analog servo amplifier installation guide-condor - … analog servo amplifier installation guide...

40
Condor Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1) www.elmomc.com

Upload: hoanganh

Post on 17-Apr-2018

229 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

 

Condor Analog Servo Amplifier

Installation Guide

 

   

November 2011 (Ver. 1.1)    

 

www.elmomc.com

Page 2: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Notice

This guide is delivered subject to the following conditions and restrictions: 

• This guide contains proprietary information belonging to Elmo Motion Control Ltd. Such information is supplied solely for the purpose of assisting users of the Condor servo drive in its installation. 

• The text and graphics included in this manual are for the purpose of illustration and reference only. The specifications on which they are based are subject to change without notice. 

• Elmo Motion Control and the Elmo Motion Control logo are registered trademarks of Elmo Motion Control Ltd. EtherCAT is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany. 

• Information in this document is subject to change without notice. 

 

Document no. MAN‐CONIG (Ver. 1.1) 

Copyright © 2011  Elmo Motion Control Ltd.  

All rights reserved. 

Catalog Number

 

Revision History Ver. 1.0   Initial Release 

Ver. 1.1   PR changed to VN‐ 

Page 3: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Elmo Worldwide Head Office Elmo Motion Control Ltd. 

60 Amal St., P.O. Box 3078, Petach Tikva  49516 Israel 

Tel: +972 (3) 929‐2300  •  Fax: +972 (3) 929‐2322  •  info‐[email protected] 

North America Elmo Motion Control Inc. 

42 Technology Way, Nashua, NH  03060 USA 

Tel: +1 (603) 821‐9979  •  Fax: +1 (603) 821‐9943  •  info‐[email protected] 

Europe Elmo Motion Control GmbH 

Hermann‐Schwer‐Strasse 3, 78048 VS‐Villingen Germany 

Tel: +49 (0) 7721‐944 7120  •  Fax: +49 (0) 7721‐944 7130  •  info‐[email protected] 

China Elmo Motion Control Technology (Shanghai) Co. Ltd. 

Room 1414, Huawen Plaza, No. 999 Zhongshan West Road, Shanghai (200051) China 

Tel: +86‐21‐32516651  •  Fax: +86‐21‐32516652  •  info‐[email protected] 

Asia Pacific Elmo Motion Control 

#807, Kofomo Tower, 16‐3, Sunae‐dong, Bundang‐gu, Seongnam‐si, Gyeonggi‐do, South Korea 

Tel: +82‐31‐698‐2010   •  Fax: +82‐31‐698‐2013  •  info‐[email protected] 

 

Page 4: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

4

Table of Contents

Chapter 1:  Safety Information ....................................................................................... 6 

1.1.  Warnings .................................................................................................................... 7 1.2.  Cautions ..................................................................................................................... 7 1.3.  Directives and Standards ........................................................................................... 8 1.4.  CE Mark Conformance ............................................................................................... 8 1.5.  Warranty Information ............................................................................................... 8 

Chapter 2:  Introduction ................................................................................................. 9 

2.1.  Product Description ................................................................................................... 9 2.2.  Standard Features ..................................................................................................... 9 2.3.  Fault Protection ....................................................................................................... 10 2.4.  How to Use this Guide ............................................................................................. 10 

Chapter 3:  Installation ................................................................................................. 11 

3.1.  Before You Begin ..................................................................................................... 11 3.1.1.  Site Requirements .................................................................................... 11 

3.2.  Unpacking the Amplifier .......................................................................................... 11 3.3.  Mounting the Condor .............................................................................................. 12 3.4.  Connecting the Cables ............................................................................................. 13 

3.4.1.  Wiring the Condor .................................................................................... 13 3.5.  Condor Connection Diagram ................................................................................... 16 

3.5.1.  Connecting the Power Cables ................................................................... 17 3.5.1.1.  Connecting the Motor Cable ................................................... 19 3.5.1.2.  Connecting the DC Power ........................................................ 20 3.5.1.3.  Connecting the Optional Backup Supply Cable ....................... 22 

3.5.2.  Control, I/Os and Halls Cable Assemblies ................................................. 24 3.5.3.  J2 Control Port .......................................................................................... 25 

3.5.3.1.  J3 General I/O Port .................................................................. 27 3.5.3.2.  J4 Hall’s Signal Port .................................................................. 28 

3.6.  DC Power Supply ..................................................................................................... 29 3.6.1.  Powering Up ............................................................................................. 29 3.6.2.  Initializing the System ............................................................................... 29 

3.7.  Heat Dissipation ....................................................................................................... 29 3.7.1.  Condor Thermal Data ............................................................................... 30 3.7.2.  Heat Dissipation Data ............................................................................... 30 3.7.3.  How to Use the Charts .............................................................................. 32 

Chapter 4:  Servo Control Operation ............................................................................. 33 

4.1.  Condor Connected to DC Motors ............................................................................ 33 4.2.  Current Command Input ......................................................................................... 33 4.3.  External Current Limit ‐ Continuous (ECLC) ............................................................. 33 

Page 5: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Table of Contents MAN-CONIG (Ver. 1.1)

5

4.3.1.  External Voltage ........................................................................................ 33 4.3.2.  External Resistor ....................................................................................... 34 4.3.3.  External Current Limit ‐ Peak (ECLP) ......................................................... 34 4.3.4.  External Voltage ........................................................................................ 34 4.3.5.  External Resistor ....................................................................................... 34 4.3.6.  Latch Mode (LM) ....................................................................................... 34 

4.4.  Status Indications .................................................................................................... 35 

Chapter 5:  Technical Specifications .............................................................................. 36 

5.1.  General Specifications ............................................................................................. 36 5.2.  Environmental Conditions ....................................................................................... 37 5.3.  Dimensions .............................................................................................................. 38 5.4.  Compliance with Standards ..................................................................................... 39 

  

Page 6: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

6

Chapter 1: Safety Information In order to achieve the optimum, safe operation of the Condor servo drives, it is imperative that you implement the safety procedures included in this installation guide. This information is provided to protect you and to keep your work area safe when operating the Condor as well as the accompanying equipment.  

