Quick Selection Guide

London Birmingham Manchester

020 8655 7600 0121 666 4700 0161 872 2000

A guide to selecting refrigeration equipmentfor cold rooms and beer cellars

www.thermofrostcryo.co.uk

Email: [email protected]

T.Cryo Selection Guide 8.4.12_Layout 1 10/04/12 11:03 PM Page 1

Page 2: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

Copyright Thermofrost Cryo Plc, April 2012

QUICK SELECTION GUIDEA guide to selecting refrigeration equipment for cold rooms and beer cellars

Contents:

Freezer rooms at -23 deg.CTables using Maneurop Optyma and KD units, matched with Univap and Kuba coolers

tables 1 to 5

Freezer rooms at -18 deg.CTables using Cubigel, FrigorAfen, Maneurop Optyma and KD units, matched with Univap and Kuba coolers

tables 6 to 12

Chill rooms at -2 deg.CTables using Cubigel, FrigorAfen, Maneurop Optyma and KD units, matched with Univap and Kuba coolers

tables 13 to 17

Vegetable/provisions rooms at +4 deg.CTables using Cubigel, FrigorAfen, Maneurop Optyma and KD units, matched with Univap and Kuba coolers

tables 18 to 21

Beer cellars at +10 deg.C (cellar below ground)Tables using Cubigel, FrigorAfen, Maneurop Optyma, Fusion and KD units, matched with Cellartemp and Univap coolersAlso includes JCC cellar cooling systems

tables 22 to 27

Beer cellars at +10 deg.C (cellar above ground)Tables using Cubigel, FrigorAfen, Maneurop Optyma, Fusion and KD units, matched with Cellartemp and Univap coolersAlso includes JCC cellar cooling systems

tables 28 to 33

Equipment selections are specifically for the conditions stated and are offered as guidelines only. The Purchaser should ascertain that the products selected in this guide are suitable for the specificapplication; product details and specifications can be found in our Commercial Refrigeration price list and also in the downloads section of our website: www.thermofrostcryo.co.uk. The Companyshall endeavour to supply products suitable for the Purchasers requirements but shall not be under any liability where no or incorrect technical or other information as to its application or usage hasbeen supplied. For further selections, please request a copy of our Refrigeration Equipment Selection CD-ROM, which provides selections for an even wider range of applications and equipment.

Page 3: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

FREEZER ROOMS at - 23 deg C: tables 1 to 3

Table 1: Freezer room at -23 C. Refrigerant R404A (R507). Using Maneurop Optyma LCH low temperature units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 1230 4200 LCHC048 TDM3 1650 5630 6.1 11.0 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1400 4800 LCHC048 TDM3 1650 5630 6.1 11.0 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 CONP532

10 350 1990 6800 LCHC068 TDM5 2478 8455 6.3 11.3 3/8" 3/4" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

14 500 2450 8500 LCHC068 TDM5 2478 8455 6.3 11.3 3/8" 3/4" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

21 750 2990 10200 LCHC096 TCM/E5 3261 11127 5.4 9.7 3/8" 7/8" TE2(NL) + 3 083 PSG-3S JPAR135 N/A CONP534

35 1250 3700 12400 LCHC108 TCM/E6 4009 13679 5.0 9.0 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 4200 14200 LCHC108 TCM/E6 4009 13679 5.0 9.0 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4900 16250 LCHC136 TCM/E7 5023 17138 5.3 9.5 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

84 3000 6590 22500 LCHC215 TCM/E8 7344 25058 6.3 11.3 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

98 3500 7200 24500 LCHC215 TCM/E8 7344 25058 6.3 11.3 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

113 4000 7470 25500 LCHC215 TCM/E8 7344 25058 6.3 11.3 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

141 5000 8900 30375 LCHC271 TCM/E6 x 2 9901 33782 6.1 11.0 5/8" 1.3/8" 2 x TE2(NL) + 5 165 PSG-5S JPAR145 N/A CONP175170 6000 10640 36320 LCHC271 TCM/E7 x 2 10228 34898 5.4 9.7 5/8" 1.3/8" 2 x TE2(NL) + 5 165 PSG-5S JPAR145 N/A CONP175

Table 2: Freezer room at -23 C. Refrigerant R404A (R507). Using Maneurop Optyma LCH low temperature units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 1230 4200 LCHC048 SPBE041D 1600 5459 6.1 11.0 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1400 4800 LCHC048 SPBE022D 1839 6275 5.6 10.1 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 CONP532

10 350 1990 6800 LCHC068 SPBE032D 2538 8660 5.8 10.4 3/8" 3/4" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

14 500 2450 8500 LCHC096 SPBE061D 3298 11253 5.2 9.4 3/8" 7/8" TE2(NL) + 3 083 PSG-3S JPAR135 N/A CONP534

21 750 2990 10200 LCHC096 SPBE061D 3298 11253 5.2 9.4 3/8" 7/8" TE2(NL) + 3 083 PSG-3S JPAR135 N/A CONP534

35 1250 3700 12400 LCHC108 SPBE043D 3988 13607 5.1 9.2 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 4200 14200 LCHC108 SPBE043D 3988 13607 5.1 9.2 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4900 16250 LCHC136 SPBE052D 5085 17350 5.0 9.0 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

84 3000 6590 22500 LCHC215 SPBE062D 7457 25443 5.9 10.6 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

98 3500 7200 24500 LCHC215 SPBE062D 7457 25443 5.9 10.6 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

113 4000 7470 25500 LCHC215 SPBE062D 7457 25443 5.9 10.6 5/8" 1.1/8" TE2(NL) + 6 165 PSG-5S JPAR145 N/A CONP534

141 5000 8900 30375 LCHC271 SPBE063D 10236 34925 5.3 9.5 5/8" 1.3/8" SE1.1/2-4SX35 165 PSG-5S JPAR145 N/A CONP170170 6000 10640 36320 LCHC271 SPBE063D 10236 34925 5.3 9.5 5/8" 1.3/8" SE1.1/2-4SX35 165 PSG-5S JPAR145 N/A CONP170

Table 3: Freezer room at -23 C. Refrigerant R404A (R507). Using Maneurop Optyma MCZ/MGZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 1230 4200 MCZC048 TDM3 1528 5214 5.2 9.4 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1400 4800 MCZC048 TDM3 1528 5214 5.2 9.4 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

10 350 1990 6800 MCZC060 TDM5 2145 7319 5.5 9.9 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

14 500 2450 8500 MCZC086 TDM5 2622 8946 6.6 11.9 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 N/A CONP532

21 750 2990 10200 MCZC096 TCM/E5 3040 10372 5.0 9.0 3/8" 7/8" TE2 + 3 084 PSG-4S JPAR140 N/A CONP534

35 1250 3700 12400 MCZC108 TCM/E5 3573 12191 5.9 10.6 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 4200 14200 MCZC121 TCM/E6 4248 14494 5.3 9.5 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4900 16250 MCZC136 TCM/E6 4857 16572 6.0 10.8 1/2" 1.1/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

84 3000 6590 22500 MGZD215 TCM/E8 7234 24682 6.1 11.0 5/8" 1.1/8" TE2 + 6 165 PSG-5S JPAR145 N/A CONP170

98 3500 7200 24500 MGZD215 TCM/E8 7234 24682 6.1 11.0 5/8" 1.1/8" TE2 + 6 165 PSG-5S JPAR145 N/A CONP170

113 4000 7470 25500 MGZD215TCM/E9 x 1

TCM/E5 x 27582 25870 5.3 9.5 5/8" 1.1/8"

TE2 + 6

2 x TE2 + 4165 PSG-5S JPAR145 N/A

CONP170

CONP175

141 5000 8900 30375 MGZD242 TCM/E7 x 2 9105 31066 5.0 9 5/8" 1.3/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP175170 6000 10640 36320 MGZD271 TCM/E8 x 2 10280 35075 5.0 9 5/8" 1.3/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP175

