a presentation to the qcwa chapter 70 about lightning and grounding

71
A presentation to the QCWA Chapter 70 about Lightning and Grounding

Upload: marcia-sherman

Post on 20-Jan-2016

229 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A presentation to the QCWA Chapter 70 about Lightning and Grounding

A presentation to the QCWA Chapter 70 about Lightning and

Grounding

Page 2: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Many of the following slides courtesy of

Todd Sirola C.O.O.SAE Inc.

Todd provided a presentation to the CCBE last fall on the following topics

Threats To EquipmentGrounding FundamentalsElectrical Protection SystemsCase Studies

Page 3: A presentation to the QCWA Chapter 70 about Lightning and Grounding

How do we get lightning?

• We need convection, cumulo-nimbus clouds, the ones with the anvil shape, the result of a collision of warm and cold air masses

• Ice pellets and grauple• Super cooled water droplets above the

freezing level• Earth has a positive charge, the bottom of the

cloud negative charge• Air is a great insulator so the charges build up

Page 4: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Capacitor Analogy

Page 5: A presentation to the QCWA Chapter 70 about Lightning and Grounding

And then, BOOM!

Page 6: A presentation to the QCWA Chapter 70 about Lightning and Grounding

• At some point the charge is large enough to overcome the insulator

• The leaders build out slowly at relatively low current in both directions

• Once they join the current flows. Upwards of 400,000 amps peak

• Power levels in excess of 1 Gigawatt may be encountered

• Systems need to be engineered with this in mind

Page 7: A presentation to the QCWA Chapter 70 about Lightning and Grounding

• lightning can, and often does, strike the same spot more than once--even the same person. U.S. park ranger Roy Sullivan reportedly was struck seven times between 1942 and 1977.

• Take especially swift action if your hair stands on end, as that means charged particles are starting to use your body as a pathway.

Page 8: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 9: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Just remember

Lightning energy and power system ground faults will find a path to earth.

The key is to design an electrical protection

system to ensure it doesn’t damage equipment.

Page 10: A presentation to the QCWA Chapter 70 about Lightning and Grounding

09/03/93 - 29.6 kA strike - Sandia National Labs

Page 11: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 12: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 13: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 14: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Evidence in Nature

Page 15: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Electrical representation of a tree

Roots

Branches

Trunk

Page 17: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Types of Lightning

• Cloud to Cloud (CC)• Cloud to Air (CA)• In Cloud• Cloud to Ground (CG)• Peak or Positive Giant• Blue Streak • Red Sprite

Page 18: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 19: A presentation to the QCWA Chapter 70 about Lightning and Grounding

A plug for Todd, he can provide

Design, Supply and Install Professional Engineering SupportGrounding System AuditsSystem Resistance (R-Value) TestingSoil Resistivity TestingForensic AnalysisEducational and Training Seminars

Page 20: A presentation to the QCWA Chapter 70 about Lightning and Grounding

What are the threatsLightning

• Direct• Induced

• AC mains• Telecom twisted pair

Electric power systems• Switching operations• Power system ground faults

Page 21: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 22: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 23: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 24: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 25: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 26: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 27: A presentation to the QCWA Chapter 70 about Lightning and Grounding

A typical Ham installation

Page 28: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Definition of Grounding

An engineered , low impedance path to earth.

Definition of Soil Resistivity

A measurement of the electrical resistance of a unit volume of soil. The commonly used unit of measure is the ohm-m.

Page 29: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Factors Influencing Soil Resistivity

Soil Type (chemical makeup)• natural elements (clays, quartz)• foreign elements (salts, fertilizer)

Moisture Content

Temperature

Page 30: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Soil Type

Soil Type Resistivity (ohm-m)

Clays 10-150Sandy Clays 150-600Pure Sand 600-5000Gravel 5000-30,000

Shale/Slate 400-1,000Limestone 1,000-5,000Sandstone 5,000-50,000Granite 1,000-80,000

Page 31: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Moisture Content

Page 32: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Temperature

Temperature Resistivity (ohm-m)

20 0 C 72 10 0 C 99 0 0 C 130 0 0 C (ice) 300 -5 0 C 790 -15 0 C 3,300

Page 33: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Ground Resistance Formula

R = X fR = ground resistance = soil resistivityf = a function determined by

the shape and size of the

electrode

Page 34: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Electrical Protection Systems

Outside Ground Electrodes• Low R value, Low Impedance, High

capacitance, • High energy dissipation

Inside/Equipment Grounding• Single point

Surge Protection Devices (SPD’s)• AC system, Incoming telecom, Transmission

lines

Structural Lightning Protection• Lightning rods, Down conductors

Proactive Lightning Detection

Page 35: A presentation to the QCWA Chapter 70 about Lightning and Grounding

What makes a good outside grounding system?

Low Impedance• Low Resistance• Low Inductance• High Capacitance

High Energy Dissipation

Proper Orientation

Corrosion Resistance

Theft Resistant

Page 36: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Low Impedance Grounds

Z = V / I or

Z = [ R2 + (2ƒL - 2ƒC-1)2 ] 1/2

Lower ResistanceLower Inductance

Increase Capacitance

Page 37: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Low Impedance Grounds

• Increase electrode surface area• Use a capacitive enhancement

product• Increase conductor size• Minimize bends• Maximize bending radius• Eliminate 90º bends• Decrease # of connections

Page 38: A presentation to the QCWA Chapter 70 about Lightning and Grounding

The Trouble with “T” Connections

Lightning travels in straight lines.90 degree connections offer much higher impedance than a straight horizontal conductor.