Please read this chapter carefully before you begin the installation process. 

Before you start, ensure that all system components are connected to earth ground. Electrical safety is provided through a low‐resistance earth connection. 

Only qualified personnel may install, adjust, maintain and repair the servo drive. A qualified person has the knowledge and authorization to perform tasks such as transporting, assembling, installing, commissioning and operating motors. 

The Condor servo drives contain electrostatic‐sensitive components that can be damaged if handled incorrectly. To prevent any electrostatic damage, avoid contact with highly insulating materials, such as plastic film and synthetic fabrics. Place the product on a conductive surface and ground yourself in order to discharge any possible static electricity build‐up. 

To avoid any potential hazards that may cause severe personal injury or damage to the product during operation, keep all covers and cabinet doors shut. 

The following safety symbols are used in this manual: 

 

Warning: This information is needed to avoid a safety hazard, which might cause bodily injury. 

 

Caution: This information is necessary for preventing damage to the product or to other equipment. 

 

www.elmomc.com 

Page 7: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Safety Information MAN-CONIG (Ver. 1.1)

7

1.1. Warnings • To avoid electric arcing and hazards to personnel and electrical contacts, never 

connect/disconnect the servo drive while the power source is on. 

• Power cables can carry a high voltage, even when the motor is not in motion. Disconnect the Condor from all voltage sources before it is opened for servicing. 

• The Condor servo drives contain grounding conduits for electric current protection. Any disruption to these conduits may cause the instrument to become hot (live) and dangerous. 

• After shutting off the power and removing the power source from your equipment, wait at least 1 minute before touching or disconnecting parts of the equipment that are normally loaded with electrical charges (such as capacitors or contacts). Measuring the electrical contact points with a meter, before touching the equipment, is recommended. 

1.2. Cautions • The Condor servo drives contain hot surfaces and electrically‐charged components during 

operation. 

• The maximum DC power supply connected to the instrument must comply with the parameters outlined in this guide. 

• When connecting the Condor to an approved 12 to 95 VDC auxiliary power supply, connect it through a line that is separated from hazardous live voltages using reinforced or double insulation in accordance with approved safety standards. 

• Before switching on the Condor, verify that all safety precautions have been observed and that the installation procedures in this manual have been followed. 

www.elmomc.com 

Page 8: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Safety Information MAN-CONIG (Ver. 1.1)

www.elmomc.com 

8

1.3. Directives and Standards The Condor conforms to the following industry safety standards: 

 

Safety Standard  Item 

In compliance with UL 508C   Power Conversion Equipment  

In compliance with UL 840  Insulation Coordination, Including Clearance and Creepage Distances of Electrical Equipment 

In compliance with UL 60950‐1   (formerly UL 1950) 

Safety of Information Technology Equipment, Including Electrical Business Equipment 

In compliance with EN 60204‐1  Low Voltage Directive, 73/23/EEC 

The Condor servo drives have been developed, produced, tested and documented in accordance with the relevant standards. Elmo Motion Control is not responsible for any deviation from the configuration and installation described in this documentation. Furthermore, Elmo is not responsible for the performance of new measurements or ensuring that regulatory requirements are met.   

1.4. CE Mark Conformance The Condor servo drives are intended for incorporation in a machine or end product. The actual end product must comply with all safety aspects of the relevant requirements of the European Safety of Machinery Directive 98/37/EC as amended, and with those of the most recent versions of standards EN 60204‐1 and EN 292‐2 at the least. 

According to Annex III of Article 13 of Council Directive 93/68/EEC, amending Council Directive 73/23/EEC concerning electrical equipment designed for use within certain voltage limits, the Condor meet the provisions outlined in Council Directive 73/23/EEC. The party responsible for ensuring that the equipment meets the limits required by EMC regulations is the manufacturer of the end product. 

1.5. Warranty Information The products covered in this manual are warranted to be free of defects in material and workmanship and conform to the specifications stated either within this document or in the product catalog description. All Elmo drives are warranted for a period of 12 months from the time of installation, or 18 months from time of shipment, whichever comes first. No other warranties, expressed or implied — and including a warranty of merchantability and fitness for a particular purpose — extend beyond this warranty. 

   

Page 9: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

9

Chapter 2: Introduction This Installation Guide is intended for design engineers who are integrating Elmo Motion Control Condor servo amplifiers into a machine.  

2.1. Product Description The Condor series of servo amplifiers is designed to operate in the current mode controlling permanent‐magnet trapezoidal brushless motor and DC brush motor.  

The Condor exhibits “the highest density of power and intelligence” and can deliver up to 11.3 kW of continuous power or 13.6 k W of peak power in a most compact and efficient package.  

The Condor operates from a DC power source in the range from 12 to 195 VDC.  

The Power stage of the Condor is fully isolated from other sections of the Condor, such as the control stage and the heatsink. This contributes very significantly to the safety and the EMI immunity of the Condor. In addition it simplifies the requirements of the DC power supply used to power the DC bus of the Condor and allows also the operation with a non‐isolated DC power source. 

The Condor incorporates full custom mixed analog/digital ICs and a hybrid power stage. The basic configuration is a current mode amplifier targeting the OEM market. As such, no trimmers are used in the basic version. In addition to its compliance with relevant MIL standards, the Condor amplifier also meets UL 508C and the relevant CE regulations. 

The Condor power stage is implemented on ceramic substrates. This design enables very high thermal conductivity, high current carrying capacity, improved EMC and good mechanical strength. The control section is implemented by dedicated custom ICs that contribute to enhanced performance and reliability. 