Room Volume Delta T

Room Volume Delta TRequired Duty Actual Duty

Actual DutyRequired Duty

Room Volume Required Duty Actual Duty Delta T

Control Panel

Control Panel

Control Panel

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 4: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

FREEZER ROOMS at - 23 deg C: tables 4 and 5

Table 4: Freezer room at -23 C, refrigerant R404A (R507). Using Maneurop Optyma MCZ/MGZ units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 1230 4200 MCZC048 SPBE031D 1412 4818 6.3 11.3 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1400 4800 MCZC048 SPBE031D 1412 4818 6.3 11.3 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

10 350 1990 6800 MCZC060 SPBE022D 2055 7012 6.2 11.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

14 500 2450 8500 MCZC096 SPBE023D 2900 9895 5.8 10.4 3/8" 7/8" TE2 + 3 083 PSG-3S JPAR135 N/A CONP534

21 750 2990 10200 MCZC108 SPBE061D 3632 12392 5.6 10.1 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

35 1250 3700 12400 MCZC108 SPBE061D 3632 12392 5.6 10.1 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 4200 14200 MCZC121 SPBE061D 4025 13733 6.2 11.2 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP535

57 2000 4900 16250 MCZC136 SPBE043D 4844 16528 6.1 11.0 1/2" 1.1/8" TE2 + 4 084 PSG-4S JPAR145 N/A CONP535

84 3000 6590 22500 MGZD215 SPBE081D 7274 24819 6.0 10.8 5/8" 1.1/8" TE2 + 6 165 PSG-5S JPAR145 N/A CONP170

98 3500 7200 24500 MGZD215 SPBE081D 7274 24819 6.0 10.8 5/8" 1.1/8" TE2 + 6 165 PSG-5S JPAR145 N/A CONP170

113 4000 7470 25500 MGZD242 SPBE062D 8346 28477 5.5 9.9 5/8" 1.1/8" J8E+6 165 PSG-5S JPAR145 N/A CONP170

141 5000 8900 30375 MGZD242 SPBE072D 9035 30827 5.0 9 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP170170 6000 10640 36320 MGZD271 SPBE082D 10285 35092 5.0 9 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP170

Table 5: Freezer room at -23 C, refrigerant R404A (R507). Using KD Scroll housed low noise units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

4 150 1400 4800 1PAL030L3 TDM3 1930 6585 6.6 11.9 3/8" 5/8" TE2(NL) + 2 Included Included JPAR135 N/A CONP525

14 500 2450 8500 1PAL035L3 TDM5 2460 8394 6.3 11.3 3/8" 3/4" TE2(NL) + 3 Included Included JPAR135 N/A CONP525

21 750 2990 10200 2PAL050L3 TCM/E5 3510 11976 5.9 10.6 3/8" 7/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP525

35 1250 3700 12400 2PAL060L3 TCM/E5 4080 13921 6.8 12.2 1/2" 7/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP52557 2000 4900 16250 2PAL075L3 TCM/E6 5100 17401 6.0 10.8 1/2" 1.1/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP525

Selection conditions for all -23 deg C freezer room tables:

Ambient temperature to room 27 C ( 80 C ). Ambient temperature to condenser 32 C ( 90 C ). Insulation 100mm thick Polyurethane (sides, walls & floor)

Product load based on 56kg/m3. Entering at no more than 5 C above Room Temperature.Product Sp. Ht. 1.88kj/kg/k. Refrigerant lines no longer than 15m. N/A = not applicable

Room Volume Required Duty Actual Duty Delta T

Control PanelRoom Volume Required Duty Actual Duty Delta T

Control Panel

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 5: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

FREEZER ROOMS at - 18 deg C: tables 6 and 7

Table 6: Freezer room at -18 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma LCH low temperature units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 CMX21FBTCM/E1

MA3-ED

1025

1102

3497

3760

6.8

5.1

12.2

9.23/8" 1/2" TE2(NL) + 2 083 PSG-3S JPAR135

CONP513N/A

4 150 1140 3890 CMS26FBTCM/E2

MA3-ED

1333

1356

4548

4627

6.7

6.3

12.1

12.13/8" 1/2" TE2(NL) + 2 083 PSG-3S JPAR135

CONP513N/A

6 200 1345 4590 CMS30FBTCM/E2

MA3-ED

1426

1451

4865

4950

7.0

6.7

12.6

12.13/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135

CONP230N/A

7 300 1550 5295 CMS34FBTCM/E3

MA4-ED

1654

1592

5643

5432

5.5

6.3

9.9

11.33/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135

CONP230N/A

8 350 1675 5715 CMS34FB TCM/E3 1654 5643 5.5 9.9 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

11 400 1920 6560 LCHC048 TCM/E3 2001 6827 6.6 11.9 3/8" 3/4" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 LCHC068 TCM/E4 2783 9496 6.9 12.4 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

28 1000 2790 9525 LCHC068 TCM/E4 2783 9496 6.9 12.4 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

35 1250 3160 10785 LCHC096 TCM/E5 3669 12519 5.9 10.6 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 3530 12045 LCHC096 TCM/E5 3669 12519 5.9 10.6 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4265 14560 LCHC108 TCM/E5 4228 14426 6.8 12.2 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 LCHC108 TCM/E6 4507 15378 5.4 9.7 1/2" 1.1/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP53485 3000 5840 19925 LCHC136 TCM/E7 5613 19152 5.7 10.3 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

Table 7: Freezer room at -18 C. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma LCH low temperature units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 UCG120ATCM/E1

MA3-ED

1000

1050

3497

3412

6.8

5.1

12.2

9.23/8" 1/2" TE2(NL) + 2 083 PSG-3S JPAR135

CONP513N/A

4 150 1140 3890 UCG150ATCM/E2

MA3-ED

1250

1290

4265

4401

6.7

6.3

12.1

12.13/8" 1/2" TE2(NL) + 2 083 PSG-3S JPAR135

CONP513N/A

6 200 1345 4590 UCG150AMA3-ED

MA4-ED

1300

1350

4435

4605

5.5

6.7

10.8

9.93/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135

CONP230N/A

8 350 1675 5715 UCG200U TCM/E3 2100 7165 7.0 12.6 3/8" 3/4" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

11 400 1920 6560 LCHC048 TCM/E3 2001 6827 6.6 11.9 3/8" 3/4" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 LCHC068 TCM/E4 2783 9496 6.9 12.4 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

28 1000 2790 9525 LCHC068 TCM/E4 2783 9496 6.9 12.4 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

35 1250 3160 10785 LCHC096 TCM/E5 3669 12519 5.9 10.6 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

42 1500 3530 12045 LCHC096 TCM/E5 3669 12519 5.9 10.6 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4265 14560 LCHC108 TCM/E5 4228 14426 6.8 12.2 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 LCHC108 TCM/E6 4507 15378 5.4 9.7 1/2" 1.1/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP53485 3000 5840 19925 LCHC136 TCM/E7 5613 19152 5.7 10.3 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

Delta T Control Panel

Control PanelDelta TRoom Volume Required Duty Actual Duty

Room Volume Required Duty Actual Duty

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 6: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

FREEZER ROOMS at - 18 deg C: tables 8 to 10

Table 8: Freezer room at -18 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma LCH low temperature units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 CMX21FB SPBE021D 1053 3593 6.2 11.2 3/8" 1/2" T2(NL) + 2 083 PSG-3S JPAR135 CONP513 N/A

4 150 1140 3890 CMS26FB SPBE031D 1375 4692 6.0 10.8 3/8" 1/2" TE2(NL) + 2 083 PSG-3S JPAR135 CONP513 N/A

6 200 1345 4590 CMS30FB SPBE031D 1471 5019 6.4 11.5 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

