Level 1, 50 Subiaco Square Road, Subiaco, WA 6008 P.O. Box 243, Subiaco, WA 6904 Phone: (08) 9380 3100 Fax: (08) 9380 4606 177 Spencer Street, Bunbury, WA 6230 P.O. Box 287, Bunbury, WA 6231 Phone: (08) 9792 4797 Fax: (08) 9792 4708 Email: [email protected] Web: www.strategen.com.au ABN: 32 056 190 419 To: Preston O'Keefe Date: 22 August 2018 Company: Cedar Woods Properties Limited Project No: CED18426.01 Email: [email protected] Inquiries: Zac Cockerill AS 3959 Bushfire Attack Level (BAL) Compliance Report Stage 6 Ariella Estate, Brabham Site Details Address: 47 residential lots within Stage 6 Ariella Estate Suburb: Brabham State: Western Australia Local Government Area: City of Swan Description of building works: Residential development (Class 1, 2 or 3 buildings with associated Class 10a buildings) Report details Report/Job number: CED18426.01 Report reference: CED18426_01 M001 Rev A Assessment date: 26/10/17 and 27/07/18 Report date: 22 August 2018 Endorsement/Review Zac Cockerill BPAD Level 2: 37803 Introduction This Bushfire Attack Level (BAL) compliance report has been prepared for 47 residential lots within Stage 6 Ariella Estate, Brabham (hereon referred to as the project area), located in the City of Swan. Lots within Stage 6 are subject to WAPC subdivision approval (WAPC Ref. 150306). This report provides a post-subdivisional works update of the BAL ratings for individual lots within the project area and has been prepared for the benefit of the developer, future lot purchasers and decision- makers. BAL certificates for each individual lot (contained in Appendix 1) have been prepared based on the final site compliance check and are appended to this report for use at the building permit stage. The BAL assessment outlined in this report is the most up to date assessment relating to the project area and therefore supersedes any previous Strategen BAL assessments undertaken within the project area, including those documented in previously approved Bushfire Management Plans (BMPs) to accompany both the original Ariella Private Estate subdivision (2015) and revised subdivision for Stages 5–7 (2018). The approach for preparation of this BAL compliance report is consistent with Section 4.2 and Appendix 3 of Guidelines for Planning in Bushfire Prone Areas (the Guidelines). The BAL compliance assessment has been completed by a Level 2 accredited Bushfire Planning and Design practitioner (Zac Cockerill, BPAD37803) in accordance with Method 1 of AS 3959–2009 Construction of Buildings in Bushfire-prone Areas (AS 3959) and results are consistent with on-ground conditions observed at the time of inspection on 26 October 2017 and reassessment on 27 July 2018. Should subdivision design or the classified vegetation extent be further modified prior to building construction, then an updated BAL assessment for the affected lots may need to be undertaken to account for these changes.

Upload: others

Post on 15-Oct-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

Level 1, 50 Subiaco Square Road, Subiaco, WA 6008 P.O. Box 243, Subiaco, WA 6904 Phone: (08) 9380 3100 Fax: (08) 9380 4606 177 Spencer Street, Bunbury, WA 6230 P.O. Box 287, Bunbury, WA 6231 Phone: (08) 9792 4797 Fax: (08) 9792 4708

Email: [email protected] Web: www.strategen.com.au ABN: 32 056 190 419

To: Preston O'Keefe Date: 22 August 2018

Company: Cedar Woods Properties Limited Project No: CED18426.01

Email: [email protected] Inquiries: Zac Cockerill

AS 3959 Bushfire Attack Level (BAL) Compliance Report Stage 6 Ariella Estate, Brabham

Site Details

Address: 47 residential lots within Stage 6 Ariella Estate

Suburb: Brabham State: Western AustraliaLocal Government Area: City of SwanDescription of building works: Residential development (Class 1, 2 or 3 buildings with associated Class 10a

buildings)

Report details

Report/Job number: CED18426.01 Report reference: CED18426_01 M001 Rev AAssessment date: 26/10/17 and 27/07/18 Report date: 22 August 2018 Endorsement/Review Zac Cockerill BPAD Level 2: 37803

Introduction

This Bushfire Attack Level (BAL) compliance report has been prepared for 47 residential lots within Stage 6 Ariella Estate, Brabham (hereon referred to as the project area), located in the City of Swan. Lots within Stage 6 are subject to WAPC subdivision approval (WAPC Ref. 150306).