2.2. Standard Features • Operates in current mode  

• Internal DC‐to‐DC converter, which allows for operation from a single supply 

• Zero dead‐band 

• Excellent linearity 

• One differential input 

• Motor current monitor 

• Current gain change for low inductance motors 

• Remote current gain control 

• Status indication and remote control functions by four open collector transistors 

• External continuous and peak current‐limit adjustments 

• Package: plated‐aluminum base plate, plastic housing, UL 94V0 recognized 

• Ultra‐lightweight of 700 grams (24.7 oz) 

www.elmomc.com 

Page 10: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Introduction MAN-CONIG (Ver. 1.1)

www.elmomc.com 

10

2.3. Fault Protection Built‐in protection against possible fault conditions, including: 

• Shorts between the outputs or between each output and the power input/return 

• Overheating 

• Undervoltage/overvoltage 

• Failure of internal power supplies 

• Latch mode for each protective feature  

2.4. How to Use this Guide Installation is the first step in integrating and operating the Elmo Condor servo amplifiers. After carefully reading the safety instructions in the first chapter, the following chapters provide you with installation instructions as follows: 

• Chapter 3, Installation, provides step‐by‐step instructions for unpacking, mounting and connecting the Condor. 

• Chapter 4, Servo Control Operation, explains how to control the operation of the servo amplifier. 

• Chapter 5, Technical Specifications, lists all the drive ratings and specifications. 

 

Page 11: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

11

Chapter 3: Installation

3.1. Before You Begin

3.1.1. Site Requirements 

You can guarantee the safe operation of the Condor by ensuring that it is installed in an appropriate environment. 

Feature  Value 

Ambient operating temperature  ‐40 °C to +70 °C (‐40 °F to 160 °F) 

Maximum non‐condensing humidity  90% 

Operating area atmosphere  No flammable gases or vapors permitted in area 

Note:  Models for extended environmental conditions are available. 

 

 

Caution: The Condor dissipates its heat by convection. The maximum ambient operating temperature of ‐40 °C to +70 °C (‐40 °F to 160 °F) must not be exceeded. 

3.2. Unpacking the Amplifier To unpack the Condor: 

1. Carefully remove the servo amplifier from the box and the Styrofoam.  

2. Check the amplifier to ensure that there is no visible damage to the instrument. If any damage has occurred, report it immediately to the carrier that delivered your amplifier. 

3. To ensure that the Condor you have unpacked is the appropriate type for your requirements, find the part number sticker on the side of the product: 

 

The P/N gives the type designation as follows: 

 

www.elmomc.com 

Page 12: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

12

4. Verify that the Condor type is the one that you ordered, and ensure that the voltage meets your specific requirements. 

3.3. Mounting the Condor The Condor has been designed for Wall Mount along the back (it can also be mounted horizontally on a metal surface) 

M5 socket head cap screws, one through each opening in the heatsink, are used to mount the Condor (see the diagram below). 

For full power output capability the Condor is designed to be mounted on an external heatsink. It is highly recommended that the wall on which the Condor is mounted will have heat dissipation capabilities. The Condor at “free air convection” (without an additional heatsink) can dissipate around 12 W to 15 W.  

 

Figure 1: Mounting the Condor 

www.elmomc.com 

Page 13: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

13

3.4. Connecting the Cables

3.4.1. Wiring the Condor Once the Condor is mounted, you are ready to wire the device. Proper wiring, grounding and shielding are essential for ensuring safe, immune and optimal servo performance of the Condor. 

 

Caution: Follow these instructions to ensure safe and proper wiring: 

• Use twisted pair shielded cables for control, feedback and communication connections. For best results, the cable should have an aluminum foil shield covered by copper braid, and should contain a drain wire. 

The drain wire is a non‐insulated wire that is in contact with parts of the cable, usually the shield. It is used to terminate the shield and as a grounding connection. 

• The impedance of the wire must be as low as possible. The size of the wire must be thicker than actually required by the carrying current. A 24, 26 or 28 AWG wire for control and feedback cables is satisfactory although 24 AWG is recommended. 

• Use shielded wires for motor connections as well. If the wires are long, ensure that the capacitance between the wires is not too high: C < 30 nF is satisfactory for most applications. 

• Keep all wires and cables as short as possible. 

• Keep the motor wires as far away as possible from the feedback, control and communication cables. 

• Ensure that in normal operating conditions, the shielded wires and drain carry no current. The only time these conductors carry current is under abnormal conditions, when electrical equipment has become a potential shock or fire hazard while conducting external EMI interferences directly to ground, in order to prevent them from affecting the drive. Failing to meet this requirement can result in drive/controller/host failure. 

• After completing the wiring, carefully inspect all wires to ensure tightness, good solder joints and general safety. 

www.elmomc.com 

Page 14: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

14

 

Figure 2: Condor Connection Diagram  

 

www.elmomc.com 

Page 15: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

15

Type  Function  Port  Connector Location 

Barrel Connector + M6 Spring Washer + M6 Nut 

Power  VP+, VN‐ 

 

Motor  M1, M2, M3 

Barrel Connector + M5 Flat Washer + M5 Spring Washer + M5 screw  

Ground  PE, PE, PE, PE

Note: If longer screws are required consult Elmo. 

Table 1: Power Connectors on the Condor 

Type  Function  Port  Connector Location 

15‐Pin D‐Sub female 

Halls signals.  J4 

 

9‐Pin D‐Sub female  Inputs, Outputs (IO) 

J3 

Table 2: Halls signals and I/O Connectors on the Condor 

Type  Function  Port  Connector Location 

9‐Pin D‐Sub male  Backup Supply 

J1 

  

15‐Pin High   Density D‐Sub male 

Control  J2 

Table 3: Controls and Backup Connectors on the Condor 

PEPE

J4 Female: Halls signals J3 Female: I/O

J1 Male: Optional Backup Supply

J2 Male: logic

www.elmomc.com 

Page 16: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

16

3.5. Condor Connection Diagram

 

Figure 3: Condor Connection Diagram  

 

www.elmomc.com 

Page 17: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

17

3.5.1. Connecting the Power Cables The main power connector located at the bottom of the Condor, as follows:  

Pin  Function  Cable  Pin Positions 

VP+  Pos. Power input  Power   

 

VN‐  Neg. Power input  Power 

PE  Protective earth  Power 

    AC Motor Cable 

DC Motor Cable 

PE  Protective earth  Motor  Motor 

M1  Motor phase  Motor  N/C 

M2  Motor phase  Motor  Motor 

M3  Motor phase  Motor  Motor 

Notes:   

• When connecting several motors, all must be wired in an identical manner. 