7 300 1550 5295 CMS34FB SPBE041D 1625 5545 5.9 10.6 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

8 350 1675 5715 CMS34FB SPBE041D 1625 5545 5.9 10.6 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

11 400 1920 6560 LCHC048 SPBE022D 2047 6984 6.0 10.8 3/8" 5/8" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 LCHC068 SPBE023D 2939 10028 5.7 10.3 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

28 1000 2790 9525 LCHC068 SPBE023D 2939 10028 5.7 10.3 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

35 1250 3160 10785 LCHC096 SPBE042D 3560 12147 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP532

42 1500 3530 12045 LCHC096 SPBE042D 3560 12147 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP532

57 2000 4265 14560 LCHC108 SPBE061D 4292 14644 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 LCHC136 SPBE043D 5393 18401 6.6 11.9 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP53485 3000 5840 19925 LCHC136 SPBE071D 5603 19117 5.7 10.3 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

Table 9: Freezer room at -18 C. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma LCH low temperature units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 UCG120A SPBE011D 990 3378 7.0 12.6 3/8" 1/2" T2(NL) + 2 083 PSG-3S JPAR135 CONP513 N/A

4 150 1140 3890 UCG150A SPBE021D 1220 4163 7.0 12.6 3/8" 1/2" T2(NL) + 2 083 PSG-3S JPAR135 CONP513 N/A

6 200 1345 4590 UCG150A SPBE031D 1320 4504 6.0 10.8 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

8 350 1675 5715 UCG200U SPBE041D 2050 6995 7.5 13.5 3/8" 5/8" TE2(NL) + 2 083 PSG-3S JPAR135 CONP230 N/A

11 400 1920 6560 LCHC048 SPBE022D 2047 6984 6.0 10.8 3/8" 5/8" TE2(NL) + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 LCHC068 SPBE023D 2939 10028 5.7 10.3 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

28 1000 2790 9525 LCHC068 SPBE023D 2939 10028 5.7 10.3 3/8" 7/8" TE2(NL) + 3 084 PSG-4S JPAR140 CONP230 CONP532

35 1250 3160 10785 LCHC096 SPBE042D 3560 12147 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP532

42 1500 3530 12045 LCHC096 SPBE042D 3560 12147 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP532

57 2000 4265 14560 LCHC108 SPBE061D 4292 14644 6.5 11.7 1/2" 7/8" TE2(NL) + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 LCHC136 SPBE043D 5393 18401 6.6 11.9 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP53485 3000 5840 19925 LCHC136 SPBE071D 5603 19117 5.7 10.3 1/2" 1.1/8" TE2(NL) + 5 084 PSG-4S JPAR140 N/A CONP534

Table 10: Freezer room at -18 C. Refrigerant R404A (R507). Using Maneurop Optyma MCZ/MGZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 MCZC030 TCM/E1 806 2750 5.3 9.5 3/8" 1/2" TE2 + 1 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1140 3890 MCZC038 TCM/E2 1282 4374 6.4 11.5 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

6 200 1345 4590 MCZC038 TCM/E3 1428 4872 4.7 8.5 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

7 300 1550 5295 MCZC048 TCM/E3 1782 6080 5.9 10.6 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

8 350 1675 5715 MCZC048 TCM/E3 1782 6080 5.9 10.6 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

11 400 1920 6560 MCZC054 TCM/E3 2017 6882 6.7 12.1 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 MCZC060 TCM/E4 2460 8394 6.1 11.0 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2790 9525 MCZC068 TCM/E4 2782 9492 6.9 12.4 3/8" 7/8" TE2 + 3 084 PSG-4S JPAR140 N/A CONP532

35 1250 3160 10785 MCZC068 TCM/E5 3089 10540 5.0 9.0 3/8" 7/8" TE2 + 3 084 PSG-4S JPAR140 N/A CONP534

42 1500 3530 12045 MCZC096 TCM/E5 3510 11976 5.7 10.3 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

57 2000 4265 14560 MCZC108 TCM/E6 4398 15006 5.3 9.5 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 MCZC121 TCM/E6 4868 16610 5.8 10.4 1/2" 1.1/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

85 3000 5840 19925 MCZC136 TCM/E7 5758 19646 5.8 10.4 1/2" 1.1/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

113 4000 7500 25610 MGZD215 TCM/E8 8210 28013 6.8 12.2 1/2" 1.1/8" J8E+6 084 PSG-4S JPAR140 N/A CONP170

141 5000 8925 30465 MGZD215 TCM/E9 8668 29575 5.8 10.4 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP170170 6000 10545 35995 MGZD242 TCM/E6 x 2 10051 34294 6.0 10.8 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP175

Control PanelDelta T

Room Volume

Room Volume Required Duty Delta TActual Duty Control Panel

Room Volume Required Duty Actual Duty

Required Duty Actual Duty Delta T Control Panel

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 7: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

FREEZER ROOMS at - 18 deg C: tables 11 and 12

Table 11: Freezer room at -18 C. Refrigerant R404A (R507). Using Maneurop Optyma MCZ/MGZ units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

3 100 935 3190 MCZC030 SPBE011D 791 2699 5.6 10.1 3/8" 1/2" T2 + 1 083 PSG-3S JPAR135 CONP230 CONP532

4 150 1140 3890 MCZC038 SPBE031D 1329 4535 5.9 10.6 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

6 200 1345 4590 MCZC038 SPBE031D 1329 4535 5.9 10.6 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

7 300 1550 5295 MCZC048 SPBE031D 1632 5568 7.2 13.0 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

8 350 1675 5715 MCZC048 SPBE041D 1730 5903 6.3 11.3 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

11 400 1920 6560 MCZC054 SPBE022D 2082 7104 6.2 11.2 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

20 700 2415 8250 MCZC060 SPBE032D 2528 8626 5.6 10.1 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2790 9525 MCZC068 SPBE051D 2988 10195 5.6 10.1 3/8" 7/8" TE2 + 3 084 PSG-4S JPAR140 N/A CONP532

35 1250 3160 10785 MCZC086 SPBE051D 3235 11038 6.1 11.0 3/8" 7/8" TE2 + 3 084 PSG-4S JPAR140 N/A CONP532

42 1500 3530 12045 MCZC096 SPBE061D 3566 12167 5.4 9.7 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP532

57 2000 4265 14560 MCZC108 SPBE061D 4150 14160 6.3 11.3 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

70 2500 4995 17050 MCZC121 SPBE043D 4841 16517 5.9 10.6 1/2" 1.1/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP534

85 3000 5840 19925 MCZC136 SPBE071D 5745 19602 5.9 10.6 1/2" 1.1/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

113 4000 7500 25610 MGZD215 SPBE062D 8387 28616 6.4 11.5 1/2" 1.1/8" J8E+6 084 PSG-4S JPAR140 N/A CONP170

141 5000 8925 30465 MGZD242 SPBE053D 9952 33956 6.2 11.2 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP170170 6000 10545 35995 MGZD242 SPBE072D 10366 35369 5.4 9.7 5/8" 1.3/8" SE1.1/2-4SW 165 PSG-5S JPAR145 N/A CONP170

Table 12: Freezer room at -18 C. Refrigerant R404A (R507). Using KD Scroll housed low noise units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sightglass SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

11 400 1920 6560 1PAL030L3 TCM/E3 2300 7848 7.7 13.9 3/8" 5/8" TE2(NL) + 3 Included Included JPAR135 N/A CONP525

20 700 2415 8250 1PAL030L3 TCM/E4 2480 8462 6.2 11.2 3/8" 7/8" TE2(NL) + 3 Included Included JPAR140 N/A CONP525

28 1000 2790 9525 1PAL035L3 TCM/E4 2930 9997 7.3 13.1 3/8" 7/8" TE2(NL) + 3 Included Included JPAR140 N/A CONP525

42 1500 3530 12045 1PAL040L3 TCM/E5 3610 12317 5.9 10.6 1/2" 7/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP525

57 2000 4265 14560 2PAL050L3 TCM/E5 4220 14399 6.8 12.2 1/2" 7/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP52570 2500 4995 17050 2PAL060L3 TCM/E6 5230 17845 6.3 11.3 1/2" 1.1/8" TE2(NL) + 4 Included Included JPAR140 N/A CONP525

Selection conditions for all -18 deg C freezer room tables:

Ambient temperature to room 27 C ( 80 C ). Ambient temperature to condenser 32 C ( 90 C ). Insulation 75mm thick Polyurethane (sides, walls & floor)

Product load based on 56kg/m3. Entering at no more than 5 C above Room Temperature.