This report provides a post-subdivisional works update of the BAL ratings for individual lots within the project area and has been prepared for the benefit of the developer, future lot purchasers and decision-makers. BAL certificates for each individual lot (contained in Appendix 1) have been prepared based on the final site compliance check and are appended to this report for use at the building permit stage.

The BAL assessment outlined in this report is the most up to date assessment relating to the project area and therefore supersedes any previous Strategen BAL assessments undertaken within the project area, including those documented in previously approved Bushfire Management Plans (BMPs) to accompany both the original Ariella Private Estate subdivision (2015) and revised subdivision for Stages 5–7 (2018).

The approach for preparation of this BAL compliance report is consistent with Section 4.2 and Appendix 3 of Guidelines for Planning in Bushfire Prone Areas (the Guidelines).

The BAL compliance assessment has been completed by a Level 2 accredited Bushfire Planning and Design practitioner (Zac Cockerill, BPAD37803) in accordance with Method 1 of AS 3959–2009 Construction of Buildings in Bushfire-prone Areas (AS 3959) and results are consistent with on-ground conditions observed at the time of inspection on 26 October 2017 and reassessment on 27 July 2018.

Should subdivision design or the classified vegetation extent be further modified prior to building construction, then an updated BAL assessment for the affected lots may need to be undertaken to account for these changes.

Page 2: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 2

Site assessment and site plan

The assessment of this site/development was undertaken initially on 26 October 2017, then reassessed on 27 July 2018 by a BPAD Accredited Practitioner for the purpose of determining the Bushfire Attack Level in accordance with AS 3959 - 2009 (Simplified Procedure [Method 1]).

A site plan and site assessment results are depicted in Figure 1.

Vegetation classification

All vegetation within 100 m of the site/development was classified in accordance with Clause 2.2.3.2 of AS 3959-2009 and the Visual Guide for Bushfire Risk Assessment in Western Australia. Each distinguishable vegetation class with the potential to determine the Bushfire Attack Level is identified below in Table 1 and Figure 1.

Future rehabilitation in the Resource Enhancement Wetland (REW) and adjacent buffer to the south of the project area will result in the following vegetation classifications as per the approved landscape plan:

• rehabilitation consistent with a Class B woodland status within the REW

• rehabilitation consistent with a Class C shrubland status within the REW buffer.

Subdivisional works have resulted in the following exclusions within and adjacent to the project area: • the project area is in a cleared, managed low fuel state and is excluded from classification under

Clauses 2.2.3.2 (e) and (f)

• adjacent Stages 5 and 7 to the west are in a cleared, managed low fuel state and are excluded from classification under Clauses 2.2.3.2 (e) and (f)

• built stages of Ariella Estate to the north are in a cleared, managed low fuel state and are excluded from classification under Clauses 2.2.3.2 (e) and (f)

• adjacent development south of Woollcott Avenue (Whiteman Edge) is in a cleared, managed low fuel state and is excluded from classification under Clauses 2.2.3.2 (e) and (f)

• adjacent development to the east (Flamewood Estate) is in a cleared, managed low fuel state and is excluded from classification under Clauses 2.2.3.2 (e) and (f)

• the adjacent east Dampier to Bunbury Natural Gas Pipeline (DBNGP) corridor is in a cleared, managed low fuel state and is excluded from classification under Clauses 2.2.3.2 (e) and (f) in accordance with approved landscape plans.

Page 3: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

Figure 1: BAL compliance assessment: Stage 6 Ariella Estate

Coordinate System: GDA 1994 MGA Zone 50

Date: 22/08/2018

at A41:3,218Scale

367 465 476

490

491 374

308

309

364

310473

472 474

495

475

424

423

492

415

493

478

477

467

479468

470

471

469

466

494

369

409368

372

373

371

370421412

422

414

413

410

418

419

411 420

!(

!(

!(

!(

!(

!( !(

!(!(

!(

Arafura Wy

Flannigan St

Bye

nu

p L

n

Rolls

ton

St

Wo

ols

he

d R

d

Bro

mfie

ld A

v

Gu

nb

ow

er

Rd

Bu

ckla

nd

Rd

Watervalley Blv

Ambersun Av

9

3

2

41

6

7

5

8

10

Woollcott Av

402500

402500

402600

402600

402700

402700

402800

402800

402900

402900

403000

403000

403100

403100

403200

403200

403300

403300

64

78

30

0

64

78

30

0

64

78

400

64

78

400

64

78

50

0

64

78

50

0

64

78

60

0

64

78

60

0

64

78

70

0

64

78

70

0

0 50 100m

Legend

!(

Photo point and direction

Project area

Development layout

Surrounding subdivisions

100m assessment area

150m assessment area

Cadastre

Vegetation class

Plot 1: Class B woodland, 0-5degrees down-slope

Plot 2: Class C Shrubland, 0-5degrees down-slope

Excluded under Clause 2.2.3.2(e) and (f)