Page 39: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Weaknesses of Conventional Grounding Systems

• Poor lightning protection• Higher surge impedance• Seasonal fluctuation of R value• Subject to corrosion• Multiple connections

Page 40: A presentation to the QCWA Chapter 70 about Lightning and Grounding

How can I lower Ground Resistance?

Add more rods?

Page 41: A presentation to the QCWA Chapter 70 about Lightning and Grounding

How can I lower Ground Resistance?

Rods must be spaced appropriately ortheir benefit is diminished.

#Rods *Multiply By

2 1.16 4 1.36 8 1.68 16 1.92

24 2.16

*Multiplier if rods are spaced one length apart.

Page 42: A presentation to the QCWA Chapter 70 about Lightning and Grounding

How can I lower Ground Resistance?

Conductive Concrete

Page 43: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Horizontal Electrode Construction

Page 44: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 45: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 46: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 47: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 48: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 49: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 50: A presentation to the QCWA Chapter 70 about Lightning and Grounding
Page 51: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Vertical Electrode Construction

Page 52: A presentation to the QCWA Chapter 70 about Lightning and Grounding

What about inside the shack

Or how to keep Greg on the air

Page 53: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point Grounding

Buildings should be converted to single point grounding. This method eliminates current loops and creates an environment in which it is easier to protect equipment against power surges from whatever source.

Page 54: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point GroundingTypical Radio Site Layout

Page 55: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point GroundingTypical Radio Site Layout

Page 56: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point Grounding

Page 57: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point Grounding

Page 58: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Single Point Grounding

Materials used for inside grounding

• Green insulated grounding conductor • Rated double holed compression lugs with

stainless steel hardware• Copper ground bars with insulated

mounting brackets• NON-Metallic mounting clips• Parallel Compression Connectors

Label all conductors at both ends with permanent identification labels

Page 59: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Surge Protection

Surge Protection is required for all metallic conductors that enter the building:

• Telephone lines• Intranet Line• AC Power Systems• Transmission lines

Page 60: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Surge Protection

Page 61: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Types of Surge Protection

Voltage Limiting Devices

• Gap devices e.g. air gap carbon arrestors and gas tubes

• silicon avalanche diodes, metal oxide varistors.

Current Limiting Devices

• Fuse links

• Circuit breakers

• Heat coilsOther

• Quarter Wave Stubs• Neutralizing transformers• Isolation transformers• Dielectric fiber optics

Page 62: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Case Studies

CKVR Television, Barrie OntarioTower located at the studioComplex on top of the hill overlooking Barrie

Page 63: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Case Study: CKVR - Barrie Broadcast Tower

The protection system included a comprehensive approach to eliminating damage due to lightning and electrical surges.

• Outside grounding electrodes• Inside single point grounding• LSC2000 Lightning Strike Counter• ESID storm monitor linked directly to a stand-by Generator

Page 64: A presentation to the QCWA Chapter 70 about Lightning and Grounding

CKVR - Barrie Broadcast Tower Outside Grounding

A total of 378 m of horizontal electrode was installed at the tower center and each of the guy anchors. The overall ground resistance of the system is 0.9 ohms.

Page 65: A presentation to the QCWA Chapter 70 about Lightning and Grounding

CKVR - Barrie Broadcast Tower Outside Grounding

Guy Anchor GroundingCompound Grounding

Page 66: A presentation to the QCWA Chapter 70 about Lightning and Grounding

CKVR - Barrie Broadcast Tower Inside Grounding

SAE Inc. installed a Master Ground Bar (MGB) in the equipment building.

MGB

Page 67: A presentation to the QCWA Chapter 70 about Lightning and Grounding

CKVR - Barrie Broadcast TowerLightning Strike Counter

Sensor Unit

Counter Unit

Page 68: A presentation to the QCWA Chapter 70 about Lightning and Grounding

CKVR - Barrie Broadcast TowerESID - Generator Installation

The ESID detects storms in the area and automatically switches the site to generator power.

ESIDGenerator

Page 69: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Is there any science to this?

• It’s a lot of money to spend on the off hand chance it might take a lightning hit.

Page 70: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Case Study:CKVR - Barrie Broadcast Tower

On June 11, 2000 a severe storm rolled through Barrie. Lightning knocked out a substation at 6:21 am cutting off power to the surrounding area. Fortunately at 5:08 am the ESID had identified the storm activity and switched the site to generator power. The site remained on generator until 9:40 am when the storm had passed.

CKVR was never off the air.

Page 71: A presentation to the QCWA Chapter 70 about Lightning and Grounding

Case Study:CKVR - Barrie Broadcast Tower

During the same storm the LSC2000 registered 3 direct strikes to the tower. Global Atmospherics data confirmed the times and provided peak currents: 4:55 am 20 kA 5:10 am 35 kA 5:59 am 59 kA

The grounding system absorbed the energy of the strikes and no damage occurred to any of the sensitive broadcasting equipment.