Product Sp. Ht. 1.88kj/kg/k. Refrigerant lines no longer than 15m. N/A = not applicable

Control PanelRoom Volume Required Duty Actual Duty Delta T

Control PanelRoom Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 8: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

CHILL ROOMS at -2 deg C: tables 13 and 14

Table 13: Chill room at -2 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma MCZ/MGZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

3 100 740 2520CML80TB3

CML90TB3

CR4

MA2

730

826

2490

2818

5.6

6.2

10

111/4" 1/2" T2 + 00 052

PSG-2SJPAR130 CONP513 N/A

4 150 915 3125 CMP12TB3CR7

MA3

1184

1198

4040

4088

5.4

5.1

10

91/4" 1/2" TE2 + 1 052

PSG-2SJPAR130 CONP513 N/A

6 200 1095 3735 CMP12TB3CR7

MA3

1184

1198

4040

4088

5.4

5.1

10

91/4" 1/2" TE2 + 1 052

PSG-2SJPAR130 CONP513 N/A

10 350 1425 4860 CMX18TB MA4 1537 5244 5.6 10 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

14 500 1650 5630 CMS22TB MA5 1834 6258 5.1 9 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2110 7200 MCZC030 TDM4 2038 6954 6.2 11 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

23 800 2340 7990 MCZC038 TDM5 2916 9949 6.6 12 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2800 9560 MCZC038 TCH/E4 3066 10461 5.4 10 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

35 1250 3320 11335 MCZC048 TCH/E4 3859 13167 6.8 12 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

42 1500 3840 13110 MCZC048 TCM/E5 4010 13682 5.9 11 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP532

57 2000 4880 16600 MCZC054 TCH/E5 4566 15579 5.3 10 1/2" 7/8" TE2 + 3 084 PSG-4S JPAR140 CONP150 CONP532

70 2500 5920 20200 MCZC068 TCM/E7 5968 20363 5.6 10 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

85 3000 6900 23570 MCZC086 TCH/E6 6863 23417 6.1 11 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

99 3500 7895 26940 MCZC096 TCM/E8 7587 25887 5.7 10 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP535

127 4000 9870 33680 MCZC121 TCH/E8 10163 34676 6.0 11 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

141 5000 10825 36945 MCZC136 TCH/E9 11582 39518 5.8 10 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

170 6000 12735 43455 MCZC171 TCH/E6 x 2 13431 45827 6.0 11 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP175

198 7000 15435 52680 MGZC215 TCM/E8 x 2 17483 59652 6.6 12 5/8" 1.1/8" 2 x TE2 + 5 166 PSG-5S JPAR145 N/A CONP175226 8000 18480 63065 MGZC215 TCM/E9 x 2 18187 62054 5.6 10 5/8" 1.1/8" 2 x TE2 + 6 165 PSG-5S JPAR145 N/A CONP175

Table 14: Chill room at -2 C. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma MCZ/MGZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

4 150 915 3125 UCHG50ACR5

MA2

940

930

3207

3172

7.0

7.5

12

131/4" 1/2" TE2 + 1 052

PSG-2SJPAR130 CONP513 N/A

6 200 1095 3735 UCHG58ACR6

MA3

1095

1125

3735

3838

6.5

5.0

12

91/4" 1/2" TE2 + 1 052

PSG-2SJPAR130 CONP513 N/A

10 350 1425 4860 UCHG100A MA3 1690 5766 7.5 14 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

14 500 1650 5630 UCHG100A MA4 1730 5903 6 11 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2110 7200 MCZC030 TDM4 2038 6954 6.2 11 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

23 800 2340 7990 MCZC038 TDM5 2916 9949 6.6 12 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2800 9560 MCZC038 TCH/E4 3066 10461 5.4 10 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

35 1250 3320 11335 MCZC048 TCH/E4 3859 13167 6.8 12 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

42 1500 3840 13110 MCZC048 TCM/E5 4010 13682 5.9 11 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP532

57 2000 4880 16600 MCZC054 TCH/E5 4566 15579 5.3 10 1/2" 7/8" TE2 + 3 084 PSG-4S JPAR140 CONP150 CONP532

70 2500 5920 20200 MCZC068 TCM/E7 5968 20363 5.6 10 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

85 3000 6900 23570 MCZC086 TCH/E6 6863 23417 6.1 11 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

99 3500 7895 26940 MCZC096 TCM/E8 7587 25887 5.7 10 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP535

127 4000 9870 33680 MCZC121 TCH/E8 10163 34676 6.0 11 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

141 5000 10825 36945 MCZC136 TCH/E9 11582 39518 5.8 10 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

170 6000 12735 43455 MCZC171 TCH/E6 x 2 13431 45827 6.0 11 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP175

198 7000 15435 52680 MGZC215 TCM/E8 x 2 17483 59652 6.6 12 5/8" 1.1/8" 2 x TE2 + 5 166 PSG-5S JPAR145 N/A CONP175226 8000 18480 63065 MGZC215 TCM/E9 x 2 18187 62054 5.6 10 5/8" 1.1/8" 2 x TE2 + 6 165 PSG-5S JPAR145 N/A CONP175

Control PanelRoom Volume Required Duty Actual Duty Delta T

Control PanelRoom Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 9: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

CHILL ROOMS at -2 deg C: tables 15 and 16

Table 15: Chill room at -2 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma MCZ/MGZ units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

3 100 740 2520 CML80TB SPBE011D 749 2556 4.8 9 1/4" 1/2" T2 + 00 052 PSG-2S JPAR130 CONP513 N/A

4 150 915 3125 CMP12TB SPBE021D 1149 3920 6.3 11 1/4" 1/2" T2 + 1 052 PSG-2S JPAR130 CONP513 N/A

6 200 1095 3735 CMP12TB SPBE021D 1149 3920 6.3 11 1/4" 1/2" TE2 + 1 052 PSG-3S JPAR130 CONP513 N/A

10 350 1425 4860 CMX18TB SPBE031D 1509 5149 6.1 11 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

14 500 1650 5630 CMS22TB SPBE041D 1778 6067 6.1 11 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2110 7200 MCZC030 SPBE022D 2087 7121 5.7 10 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

23 800 2340 7990 MCZC030 SPBE032D 2206 7527 4.5 8 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2800 9560 MCZC038 SPBE032D 2981 10171 6.1 11 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

35 1250 3320 11335 MCZC038 SPBE051D 3079 10506 5.3 10 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

42 1500 3840 13110 MCZC048 SPBE061D 4054 13832 5.6 10 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP532

57 2000 4880 16600 MCZC054 SPBE043D 4591 15664 5.2 9 1/2" 7/8" TE2 + 3 084 PSG-4S JPAR140 CONP150 CONP533

70 2500 5920 20200 MCZC068 SPBE071D 5954 20315 5.6 10 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

85 3000 6900 23570 MCZC086 SPBE052D 6889 23505 6.0 11 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