BAL contours

BAL FZ

BAL 40

BAL 29

BAL 19

BAL 12.5

BAL Low

© 2017. Whilst every care has been taken to prepare this map, Strategen & CED makes no representations or warranties about its accuracy, reliability, completeness or suitability for any particular purpose and cannot accept liability and responsibility of any kind (whether in contract, tort or otherwise) for any expenses, losses, damagesand/or costs (including indirect or consequential damage) which are or may be incurred by any party as a result of the map being inaccurate, incomplete or unsuitable in any way and for any reason.

Q:\Consult\2018\CED\CED18426\01_GIS_documents\CED18426_G001_RevB.mxd

Data source: Nearmap: Aerial image, flown 06/2018. Landgate: Cadastre, 11/2017. Client: Development layout, 08/2018. Created by: jcrute

±

Whiteman Edge Estate

Flamewood Estate

DB

NG

P c

orr

ido

r

REW

REW Buffer

Page 4: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 4

Table 1: Vegetation classification

Plot 1: Class B woodland within REW (rehabilitation also to be consistent with Class B woodland)Photo 1: Trees 5-20 m in height, grassy understorey, lacking a shrubby middle layer

Plot 1: Class B woodland within REW (rehabilitation also to be consistent with Class B woodland) Photo 2: Trees 5-20 m in height, grassy understorey, lacking a shrubby middle layer

Page 5: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 5

Plot 2: REW buffer to be rehabilitated to Class C shrubland (Class B woodland REW in background)Photo 3: Currently weed regrowth, to be rehabilitated with shrubland vegetation as per landscape plan

Plot 2: REW buffer to be rehabilitated to Class C shrubland (Class B woodland REW right of shot)Photo 4: Currently cleared, to be rehabilitated with shrubland vegetation as per landscape plan

Page 6: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 6

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f])Photo 5: DBNGP corridor currently cleared, to be landscaped to non-vegetated and low threat state

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f]) Photo 6: DBNGP corridor currently cleared, to be landscaped to non-vegetated and low threat state

(Flamewood Estate cleared land in background)

Page 7: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 7

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f])Photo 7: DBNGP corridor currently cleared, to be landscaped to non-vegetated and low threat state

(Flamewood Estate cleared land in background)

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f]) Photo 8: Cleared land within Stage 5 Ariella Estate

Page 8: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 8

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f]) Photo 9: Cleared land within Stage 5 Ariella Estate

N/A Excluded – Non-vegetated & Low threat (Clauses 2.2.3.2 [e] and [f])Photo 10: Cleared land within Stage 7 Ariella Estate

Page 9: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 9

Relevant Fire Danger Index

The fire danger index for this site/development has been determined in accordance with Table 2.1 of AS 3959–2009 or otherwise determined in accordance with a jurisdictional variation applicable to the site. Fire Danger Index

FDI 40 Table 2.4.5

FDI 50 Table 2.4.4

FDI 80 Table 2.4.3

FDI 100 Table 2.4.2

Potential bushfire impacts

The potential bushfire impact to the site/development from each of the identified vegetation plots are identified in Table 2.

Table 2: Method 1 BAL calculation Classified vegetation Effective slope BAL contour width (m) BAL rating Comment

Class B woodland

Downslope >0-5 degrees

<13 BAL–FZ No development is proposed in this area

13–<17 BAL–40 No development is proposed in this area

17–<25 BAL–29 No development is proposed in this area

25–<35 BAL–19 No development is proposed in this area

35–<100 BAL–12.5 Development will occur in this area

Class C shrubland

Downslope >0-5 degrees

<7 BAL–FZ No development is proposed in this area

7–<10 BAL–40 No development is proposed in this area

10–<15 BAL–29 No development is proposed in this area as a result of mandatory R-code building setbacks

15–<22 BAL–19 Development may occur in this area

22–<100 BAL–12.5 Development will occur in this area

Determined Bushfire Attack Level

The Determined Bushfire Attack Level (highest BAL) for the proposed development has been determined in accordance with Clause 2.2.6 (Simplified Procedure [Method 1]) of AS 3959-2009 using the above analysis and documented in each of the BAL certificates in Appendix 1. No development will occur in areas of BAL-40 or BAL-FZ.