• If longer screws are required consult Elmo. 

PEPE

PEPE 

Table 4: Connector for Main Power and Motor Cables 

  

www.elmomc.com 

Page 18: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

18

M6 nut (available with the drive) 

M6 spring washer 

Step 1: PE Connection 

 

Note:  PE connection can also be accomplished by attaching the Condor to ground surface. 

Step 2: Power and Motor Connection 

 

Table 5: Connecting the Main Power and Motor Cables 

M5 screw

Barrel connector 

M5 spring washer

Barrel connector  M5 flat washer

M5 screw 

M5 spring washer 

M5 flat washer Barrel connector 

 

M6 nut (available with the drive) 

M6 spring washer 

Barrel connector  

www.elmomc.com 

Page 19: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

19

3.5.1.1. Connecting the Motor Cable 

Connect the motor power cable to the M1, M2, and M3 terminals of the main power connector and the fourth wire to the PE (Protective Earth) on the heatsink (see diagram above). 

Notes for connecting the motor cables:  

• For best immunity, it is highly recommended to use a shielded (not twisted) cable for the motor connection. A 4‐wire shielded cable should be used. The gauge is determined by the actual current consumption of the motor. 

• Connect the shield of the cable to the closest ground connection at the motor end. 

• Connect the shield of the cable to the PE terminal on the heatsink. 

• Be sure that the motor chassis is properly grounded. 

• To close the motor cable into the drive, use the barrel connector, M6 spring washer and M6 nut (in the drive). The required torque is 3 to 4 Nm. 

• To close the PE wire into the drive, use the barrel connector, M5 flat washer, M5 spring washer and M5 screw to the heatsink. The required torque is 3 to 4 Nm. 

• Use flex wire 6/8/10 AWG to barrel connector. 

 

 

Figure 4: AC Motor Power Connection Diagram 

www.elmomc.com 

Page 20: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

20

3.5.1.2. Connecting the DC Power 

The Power stage of the Condor is fully isolated from other sections of the Condor, such as the control stage and the heatsink. This contributes very significantly to the safety and the EMI immunity of the Condor. In addition it simplifies the requirements of the DC power supply used to power the DC bus of the Condor and allows also the operation with a non‐isolated DC power source. 

3.5.1.2.a Operation with an Isolated DC power Supply: 

The PE (Protective Ground of the AC network) is connected to the VN‐ terminal (the Negative Power Input terminal).  

 

Figure 5: Isolated DC Power Supply 

In this case the isolation is achieved by the isolation transformer.  

It is highly recommended to connect the network PE to the Return (negative terminal) of the Power Supply.  

  

Figure 6: Isolated Power Supply 

In this case the isolation is achieved by using a battery.  

It is highly recommended to connect the PE to the Return (negative terminal) of the Power Supply.  

www.elmomc.com 

Page 21: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

21

3.5.1.2.b Operation with a Non‐ Isolated DC power Supply: 

The PE (Protective Ground of the AC network) must not be connected to the Negative Power Input (the VN‐ terminal)  of the Condor.  

  

Figure 7: Non‐Isolated DC Power Supply 

The Power Supply is directly connected to the AC line. 

(In the case of a 200 VDC drive, for example, the AC must be limited to 135 VAC so as not to exceed the maximum of 190 VDC.) 

The network PE must not be connected to the Return of the Power Supply. 

 

  

Figure 8: Non‐Isolated DC Power Supply 

The Power Supply is directly connected to the AC line through an Autotransformer. 

The network PE must not be connected to the Return of the Power Supply. 

 

Caution: Connecting the PE to the VN‐ with a non‐ isolated power supply will cause damages to the system (Any component that is connected to the system might be damaged). 

www.elmomc.com 

Page 22: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

22

Notes for connecting the DC power supply:  

• The Condor can operate from either an: 

isolated DC power supply  

or a 

non‐isolated DC power supply 

• For best immunity, it is highly recommended to use twisted cables for the DC power supply cable. A 3‐wire shielded cable should be used. The gauge is determined by the actual current consumption of the motor. 

• Connect both ends of the cable shield to the closest ground connection, one end near the power supply and the other end to the PE terminal on the Condor’s heatsink. 

• Only when using an isolated power DC source, connect the VN‐ of the power supply to the closest ground connection for safety reasons. 

• To close the power supply cable into the drive, use the barrel connector, M6 spring washer and M6 nut (in the drive). The required torque is 3 to 4 Nm. 

• To close the PE wire into the drive, use the barrel connector, M5 flat washer, M5 spring washer and M5 screw to the heatsink. The required torque is 3 to 4 Nm. 

3.5.1.3. Connecting the Optional Backup Supply Cable 

Power to the Condor is provided by a 12 to 195 VDC source (depending on model type). A “smart” control‐supply algorithm enables the Condor to operate with the power supply only, with no need for an auxiliary supply voltage. If backup functionality is required for storing control parameters in case of power‐outs, an external 12 to 195 VDC power supply can be connected, providing maximum flexibility and optional backup functionality when needed. 

To connect the backup supply to the Auxiliary port, use the Condor's J1 connector (Back up supply connector). Remember, you are working with DC power so be sure to exercise caution.  

Notes for backup supply connections:   

• Use a 24 AWG twisted pair shielded cable. The shield should have copper braid. 

• The source of the backup supply must be isolated. 

• Connect the cable shield to the closest ground near the power source.  

• Before applying power, first verify the polarity of the connection. 

www.elmomc.com 

Page 23: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

23

Pin  Signal  Function  Pin Position 

J1‐9  Backup+ Supply  +VDC backup supply 

 

J1‐8  Backup‐ Supply  Return (common) of the backup supply 

Table 6: Backup Cable Plug 

  

Figure 9: Backup Supply Connection Diagram 

Note:  The return of the backup supply must not be connected to PE, as such a connection can 

damage the drive.  