99 3500 7895 26940 MCZC096 SPBE081D 7605 25948 5.7 10 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP533

127 4000 9870 33680 MCZC121 SPBE053D 10229 34901 5.9 11 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

141 5000 10825 36945 MCZC136 SPBE072D 11666 39804 5.6 10 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

170 6000 12735 43455 MCZC171 SPBE082D 13812 47127 5.2 9 5/8" 1.1/8" SE4.1/2-6SW 165 PSG-5S JPAR145 N/A CONP170

198 7000 15435 52680 MGZC215 SPBE082D 17500 59710 6.6 12 5/8" 1.1/8" SE4.1/2-6SW 166 PSG-5S JPAR145 N/A CONP170226 8000 18480 63065 MGZC215 SPBE073D 18095 61740 5.8 10 5/8" 1.1/8" SE4.1/2-6SW 165 PSG-5S JPAR145 N/A CONP170

Table 16: Chill room at -2 C. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma MCZ/MGZ units with Kuba evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

4 150 915 3125 UCHG50A SPBE011D 950 3241 6.5 12 1/4" 1/2" T2 + 1 052 PSG-2S JPAR130 CONP513 N/A

6 200 1095 3735 UCHG58A SPBE021D 1095 3736 6.5 12 1/4" 1/2" T2 + 1 052 PSG-3S JPAR130 CONP513 N/A

14 500 1650 5630 UCH100A SPBE031D 1680 5732 7 13 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2110 7200 MCZC030 SPBE022D 2087 7121 5.7 10 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

23 800 2340 7990 MCZC030 SPBE032D 2206 7527 4.5 8 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP532

28 1000 2800 9560 MCZC038 SPBE032D 2981 10171 6.1 11 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

35 1250 3320 11335 MCZC038 SPBE051D 3079 10506 5.3 10 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP532

42 1500 3840 13110 MCZC048 SPBE061D 4054 13832 5.6 10 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP532

57 2000 4880 16600 MCZC054 SPBE043D 4591 15664 5.2 9 1/2" 7/8" TE2 + 3 084 PSG-4S JPAR140 CONP150 CONP533

70 2500 5920 20200 MCZC068 SPBE071D 5954 20315 5.6 10 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

85 3000 6900 23570 MCZC086 SPBE052D 6889 23505 6.0 11 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP533

99 3500 7895 26940 MCZC096 SPBE081D 7605 25948 5.7 10 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP533

127 4000 9870 33680 MCZC121 SPBE053D 10229 34901 5.9 11 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

141 5000 10825 36945 MCZC136 SPBE072D 11666 39804 5.6 10 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

170 6000 12735 43455 MCZC171 SPBE082D 13812 47127 5.2 9 5/8" 1.1/8" SE4.1/2-6SW 165 PSG-5S JPAR145 N/A CONP170

198 7000 15435 52680 MGZC215 SPBE082D 17500 59710 6.6 12 5/8" 1.1/8" SE4.1/2-6SW 166 PSG-5S JPAR145 N/A CONP170226 8000 18480 63065 MGZC215 SPBE073D 18095 61740 5.8 10 5/8" 1.1/8" SE4.1/2-6SW 165 PSG-5S JPAR145 N/A CONP170

Control PanelRoom Volume Required Duty Actual Duty Delta T

Room Volume Required Duty Actual Duty Delta T Control Panel

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 10: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

CHILL ROOMS at -2 deg C: table 17

Table 17: Chill room at -2 C. Refrigerant R404A (R507). Using KD housed low noise units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

6 200 1095 3735 PAD008M1 TDM1 1159 3955 7.5 14 1/4" 1/2" TE2 + 1 Included Included JPAR135 CONP513 N/A

10 350 1425 4860 PAD010M1 TDM2 1411 4814 6.5 12 3/8" 5/8" TE2 + 1 Included Included JPAR135 CONP513 N/A

14 500 1650 5630 PAD010M1 TDM3 1531 5224 5.0 9 3/8" 5/8" TE2 + 1 Included Included JPAR135 CONP513 N/A

20 700 2110 7200 PAD012M1 TDM3 2179 7435 7.0 13 3/8" 5/8" TE2 + 2 Included Included JPAR135 CONP513 N/A

23 800 2340 7990 1PAL015M TDM5 2460 8394 6.1 11 3/8" 5/8" TE2 + 3 Included Included JPAR135 CONP513 N/A

28 1000 2800 9560 1PAL020M TDM6 3341 11399 7.0 13 3/8" 5/8" TE2 + 3 Included Included JPAR135 CONP230 CONP525

35 1250 3320 11335 1PAL020M TCH/E4 3470 11840 6.2 11 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP525

42 1500 3840 13110 1PAL025M TCH/E4 3880 13239 6.9 12 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP525

57 2000 4880 16600 1PAL030M TCM/E5 4900 16719 7.3 13 1/2" 7/8" TE2 + 3 Included Included JPAR140 CONP150 CONP525

70 2500 5920 20200 1PAL035M TCM/E6 5760 19653 6.4 12 1/2" 7/8" TE2 + 4 Included Included JPAR140 N/A CONP525

85 3000 6900 23570 1PAL040M TCM/E7 6920 23611 6.4 12 1/2" 7/8" TE2 + 4 Included Included JPAR140 N/A CONP526

99 3500 7895 26940 2PAL050M TCH/E6 8200 27978 7.3 13 1/2" 7/8" TE2 + 5 Included Included JPAR140 N/A CONP526127 4000 9870 33680 2PAL075M TCH/E8 10300 35144 6.0 11 1/2" 7/8" TE2 + 6 Included Included JPAR140 N/A CONP526

Selection conditions for all -2 deg C chill room tables:

Ambient temperature to room 27 C ( 80 C ). Ambient temperature to condenser 32 C ( 90 C ). Insulation 75mm thick Polyurethane (sides, walls & floor)

Product load based on 64kg/m3. Entering at no more than 4 C above Room Temperature..

Product Sp. Ht. 3.14kj/kg/k. Refrigerant lines no longer than 15m. N/A = not applicable

Control PanelRoom Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 11: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

VEGETABLE/PROVISIONS ROOMS at +4 deg C: tables 18 and 19

Table 18: Vegetable/provisions room at +4 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma MCZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

4 150 835 2850 CML80TB3

CR5

MA2

886

882

3023

3009

5.7

5.8

10.3

10.4 1/4" 1/2"TE2 + 00

082 PSG-2S JPAR130 CONP513 N/A

7 250 990 3400 CML90TB3

CR6

MA3

1026

1063

3500

3627

5.2

4.0

9.4

7.2 1/4" 1/2"TE2 + 1

082 PSG-2S JPAR130 CONP513 N/A

11 400 1350 4600 CML12TB3 CR7 1419 4842 5.7 10.3 1/4" 1/2" TE2 + 1 082 PSG-2S JPAR130 CONP513 N/A

14 500 1550 5450 CMP14TB3 MA4 1568 5350 5.0 9.0 3/8" 1/2" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

17 600 1835 6260 CMX18TB3 MA6 1927 6575 4.0 7.2 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2050 7000 CMS22TB MA6 2273 7755 4.7 8.5 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

28 1000 2780 9500 MCZC030 TCM/E4 2744 9363 6.5 11.7 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP520

35 1250 3260 11200 MCZC038 TCM/E5 3910 13341 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

42 1500 3750 12800 MCZC038 TCM/E5 3910 13341 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

57 2000 4570 15600 MCZC048 TCM/E6 5203 17753 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP533

74 2500 5570 19000 MCZC048 TCM/E6 5203 17753 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP533

85 3000 6695 22850 MCZC060 TCH/E6 6444 21987 5.1 9.2 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 CONP150 CONP533

113 4000 8360 28520 MCZC086 TCM/E9 8896 30353 4.9 8.8 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