BAL certificates

BAL certificates are provided in Appendix 1 for all 47 residential lots within the project area as per the BAL compliance assessment outlined in Figure 1. Should a lower BAL rating be realistically achievable through an appropriate building setback, then the landowner can refer to detailed advice for recommended setbacks in Table 3. The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot and a revised BAL certificate can be issued at that time.

Page 10: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

AS 3959 Bushfire Attack Level (BAL) Compliance Report

CED18426_01 M001 Rev A

22-Aug-18 10

Table 3: Recommended setbacks to achieve a lower BAL rating

Lot number

Current separation distance

Current BAL

rating

Recommended setback to achieve lower BAL

New separation distance New BAL rating*

308

15 m (including 14m wide

Watervalley Boulevard road reserve and at

least a 1 m mandatory front R-code building

setback)

BAL-19 8 m front building setback

22 m (including 14m wide Watervalley Boulevard road

reserve and an 8 m front building

setback)

BAL-12.5 309 BAL-19 8 m front building setback BAL-12.5

310 BAL-19 8 m front building setback BAL-12.5

364 BAL-19 8 m front building setback BAL-12.5

374 BAL-19 8 m front building setback BAL-12.5

415 BAL-19 8 m front building setback BAL-12.5

424 BAL-19 8 m front building setback BAL-12.5

472 BAL-19 8 m front building setback BAL-12.5

473 BAL-19 8 m front building setback BAL-12.5

474 BAL-19 8 m front building setback BAL-12.5

475 BAL-19 8 m front building setback BAL-12.5

490 BAL-19 8 m front building setback BAL-12.5

491 BAL-19 8 m front building setback BAL-12.5

492 BAL-19 8 m front building setback BAL-12.5

493 BAL-19 8 m front building setback BAL-12.5

*The new BAL rating in Table 3 can only be confirmed once the building plan for the relevant lot has been prepared to demonstrate compliance with the recommended setback. Once the setback has been confirmed, a new BAL certificate for the lower BAL rating can be prepared and issued to accompany the building permit application.

Conclusion and recommendations

This BAL compliance report has been prepared for Stage 6 Ariella Estate to provide a final BAL check for individual lots for use at the building permit stage. Assessment results are consistent with current on-ground conditions. Strategen can confirm that the existing BMPs over the site have been implemented as intended throughout the duration of subdivisional works for the relevant Stage 6 area and adjacent land to achieve the bushfire management outcomes as planned for in these documents.

In the absence of any change in development design or post-development classified vegetation extent, Strategen considers that the BAL assessment and BAL certificates outlined in this report are accurate to inform individual lot building permit applications.

Should the extent of classified vegetation change or new vegetation be introduced within 100 m of proposed development, then the BAL rating should be reassessed at the building permit stage to ensure accuracy with on-ground conditions.

Should it be determined through demonstration on the building plan that compliance with the recommended building setbacks has been achieved and subsequently a lower BAL rating has been achieved (as per Table 3), then the lower BAL rating should apply and be reflected in an updated BAL certificate prepared at that time.

The BAL assessment outlined in this report is the most up to date assessment relating to the project area and therefore supersedes any previous Strategen BAL assessments undertaken within the project area.

Ongoing requirements of the current City of Swan annual firebreak notice should continue to be implemented as required, particularly with regards to ongoing fuel management of vacant land and road reserves.

Page 11: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot

Appendix 1 BAL certificates

Page 12: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 13: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 14: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 15: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 16: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 17: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 18: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 19: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 20: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 21: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 22: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 23: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 24: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 25: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 26: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 27: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 28: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 29: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 30: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 31: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 32: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 33: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 34: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 35: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 36: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 37: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 38: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 39: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 40: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 41: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 42: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 43: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 44: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 45: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 46: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 47: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 48: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 49: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 50: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 51: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 52: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 53: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 54: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 55: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 56: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 57: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 58: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot
Page 59: AS 3959 Bushfire Attack Level (BAL) Compliance Report ......The lower BAL rating may be achieved if the recommended building setback is reflected on the building plan for that lot