pdf 31

Page 32: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings

• Accessories to be used with race way.

• Purpose

– To firmly hang the raceway

– To smoothly change the direction of raceway

– To easily pull the cable into the raceway

– To properly splice the cables

32

Page 33: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings - Boxes

33

• Termination point (switch, receptacle) or Stop point (splice, tap) for the wiring system.

• Metal or non-metal.

• Sizing is based on the required space.

• Have no hole for the object larger than 7.5 mm in diameter to pass thru.

Page 34: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings - Boxes

http://www.topaz-usa.com/catalogs/electrical_fittings_catalog.pdf

34

Page 35: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Pull Boxes

http://ecmweb.com/code-basics/sizing-junction-boxes

35

Page 36: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Pull Boxesstraight pulls

http://ecmweb.com/code-basics/sizing-junction-boxes

36

The horizontal dimension (A) is 8 times of the largest raceway size.

Page 37: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Pull Boxesangle pulls

http://ecmweb.com/code-basics/sizing-junction-boxes

37

The distance between raceways (C) is 6 times of the diameters of the raceways.

Page 38: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Other AccessoriesConnectors

http://www.topaz-usa.com/catalogs/electrical_fittings_catalog.pdfhttp://numthaveerung.co.th/pdf/Steel%20Conduit-Accessories%20Fitting.pdf

38

• Steel Coupling

• Compression

• Set Screw

• Rain Tight

Page 39: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Other AccessoriesBushing

http://www.topaz-usa.com/catalogs/electrical_fittings_catalog.pdf

39

• Metal

• Non-metal

• Grouding

Page 40: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

Fittings – Other AccessoriesElbow & Strap

http://www.topaz-usa.com/catalogs/electrical_fittings_catalog.pdf

40

• Elbow

• Strap

Page 41: Assumption University Thailand EE4503 Electrical Systems Design Raceways 1

Assumption University Thailand

• Electrical Systems Design: ประสิ�ทธิ์�� พิ�ทยพิ�ฒน์�

Reference

41