141 5000 10020 34200 MCZC096 TCH/E8 9716 33151 5.1 9.2 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

198 7000 13765 46980 MCZC121 TCH/E6 x 2 13101 44701 5.1 9.2 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP170226 8000 15390 52520 MCZC136 TCM/E8 x 2 14683 50098 4.9 8.8 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP170

Table 19: Vegetable/provisions room at +4 C. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma MCZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

4 150 835 2850 UCHG33A

CR6

MA2

840

830

2866

2832

4.5

5.5

8.6

9.9 1/4" 1/2"TE2 + 00

082 PSG-2S JPAR130 CONP513 N/A

7 250 990 3400 UCHG50A

CR6

MA3

1070

1200

3650

4094

6.0

5.0

10.8

9.0 1/4" 1/2"TE2 + 1

082 PSG-2S JPAR130 CONP513 N/A

11 400 1350 4600 UCHG58A CR7 1350 4606 5.5 9.9 1/4" 1/2" TE2 + 1 082 PSG-2S JPAR130 CONP513 N/A

14 500 1550 5450 UCHG75A MA3 1590 5425 6.0 10.8 3/8" 1/2" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

20 700 2050 7000 UCHG100A MA5 2180 7438 5.0 9.0 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

28 1000 2780 9500 MCZC030 TCM/E4 2744 9363 6.5 11.7 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP230 CONP520

35 1250 3260 11200 MCZC038 TCM/E5 3910 13341 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

42 1500 3750 12800 MCZC038 TCM/E5 3910 13341 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

57 2000 4570 15600 MCZC048 TCM/E6 5203 17753 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP533

74 2500 5570 19000 MCZC048 TCM/E6 5203 17753 5.1 9.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP533

85 3000 6695 22850 MCZC060 TCH/E6 6444 21987 5.1 9.2 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 CONP150 CONP533

113 4000 8360 28520 MCZC086 TCM/E9 8896 30353 4.9 8.8 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

141 5000 10020 34200 MCZC096 TCH/E8 9716 33151 5.1 9.2 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534

198 7000 13765 46980 MCZC121 TCH/E6 x 2 13101 44701 5.1 9.2 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP170226 8000 15390 52520 MCZC136 TCM/E8 x 2 14683 50098 4.9 8.8 5/8" 1.1/8" 2 x TE2 + 4 165 PSG-5S JPAR145 N/A CONP170

Control Panel

Control PanelRoom Volume Required Duty Actual Duty Delta T

Room Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 12: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

VEGETABLE/PROVISIONS ROOMS at +4 deg C: tables 20 and 21

Table 20: Vegetable/provisions room at +4 C. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma MCZ units with Kuba evaporatorsCond Evaporator Liquid Suction Expansion Drier Sight Solenoid

M3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase4 150 835 2850 CML80TB3 SPA011D 929 3170 4.1 7.4 1/4" 1/2" T2 + 00 082 PSG-2S JPAR130 CONP513 N/A7 250 990 3400 CML90TB3 SPA011D 1043 3559 4.6 8.3 1/4" 1/2" T2 + 1 082 PSG-2S JPAR130 CONP513 N/A

11 400 1350 4600 CML12TB4 SPA021D 1417 4835 5.8 10.4 1/4" 1/2" T2 + 1 082 PSG-2S JPAR130 CONP513 N/A14 500 1550 5450 CML14TB4 SPA021D 1515 5169 6.2 11.2 3/8" 1/2" T2 + 1 083 PSG-3S JPAR135 CONP513 N/A17 600 1835 6260 CMX18TB SPA031D 1866 6367 5.2 9.4 3/8" 5/8" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A20 700 2050 7000 CMS22TB SPA041D 2224 7588 5.4 9.7 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A28 1000 2780 9500 MCZC030 SPA022D 2738 9342 5.5 9.9 3/8" 5/8" TE2 + 2 083 PSG-2S JPAR135 CONP230 CONP52035 1250 3260 11200 MCZC038 SPA023D 3897 13297 5.2 9.4 3/8" 3/4" TE2 + 3 083 PSG-2S JPAR135 CONP230 CONP52042 1500 3750 12800 MCZC038 SPA023D 3897 13297 5.2 9.4 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP52057 2000 4570 15600 MCZC054 SPA043D 5760 19653 4.7 8.5 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP53374 2500 5570 19000 MCZC054 SPA043D 5760 19653 4.7 8.5 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP150 CONP53385 3000 6695 22850 MCZC060 SPA043D 6405 21854 5.2 9.4 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 CONP150 CONP533113 4000 8360 28520 MCZC086 SPA081D 8866 30251 5.0 9.0 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534141 5000 10020 34200 MCZC096 SPA062D 9658 32953 5.3 9.5 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP534198 7000 13765 46980 MCZC121 SPA053D 13047 44516 5.3 9.5 5/8" 1.1/8" TE2 + 6 165 PSG-5S JPAR145 N/A CONP170226 8000 15390 52520 MCZC136 SPA072D 14664 50034 5.0 9.0 5/8" 1.1/8" SE4.1/2-6SW 165 PSG-5S JPAR145 N/A CONP170

Table 21: Vegetable/provisions room at +4 C. Refrigerant R404A (R507). Using KD housed low noise units with Univap evaporatorsCond Evaporator Liquid Suction Expansion Drier Sight Solenoid

M3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase14 500 1550 5450 PAD008M TCM/E2 1592 5432 6.5 11.7 3/8" 1/2" TE2 + 1 Included Included JPAR135 CONP513 N/A17 600 1835 6260 PAD010M TCH/E2 1892 6456 6.0 10.8 3/8" 5/8" TE2 + 1 Included Included JPAR135 CONP513 N/A20 700 2050 7000 PAD010M TCM/E3 1949 6650 5.3 9.5 3/8" 5/8" TE2 + 1 Included Included JPAR135 CONP513 N/A

28 1000 2780 9500 PAD012M TCH/E3 2955 10082 6.1 11.0 3/8" 5/8" TE2 + 2 Included Included JPAR135 CONP513 N/A

35 1250 3260 11200 1PAL015M TCH/E4 3300 11260 5.2 9.4 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP520

42 1500 3750 12800 1PAL020M TCM/E5 4450 15183 5.9 10.6 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP520

57 2000 4570 15600 1PAL025M TCH/E5 5250 17913 5.5 9.9 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP525

74 2500 5570 19000 1PAL030M TCM/E6 6480 22110 6.4 11.5 3/8" 3/4" TE2 + 3 Included Included JPAR135 CONP513 CONP525

85 3000 6695 22850 1PAL030M TCM/E7 6690 22826 5.6 10.1 1/2" 7/8" TE2 + 4 Included Included JPAR140 CONP513 CONP526

113 4000 8360 28520 1PAL040M TCM/E8 8820 30094 6 10.8 1/2" 7/8" TE2 + 5 Included Included JPAR140 N/A CONP526

141 5000 10020 34200 2PAL050M TCH/E8 11080 37805 5.9 10.6 1/2" 7/8" TE2 + 6 Included Included JPAR140 N/A CONP526198 7000 13765 46980 2PAL075M TCH/E9 13500 46062 6.0 10.8 5/8" 1.1/8" TE2 + 6 Included Included JPAR145 N/A CONP526

Selection conditions applicable to all +4 deg C vegetable room tables:

Ambient temperature to room 27 C ( 80 C ). Ambient temperature to condenser 32 C ( 90 C ). Insulation 50mm thick Polyurethane (sides, walls & floor)

Product load based on 64kg/m3. Entering at no more than 10 C.