  

“Smart” Control Supply Options  

Internal DC‐to‐DC converter that allows operation from DC power (no need for auxiliary external supply for normal operation). 

12 to 195 VDC supply for backing up the control parameters if DC power is shut off. 

J1  Male 

www.elmomc.com 

Page 24: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

24

3.5.2. Control, I/Os and Halls Cable Assemblies The Condor features easy‐to‐use D‐Sub type connections for all Control, I/Os and halls cables. Below are instructions and diagrams describing how to assemble these cables. 

• Use 24, 26 or 28 AWG twisted‐pair shielded cables (24 AWG cable is recommended). For best results, the shield should have aluminum foil covered by copper braid. 

• Use only a D‐Sub connector with a metal housing. 

• Attach the braid shield tightly to the metal housing of the D‐type connector.  

• On the motor side connections, ground the shield to the motor chassis. 

• On controller side connections, follow the controller manufacturer’s recommendations concerning the shield. 

       

Figure 10: Control, I/Os and Halls Cable Assemblies 

Note:  All D‐Sub type connectors, used with the Condor, should be assembled in this way.  

 

Metal Housing

Make sure that the braid shield is in tight contact with the metal housing

www.elmomc.com 

Page 25: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

25

3.5.3. J2 Control Port Port J2 has a 15‐pin High‐Density D‐Sub male connector. When assembling this Control cable, follow the instructions in Section  3.5.2 Control, I/Os and Halls Cable Assemblies using a 15‐pin High‐ Density metal case D‐Sub female cable connector (socket). 

Pin  Signal  Function  Description  Pin Location 

1  ANLRET  Return  Analog Return signal 

15‐Pin High‐ Density  D‐Sub 

2  CREF‐  Current Command negative 

Negative input of a differential amplifier. 

Same specification as in pin J2/3. 

3  CREF+  Current Command positive 

Positive input of a differential amplifier: 

Input operating voltage range: 

±10 V 

Maximum input voltage: ±20 V  

Maximum common mode voltage: 

±6 V  Differential input impedance: 40 kΩ 

4  GAIN  Current gain change 

Shorting this pin to LMRET pin (J2/10) reduces  

The proportional gain of the current loop by 70%. 

5  LATCH   Latch mode  Latch mode input. For more details see the Latch Mode (LM) section in Chapter 4. 

6  CMRET  Return  Current monitor (CM) signal return.

7  ECLRET  Return  Current limit signals return. 

8  ECLRET  Return  Current limit signals return. 

9  GAINRET  Return  Return for Gain signal

10  LMRET  Return  Return for Latch Mode signal.

11  CM  Current monitor 

Analog output with a scale of ±3.9 V for ± Ip. 

Output resistance: 1 kΩ

J2 Male 

www.elmomc.com 

Page 26: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

26

Pin  Signal  Function  Description  Pin Location 

12  ECLP  External current limit peak 

External voltage scales down the rated value. 

Voltage range: 0 V to 3.75 V (3.75 V = rated Ip) 

13  ECLC  External current limit continuous 

External voltage scales down the rated value. 

Voltage range: 0 V to 3.75 V (3.75 V = rated Ic) 

14  EN+  Enable +  Positive voltage input of the “Amplifier Enable” function. To enable operation of the amplifier, the optocoupler must be energized by applying voltage between this pin (+) and pin J2/15 (‐).  

The optocoupler is isolated from the amplifier.  

“OFF” voltage: 0 V < Vin < 1 V. 

“ON” voltage: 2.5 V < Vin < 10 V, 5 V typically with current consumption 2.5 mA.

15  EN‐  Enable ‐  Negative voltage input of “Amplifier Enable” function. 

Optocoupler is isolated from the amplifier. 

For details, see pin J2/14.

Table 7: J2, Control Connector Cable‐ Pin Assignments 

Note:  All of the XXRETs are shorted internally. 

www.elmomc.com 

Page 27: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

27

3.5.3.1. J3 General I/O Port  

Port J3 has a 9‐pin D‐Sub female connector. When assembling this I/O cable, follow the instructions in Section  3.5.2 Control, I/Os and Halls Cable Assemblies using a 9‐pin a metal case D‐Sub male connector (plug). 

Pin   Signal  Function  Description  Pin Position 

1  AOK  Amplifier OK 

When the amplifier under normal operating conditions, this output is in the “active low“ state. When a failure occurs, this output is changed to the “open” state. The optocoupler is an isolated, open collector NPN type. Maximum voltage = 30 V Maximum current = 8 mA “On” voltage: V OUT(On) < 0.8 V 

 

9‐Pin Female 

2  SO1  Status output 1 

Status indication output 1. Specification same as in pin J3/1. 

3  SO2  Status output 2 

Status indication output 2. Specification same as in pin J3/1. 

4  SO3  Status output 3 

Status indication output 3. Specification same as in pin J3/1. 

5  EN+  Enable +  “Amplifier Enable” function. To enable operation of the amplifier, the optocoupler must be energized by applying voltage between this pin (+) and pin J3/6 (‐).  The optocoupler is isolated from the amplifier.  “OFF” voltage: 0 V < Vin < 1 V. “ON” voltage: 2.5 V < Vin < 10 V, 5 V typically with current consumption 2.5 mA. 

6  EN‐  Enable ‐  Negative voltage input of “Amplifier Enable” function. Optocoupler is isolated from the amplifier. For details, see pin J3/5. 

7  SORET  Status output return 

Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. 

8  SORET  Status output return 

Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. 

9  SORET  Status output return 

Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. 

Table 8: J3 I/O Cable ‐ Pin Assignments 

Note:  Amplifier enable (EN+, EN‐) can be enabled from J2 or J3. 