Product Sp. Ht. 3.77kj/kg/k. Refrigerant lines no longer than 15m. N/A = not applicable

Control PanelRoom Volume Required Duty Actual Duty Delta T

Control PanelRoom Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 13: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

BEER CELLARS at +10 deg C, cellar below ground: tables 22 to 24

Table 22: Beer cellar +10 C, located below ground. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma MCZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

28 1000 1930 6600 CMX18TB TCM/E2 2017 6882 8.4 15.1 3/8" 1/2" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

42 1500 2770 9450 CMS26TB TCM/E3 3127 10669 8.8 15.8 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

57 2000 3660 12500 CMS34TB TCM/E4 4132 14098 8.5 15.3 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 N/A

85 3000 4400 15000 MCZC038 TCM/E4 4247 14491 8.7 15.7 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

113 4000 6000 20500 MCZC048 TCM/E5 5819 19854 7.8 14.0 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

140 5000 7325 25000 MCZC060 TCM/E7 7400 25249 6.4 11.5 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

226 8000 9375 32000 MCZC086 TCM/E7 9698 33090 8.2 14.8 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP520283 10000 11600 39600 MCZC096 TCM/E9 11323 38634 6.5 11.7 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 23: Beer cellar +10 C, located below ground. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma MCZ units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

28 1000 1930 6600 UCHG75A TCM/E2 1880 6415 7.0 12.6 3/8" 1/2" TE2 + 1 083 PSG-3S JPAR135 CONP513 N/A

42 1500 2770 9450 UCHG100A TCM/E3 2600 8871 7.0 12.6 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

57 2000 3660 12500 UCHG150A TCM/E4 3800 12966 7.5 13.5 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 N/A

85 3000 4400 15000 MCZC038 TCM/E4 4247 14491 8.7 15.7 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

113 4000 6000 20500 MCZC048 TCM/E5 5819 19854 7.8 14.0 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

140 5000 7325 25000 MCZC060 TCM/E7 7400 25249 6.4 11.5 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

226 8000 9375 32000 MCZC086 TCM/E7 9698 33090 8.2 14.8 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP520283 10000 11600 39600 MCZC096 TCM/E9 11323 38634 6.5 11.7 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 24: Beer cellar +10 C, located below ground. Refrigerant R404A (R507). Using Fusion housed low noise units with Cellartemp evaporators

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

28 1000 1930 6600 JEH2-088-M CTP16-60 2180 7438 8.5 15.3 3/8" 1/2" Included Included Included

42 1500 2770 9450 JEH2-0150-M CTP16-90 3200 10918 9.0 16.2 3/8" 1/2" Included Included Included

57 2000 3660 12500 JEH2-0150-M CTP26-125 3400 11601 8.0 14.4 3/8" 1/2" Included Included Included

85 3000 4400 15000 JEH2-0225-M CTP26-170 5400 18425 8.0 14.4 1/2" 3/4" Included Included Included

113 4000 6000 20500 JEH2-0300-M CTP36-200 7000 23884 8.5 15.3 1/2" 7/8" Included Included Included140 5000 7325 25000 JEH2-0300-M CTP36-200 7000 23884 8.0 14.4 1/2" 7/8" Included Included Included

Room Volume

Built In

Delta T

Built In

Required Duty Actual Duty

Built In

Control Panel

Built In

Built In

Built In

Room Volume Required Duty Actual Duty Control PanelDelta T

Control PanelRoom Volume Required Duty Actual Duty Delta T

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 14: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

BEER CELLARS at +10 deg C, cellar below ground: tables 25 to 27

Table 25: Beer cellar +10 C, located below ground. Refrigerant R404A (R507). Using KD housed low noise units with Cellartemp evaporators

Cond Evaporator Liquid Suction Expansion Drier Solenoid

M3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

21 750 1750 5970 PAD008M CTP16-60 1900 6482 8.0 14.4 3/8" 1/2" Included Included Included

28 1000 1930 6600 PAD010M CTP16-70 2250 7677 8.0 14.4 3/8" 1/2" Included Included Included

42 1500 2770 9450 PAD012M CTP16-90 3250 11941 8.0 14.4 3/8" 1/2" Included Included Included

57 2000 3660 12500 1PAL020M CTP26-170 5100 17401 8.0 14.4 3/8" 5/8" Included Included Included

85 3000 4400 15000 1PAL020M CTP26-170 5100 17401 8.0 14.4 3/8" 5/8" Included Included Included

113 4000 6000 20500 1PAL030M CTP36-200 7200 24566 8.0 14.4 1/2" 3/4" Included Included Included

140 5000 7325 250001PAL030M

1PAL035M

CTP36-250

CTP36-2008000 27296 8.0 14.4 1/2" 3/4" Included Included Included

226 8000 9375 32000 1PAL040M CTP36-250 10000 34120 8.0 14.4 1/2" 7/8" Included Included Included

Table 26: Beer cellar +10 C, located below ground. Refrigerant R404A (R507). Using KD housed low noise units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

21 750 1750 5970 PAD008M TDM2 1910 6517 8.0 14.4 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A28 1000 1930 6600 PAD010M TDM3 2360 8052 7.0 12.6 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A42 1500 2770 9450 PAD012M TDM4 3327 11351 9.0 16.2 3/8" 1/2" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A57 2000 3660 12488 1PAL015M TDM6 3770 12863 8.0 14.4 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A

85 3000 4400 15013 1PAL020M TCH/E4 5100 17401 8.0 14.4 3/8" 5/8" TE2 + 4 083 PSG-3S JPAR135 CONP513 CONP520

113 4000 6000 20472 1PAL025M TCM/E5 6000 20472 8.0 14.4 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP513 CONP520

140 5000 7325 24993 1PAL030M TCH/E5 7640 26068 8.0 14.4 1/2" 3/4" TE2 + 5 084 PSG-4S JPAR140 CONP513 CONP520

226 8000 9375 31988 1PAL040M TCH/E6 10200 34802 8.0 14.4 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP520283 10000 11600 39579 2PAL050M TCH/E7 12700 43332 8.0 14.4 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 27: Beer cellar +10 C, located below ground. Refrigerant R410A. Using JCC split systems consisting of housed outdoor unit and matched cellar cooler

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

28 1000 1930 6600 2130 7268 8.0 14.4 1/4" 1/2" Included N/A N/A

57 2000 3660 12500 3700 12624 8.0 14.4 1/4" 1/2" Included N/A N/A

85 3000 4400 15000 4680 15968 8.0 14.4 1/4" 5/8" Included N/A N/A113 4000 6000 20500 5710 19483 8.0 14.4 3/8" 5/8" Included N/A N/A

Selection conditions applicable to all below ground cellar tables:

Ambient temperature to room 27C ( 80 F ). Ambient temperature to condenser 32 C ( 90 F ).

Product load based on 45 litres/2.8m3. Entering at no more than 18 C. Refrigerant lines no longer than 15m. N/A = not applicable

Control Panel

Room Volume Delta T

Built In

Required Duty Actual Duty Control Panel

Built In

Delta T

JCC2 60E system

Control Panel

Built In

Built In

JCC2 25E system

JCC2 40E system

Actual Duty

Built In

Built In

Built In

Built In

Built In

Room Volume Required Duty Actual Duty

Built In

Room Volume Required Duty

Delta T

Built In

Built In

JCC2 50E system

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 15: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

BEER CELLARS at +10 deg C, cellar above ground: tables 28 to 30

Table 28: Beer cellar +10 C, located above ground. Refrigerant R404A (R507). Using Cubigel or Maneurop Optyma units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

28 1000 2430 8300 CMS22TB TDM3 2543 8677 7.2 13.0 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

42 1500 3165 10800 CMS26TB TDM6 3289 11222 6.9 12.4 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A

57 2000 3985 13600 CMS34TB TDM6 4132 14098 8.5 15.3 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 N/A

85 3000 5275 18000 MCZC048 TCM/E5 5793 19766 7.9 14.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

113 4000 6740 23000 MCZC054 TCM/E6 6545 22332 6.7 12.1 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

140 5000 7820 27500 MCZC068 TCM/E6 8088 27596 8.1 14.6 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP520

170 6000 8615 29400 MCZC068 TCM/E7 8303 28330 7.2 13.0 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP520283 10000 12450 42500 MCZC108 TCM/E9 13107 44721 7.5 13.5 1/2" 1.1/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 29: Beer cellar +10 C, located above ground. Refrigerant R404A (R507). Using Frigor Afen or Maneurop Optyma units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier Sight SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Glass Valve 1 phase 3 phase

28 1000 2430 8300 UCHG100A TCM/E3 2600 8871 7.0 12.6 3/8" 5/8" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

42 1500 3165 10800 UCHG120A TCM/E4 3550 12113 7.0 12.6 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A

57 2000 3985 13600 UCHG108U TCM/E4 4000 13648 8.0 14.4 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP230 N/A

85 3000 5275 18000 MCZC048 TCM/E5 5793 19766 7.9 14.2 3/8" 3/4" TE2 + 3 083 PSG-3S JPAR135 CONP230 CONP520

113 4000 6740 23000 MCZC054 TCM/E6 6545 22332 6.7 12.1 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP230 CONP520

140 5000 7820 27500 MCZC068 TCM/E6 8088 27596 8.1 14.6 1/2" 7/8" TE2 + 4 084 PSG-4S JPAR140 N/A CONP520

170 6000 8615 29400 MCZC068 TCM/E7 8303 28330 7.2 13.0 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 N/A CONP520283 10000 12450 42500 MCZC108 TCM/E9 13107 44721 7.5 13.5 1/2" 1.1/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 30: Beer cellar +10 C, located above ground. Refrigerant R404A (R507). Using Fusion low noise units with Cellartemp evaporators

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

28 1000 2430 8300 JEH2-088-M CTP16-90 2280 7779 8.5 15.3 3/8" 1/2" Included Included Included

42 1500 3165 10800 JEH2-0150-M CTP16-90 3200 10918 9.0 16.2 3/8" 1/2" Included Included Included

57 2000 3985 13600 JEH2-0225-M CTP26-170 5400 18425 8.0 14.4 1/2" 3/4" Included Included Included

85 3000 5275 18000 JEH2-0225-M CTP26-170 5400 18425 8.0 14.4 1/2" 3/4" Included Included Included

113 4000 6740 23000 JEH2-0300-M CTP36-200 7000 23884 8.5 15.3 1/2" 7/8" Included Included Included140 5000 7820 27500 JEH2-0400-M CTP36-250 10200 34802 9.0 16.2 1/2" 7/8" Included Included Included

Actual Duty Delta T

Room Volume Required Duty Actual Duty Delta T

Room Volume Required Duty

Room Volume Required Duty

Control Panel

Control Panel

Built In

Built In

Built In

Built InBuilt In

Actual Duty Delta T Control Panel

Built In

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section

Page 16: A guide to selecting refrigeration equipmentthermofrostcryo.co.uk/downloads/refrigeration/quick-selection... · A guide to selecting refrigeration equipment for cold rooms and beer

BEER CELLARS at +10 deg C, cellar above ground: tables 31 and 33

Table 31: Beer cellar +10 C, located above ground. Refrigerant R404A (R507). Using KD low noise units with Cellartemp evaporators

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

14 500 1705 5820 PAD008M CTP16-70 1900 6482 8.0 14.4 3/8" 1/2" Included Included Included

21 750 2100 7165 PAD010M CTP16-70 2250 7677 8.0 14.4 3/8" 1/2" Included Included Included

28 1000 2430 8300 PAD012M CTP16-90 3250 11088 8.0 14.4 3/8" 1/2" Included Included Included

42 1500 3165 10800 1PAL015M CTP16-90 3500 11941 8.0 14.4 3/8" 1/2" Included Included Included

57 2000 3985 13600 1PAL020M CTP26-170 5100 17401 8.0 14.4 3/8" 5/8" Included Included Included

85 3000 5275 18000 1PAL020M CTP26-170 5100 17401 8.0 14.4 3/8" 5/8" Included Included Included

113 4000 6740 23000 1PAL030M CTP36-200 7200 24566 8.0 14.4 1/2" 3/4" Included Included Included

140 5000 7820 275001PAL030M

1PAL035M

CTP36-250

CTP36-2008000 27296 8.0 14.4 1/2" 3/4" Included Included Included

226 8000 8615 29400 1PAL040M CTP36-250 10000 34120 8.0 14.4 1/2" 7/8" Included Included Included

Table 32: Beer cellar +10 C, located above ground. Refrigerant R404A (R507). Using KD low noise units with Univap evaporators

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve 1 phase 3 phase

14 500 1705 5820 PAD008M TDM2 1910 6517 8.0 14.4 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

28 1000 2430 8300 PAD010M TDM3 2360 8052 7.0 12.6 3/8" 1/2" TE2 + 2 083 PSG-3S JPAR135 CONP513 N/A

42 1500 3165 10800 PAD012M TDM5 3570 12180 7.5 13.5 3/8" 1/2" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A

57 2000 3980 13580 1PAL015M TDM6 3770 12863 8.0 14.4 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP513 N/A

85 3000 5270 17981 1PAL020M TCH/E4 5100 17401 8.0 14.4 3/8" 5/8" TE2 + 3 083 PSG-3S JPAR135 CONP513 CONP520

113 4000 6740 22997 1PAL030M TCH/E5 7640 26068 8.0 14.4 1/2" 3/4" TE2 + 4 084 PSG-4S JPAR140 CONP513 CONP520

140 5000 7820 26682 1PAL035M TCM/E6 8540 29138 8.0 14.4 1/2" 3/4" TE2 + 5 084 PSG-4S JPAR140 CONP513 CONP520

226 8000 8610 29377 1PAL035M TCM/E7 8890 30333 8.0 14.4 1/2" 7/8" TE2 + 5 084 PSG-4S JPAR140 CONP513 CONP520283 10000 12450 42479 2PAL050M TCM/E9 131700 449360 8.0 14.4 1/2" 7/8" TE2 + 6 084 PSG-4S JPAR140 N/A CONP534

Table 33: Beer cellar +10 C, located above ground. Refrigerant R410A. Using JCC split systems consisting of outdoor unit and matched cellar cooler

Cond Evaporator Liquid Suction Expansion Drier SolenoidM3 FT3 Watts Btu/h Unit Watts Btu/h C F Line Line Valve Valve

28 1000 2430 8300 2130 7268 8.0 14.4 1/4" 1/2" Included N/A N/A

57 2000 3985 13600 3700 12624 8.0 14.4 1/4" 1/2" Included N/A N/A

70 2500 4700 18900 4680 16190 8.0 14.4 3/8" 5/8" Included N/A N/A85 3000 5275 18000 5710 19483 8.0 14.4 1/4" 5/8" Included N/A N/A

Selection conditions applicable to all above ground cellar tables:

Ambient temperature to room 27C ( 80 F ). Ambient temperature to condenser 32 C ( 90 F ).

Product load based on 45 litres/2.8m3. Entering at no more than 18 C. Refrigerant lines no longer than 15m. N/A = not applicable

Room Volume Required Duty Actual Duty Delta T

Room Volume Required Duty Actual Duty Delta T

JCC2 25E system

Built In

Built In

Built In

Built In

Built In

Built In

Control Panel

Built In

Control Panel

Room Volume Required Duty Actual Duty Delta T

JCC2 60E systemJCC2 50E system

Built InBuilt In

JCC2 40E system

Control Panel

Built In

Built In

Built In

Built In

Copyright Thermofrost Cryo Plc, April 2012 Important: For the selection conditions used in these tables, see the end of this section