J3 Female 

www.elmomc.com 

Page 28: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

28

3.5.3.2. J4 Hall’s Signal Port 

Port J4 is a 15‐pin D‐Sub female connector. When assembling this cable, follow the instructions in Section  3.5.2 Control, I/Os and Halls Cable Assemblies using a 15‐pin a metal case D‐Sub male connector (plug). 

 

Pin   Signal  Function  Description  Pin Position 

1  HALL+15V  +15 V Hall supply voltage: 15 V ± 10% at 30 mA 

+15 V supply voltage for Hall sensors.  Output current: maximum of 30 mA. 

15‐Pin Female 

2  HALL+ 5V  +5 V Hall supply voltage: 5 V ± 10% at 30 mA 

+5 V supply voltage for Hall sensors.  Output current: maximum of 30 mA. 

3  HARET  Hall supply voltage return 

Return used only for Hall supply. 

4  HARET  Hall supply voltage return 

Return used only for Hall supply. 

5  HA  Hall A input  Logic levels: TTL Maximum input voltage: 15 VDC. 

6  HB  Hall B input  Logic levels: TTL Maximum input voltage: 15 VDC. 

7  HC  Hall C input  Logic levels: TTL Maximum input voltage: 15 VDC. 

8  N.C.   

9  N.C.   

10  N.C.   

11  N.C.   

12  N.C.   

13  N.C.   

14  N.C.   

15  N.C.   

J4 Female 

Table 9: J4 Halls Cable ‐ Pin Assignments 

www.elmomc.com 

Page 29: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

29

3.6. DC Power Supply The DC power supply can be at any voltage in the range defined in the technical specifications (Chapter 5 of this guide). The supply source must comply with the safety aspects of the relevant requirements, in accordance with the most recent version of the standard EN60950 or equivalent Low Voltage Directive Standard, all according to the applicable overvoltage category. If the power source to the power supply is the AC line (through an isolated or a NON isolated transformer), safety margins must be considered, in order to avoid activating the under/over voltage protection due to line variations and/or voltage drop under load. 

In addition to the above, the transformer must comply with the safety aspects of the relevant requirements in accordance with the most recent version of the standard EN60742 (Isolating and Safety Isolating Transformers). The nominal DC bus voltage should be in the following range: 

 1.2 Vdcmin < Vdc < 0.9 Vdcmax 

Where: Vdcmin is the minimum DC bus Vdcmax is the maximum DC bus 

The transformer power should be calculated such that it will be able to deliver power to the amplifier (including peak power) without significant voltage drops. 

The power supply should be located as close as possible to the amplifier. While driving high‐inertia loads, the power supply must be equipped with a shunt regulator; otherwise, the amplifier will be disabled whenever the capacitors are charged above the maximum voltage, during motor break down.   

3.6.1. Powering Up After the Condor is connected to its devices, the Condor is ready to be powered up. 

 

Caution: Before applying power, ensure that the DC supply is within the specified range and that the proper plus‐minus connections are in order. 

3.6.2. Initializing the System After the Condor has been connected and mounted, the system must be set up and initialized.  

3.7. Heat Dissipation For full power output capability the Condor is designed to be mounted on an external heatsink. It is highly recommended that the “Wall” on which the Condor is mounted will have heat dissipation capabilities. The Condor at “free air convection” (without an additional heatsink) 

can dissipate around 12 W for 40 °C ambient temperature and not exceeding 80 °C on the heatsink.  

When “Free Air Convection” is sufficient for the application it is recommended to leave approximately 10 mm of space between the Condor's heatsink and any other assembly.  

www.elmomc.com 

Page 30: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

30

3.7.1. Condor Thermal Data 

• Free air convection thermal resistance (θ): Approximately 3.6 to 4 °C/W. 

• Thermal time constant: Approximately 40 minutes/ 2400 seconds (thermal time constant means that the Condor will reach 2/3 of its final temperature after 4 minutes). 

• Self heat dissipation capability (no external heatsink): 12 W for 40 °C/W temperature rise. 

• Shut‐off temperature: 86 °C to 88 °C (measured on the heatsink). 

• The thermal resistance when connecting to an external heat sink: 

The surface of the external heatsink is 50 μm: 0.18 °C/W.  Thermal conductive compound. By proper Smearing of the surface a significant 

improvement of the thermal resistance is achieved: 0.13 °C/W  

3.7.2. Heat Dissipation Data Heat Dissipation is shown in graphically below: 

Power Dissipation 60V series

0

10

20

30

40

50

60

70

80

90

100

0 12 20 30 40 50 60 70 80 90

Motor's Current (Ampere)

Pow

er D

issi

patio

n (W

) 12VDC20VDC30VDC40VDC50VDC56VDC

HeatsinkRequired

Heatsinknot

Required Standard 40 °C Ambient Temp.

 

www.elmomc.com 

Page 31: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

31

 

                      

Power Dissipation 100V series

0

20

40

60

80

100

120

0 8.3 16.7 25.0 33.3 41.7 50.0 58.3 66.7 75.0

Motor's Current (Ampere)

Pow

er D

issi

patio

n (W

) 20VDC40VDC60VDC80VDC96VDC

HeatsinkRequired Standard 40 °C Ambient Temp.

Heatsinknot

Required

www.elmomc.com 

Page 32: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Installation MAN-CONIG (Ver. 1.1)

www.elmomc.com 

32

 

Power Dissipation 200V series

0

50

100

150

200

250

0 6.7 13.3 20.0 26.7 33.3 40.0 46.7 53.3 60.0

Motor's Current (Ampere)

Pow

er D

issi

patio

n (W

) 40VDC80VDC120VDC160VDC196VDC

 

3.7.3. How to Use the Charts The charts above are based upon theoretical worst‐case conditions. Actual test results show 30% to 50% better power dissipation.  

To determine if your application needs a heatsink: 

1. Allow maximum heatsink temperature to be 80°C or less (shunt down is 6 °C to 8 °C higher). 

2. Determine the ambient operating temperature of the Condor as ≤ 40 °C. 

3. Calculate the allowable temperature increase as follows:  

For an ambient temperature of 40°C , ΔT= 80 °C – 40 °C = 40 °C  

4. Use the chart to find the actual dissipation power of the drive. Follow the voltage curve to the desired output current and then find the dissipated power.  

5. If the dissipated power is below 12 W the Condor needs no additional cooling. 

Note:   The chart above shows that no heatsink is needed when the heatsink temperature is 

80 °C, ambient temperature is 40 °C and heat dissipated is 4 W. 

 

Page 33: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

33

Chapter 4: Servo Control Operation

4.1. Condor Connected to DC Motors In order to connect the Condor to a DC motor, connect Hall A (J4 pin 5 of the drive) to Hall return (J4 pin 3 of the drive). The motor should be connected to M2, M3. 

4.2. Current Command Input The Condor has a single differential input. The input operating voltage range is ±10 V, meaning that a 10 V signal will result in a fully rated peak current. The current limit circuits will override this signal if the peak duration exceeds 2.7 seconds and/or the required current exceeds the values set by the ECLC and ECLP signals. If the input command voltage exceeds 10 V, input scaling must be implemented by adding a pair of external resistors, according to the following formula: 

Rin (kΩ) = (5.33 * Vin) – 53.6 

Be careful not to apply input voltage above the maximum allowed input voltage as this will cause the input operational amplifier to operate beyond its limits (±20 V) and in extreme cases, may even damage it. 

4.3. External Current Limit - Continuous (ECLC) The continuous current limit of the Condor amplifiers can be scaled down by an external voltage or by an external resistor connected from pin J2/13 (ECLC) to pin J2/8 (ECLRET). 

4.3.1. External Voltage 

VECLCIC(new) =

3.75V* Ic(nom)

VECLCIC(new) =

3.75V* Ic(nom)

An external positive voltage (0 to 3.75 V) to terminal J2/13 (ECLC) in reference to terminal J2/8 (ECLRET) will control the continuous current limit from zero to Ic (nom). 

The voltage is internally clamped to 3.75 V whenever the external VECLC is greater than 3.75 V. 

The external voltage source must be able to source/ sink at least ±0.2 mA. 

The maximum absolute VECLC allowed to be connected is 5 V. 

www.elmomc.com 

Page 34: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Servo Control Operation MAN-CONIG (Ver. 1.1)

34

4.3.2. External Resistor Connect an external resistor between terminal J2/13 (ECLC) and terminal J2/8 (ECLRET).  

The resistor value is given by: 

(Kohm) = 37.4 * Ic(new)

Ic(nom)- 1RECLC (Kohm) = 37.4 * (Kohm) = 37.4 *

Ic(new)

Ic(nom)- 1RECLC RECLC

0 < RECLC < 36.4 K (1/8 Watt) 

At RECLC greater than 36.4 K, the current limit will be internally clamped to the nominal value. Ic(nom) is the nominal continuous current limit of the amplifier. 

4.3.3. External Current Limit ­ Peak (ECLP) The peak current limit of the Condor amplifiers can be scaled down by an external voltage or by an external resistor connected between pin J2/12 (ECLP) and J2/7 (ECLRET). 

4.3.4. External Voltage An external positive voltage (0 to 3.75 V) to terminal J2/12 (ECLP) in reference to terminal J2/7 (ECLRET) will control the peak current limit from zero to Ip(nom). 

VECLPIp(new) =

3.75V* Ip(nom)

VECLPIp(new) =

3.75V* Ip(nom)

The voltage is internally clamped to 3.75 V whenever the external VECLP is higher than 3.75 V. The external voltage source must be able to source/sink at least ±0.2 mA. The maximum absolute VECLP allowed to be connected is 5 V. 

(Kohm) = 37.4 * RECLP Ip(new)

Ip(nom)- 1(Kohm) = 37.4 * RECLP (Kohm) = 37.4 * RECLP

Ip(new)

Ip(nom)- 1

4.3.5. External Resistor Connect an external resistor between terminal J2/12 (ECLP) and terminal J2/7(ECLRET).  The resistor value is given by: 

0 < RECLP < 36.4 K (1/8 Watt) 

At RECLP greater than 36.4 K, the current limit will be internally clamped to the nominal value. Ip(nom) is the nominal peak current limit of the amplifier. 

4.3.6. Latch Mode (LM) By connecting J2/5 to J2/10, the amplifier is latched to disable mode whenever a Short, Commutation or Over Temperature failure occurs. Disabling the amplifier temporarily by removing the power from Enable pin J2/14 resets the latch. Be sure to restore the Enable connection when the reason for the event no longer exists.  

www.elmomc.com 

Page 35: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Servo Control Operation MAN-CONIG (Ver. 1.1)

www.elmomc.com 

35

4.4. Status IndicatiThe fo le lists the Con lifier  indicat

llowing tab

ons dor amp  status ions. 

   Function 

Latch  O n ptio

 AOK 

 SO1 

 SO2 

 SO3 

1  Amplifier OK (AOK)  Open ctor N/A  Low  Open collector  Open collector   colle

2  External disable  No  Low  Low  Open collector  Low 

3  Current limit  No  Low  Open collector  Open collector  Low 

4  Short  Yes collector 

Low  Open collector  Low Open 

5  rature  Yes collector 

Open collector  Low  Low Over tempe Open 

6  Internal supplies protection 

No collector 

Low  Low  Open collector Open 

7  Undervoltage  No collector 

Low  Open collector  Open collector Open 

8  Overvoltage  No  Open collector 

Open collector  Low  Open collector 

9  Shunt*  No  Low  Open collector  Low  Open collector 

10  Power up reset  Nocollector 

Open collector  Open collector  Open collectorOpen 

1  1  Commutation failure  Yes Open  Low  Low  Lowcollector 

* This indication can be used as a digital input for activating an external shunt regulator. 

Table 10: Condor Status Indications 

Notes:  

• Without latch modThe status indications are reset when the fault disappears. 

e: 

• : Temperature and Commutation Failure status indications are reset when 

• Multiple faults: Only the reading of the first fault is reliable. Additional faults add on to the status outputs and the indication is therefore meaningless. 

 

With latch modeThe Short, Over the enable signal is temporarily removed from the enable input. 

Page 36: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide MAN-CONIG (Ver. 1.1)

36

Chapter 5: Technical Specifications

5.1. General Specifications Feature  Units  70/48  70/60  R90/60 50/100  R75/100  35/200  R60/200  18/400 

Minimum supply voltage 

VDC  11  12  18  36  72 

Nominal supply voltage 

VDC  42  50  85  170  360 

Maximum supply voltage 

VDC  48  59  95  195  390 

Maximum continuous power output 

W  3200  4000  5100  4600  6900  6600  11300  6800 

Efficiency at rated power 

%  > 97 

Maximum output voltage 

  97% of DC bus voltage at f=32 kHz 

DC and trapezoidal commutation continuous current limit (Ic) 

A  70  70  90  50  75  35  60  18 

Peak current limit  A  2 x Ic  2 x Ic  No Peak 2 x Ic  No Peak  2 x Ic  No Peak  2 x Ic 

Weight  g (oz)  700 g (24.7 oz) 

Dimensions  mm (in) 

134 x 95 x 60 (5.3" x 3.7" x 2.4") 

Mounting method    Panel mount 

 

Feature  Units   Specification 

PWM switching frequency  kHz  32 ± 5% default on motor 

Switching method    Advanced Unipolar PWM 

Current loop bandwidth  kHz  Up to 4 

Maximum case temperature  °C (°F)  87 °C (188 °F) 

Storage temperature  °C (°F)  ‐40 °C to 100 °C (‐40 °F to +212 °F) 

Servo Modes    Current 

Commands    ±10 VDC 

Feedbacks    Digital Halls 

 

www.elmomc.com 

Page 37: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Technical Specifications MAN-CONIG (Ver. 1.1)

37

5.2. Environmental Conditions

Ambient Temperature Range 

Non‐operating conditions 

‐50 °C to +100 °C (‐58 °F to 212 °F) 

Operating conditions  ‐40 °C to +70 °C (‐40 °F to 160 °F) 

Temperature Shock 

Non‐operating conditions 

‐40 °C to +70 °C (‐40 °F to 160 °F)  within 3 min. 

Altitude  Non‐operating conditions 

Unlimited 

Operating conditions  ‐400 m to 155,000 m (‐1,300 ft to 510,000 ft) 

Maximum Non­condensing Humidity 

Non‐operating conditions 

Up to 95% at 35 °C (95 °F) 

Operating conditions  Up to 95% at 25 °C (77 °F), up to 90% at 42 °C (108 °F) 

Vibration  Operating conditions  20 Hz to2,000 Hz, 14.6g 

Mechanical Shock 

Non-operating conditions

±40g; Half sine, 11 msec 

Operating conditions ±20g; Half sine, 11 msec 

 

www.elmomc.com 

Page 38: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Technical Specifications MAN-CONIG (Ver. 1.1)

38

5.3. Dimensions

 

www.elmomc.com 

Page 39: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Technical Specifications MAN-CONIG (Ver. 1.1)

39

5.4. Compliance with Standards

Specification  Details 

Quality Assurance 

ISO 9001:2008  Quality Management 

Design 

In compliance with MIL‐STD‐704  Aircraft, Electric Power Characteristics 

In compliance with MIL‐STD‐810  Environmental Engineering Considerations and Laboratory Tests 

In compliance with MIL‐STD‐1275  Characteristics of 28 Volt DC Electrical Systems in Military Vehicles 

In compliance with MIL‐STD‐461  Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment 

In compliance with MIL‐HDBK‐ 217F  Reliability Prediction of Electronic Equipment (rating, de‐rating, stress, etc.) 

• IPC‐D‐275 

• IPC‐SM‐782 

• IPC‐CM‐770 

• UL 508C 

• UL 840 

Printed wiring for electronic equipment (clearance, creepage, spacing, conductors sizing, etc.) 

In compliance with VDE0160‐7 (IEC 68)  Type testing 

Safety 

Recognized UL 508C  Power Conversion Equipment  

In compliance with UL 840  Insulation Coordination Including Clearances and Creepage Distances for Electrical Equipment 

In compliance with UL 60950  Safety of Information Technology Equipment Including Electrical Business Equipment 

In compliance with EN 60204‐1  Low Voltage Directive 73/23/EEC 

www.elmomc.com 

Page 40: Analog Servo Amplifier Installation Guide-Condor - … Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.1)

Condor Installation Guide Technical Specifications MAN-CONIG (Ver. 1.1)

www.elmomc.com 

40

Specification  Details 

EMC 

Approved IEC/EN 61800‐3, EMC  Adjustable speed electrical power drive systems 

In compliance with EN 55011 Class A with EN 61000‐6‐2: Immunity for industrial environment, according to: IEC 61000‐4‐2 / criteria B IEC 61000‐4‐3 / criteria A IEC 61000‐4‐4 / criteria B IEC 61000‐4‐5 / criteria B IEC 61000‐4‐6 / criteria A IEC 61000‐4‐8 / criteria A IEC 61000‐4‐11 / criteria B/C 

Electromagnetic compatibility (EMC) 

Workmanship 

In compliance with IPC‐A‐610, level 3  Acceptability of electronic assemblies 

PCB 

In compliance with IPC‐A‐600, level 2  Acceptability of printed circuit boards (PCBs) 

Packing 

In compliance with EN 100015  Protection of electrostatic sensitive devices  

Environmental 

In compliance with 2002/96/EC  Waste Electrical and Electronic Equipment regulations (WEEE) 

Note: Out‐of‐service Elmo drives should be sent to the nearest Elmo sales office. 

In compliance with 2002/95/EC (effective July 2006) 

Restrictions on Application of Hazardous Substances in Electric and Electronic Equipment (RoHS)