    SPECIFICATIONS CONT. No.(1)

    SECTION 16060

    GROUNDING AND BONDING

    PART - 1 GENERAL

    1.1 DESCRIPTION

    A. This Section specifies furnishing, installing, connecting and testing of a compelte

    grounding and bonding system.

    B. Related Work Specified Elsewhere:

    1. Section 16050, General Provisions , basic material, methods and requirements

    for electrical works

    1.2 QUALITY ASSURANCE

    A. This installation shall comply in all respects with the General Requirements for

    Grounding and Bonding of Electrical Installations as set out in Article 250 of

    NEC 70 NFPA and this specification.

    B. Reference should be made to IEEE "Recommended Practice for Grounding of

    Industrial and Commercial Power Systems" published by I.E.E.E., Inc. for

    clarifiction, intent and guidance in executing the work. Also reference should be

    made to SCECO Specificaion No. SES-P-108.08 -GROUNDING.

    1.3 SUBMITTALS

    A. Shop Drawings and Manufacturer's Literature:

    B. Submit three copies of certified test report stating that equipment grounding system's

    resistance measures a maximum of 5 ohms to ground.

    PART - 2 PRODUCTS

    2.1 GENERAL

    All goods and products covered by these specifications shall be preferably, whenavailable, from an in-kingdom manufacturer approved by the Owner and conforming

    with the requirements of specifications. In case it is an imported products the

    manufacturer must have an agent in the kingdom. and shall have all required spare parts

    in stock. procurement of all goods and products must be approved by the Owner.

    A. A complete grounding system shall be provided as shown on the drawings and as

    specified. The system shall satisfy all related codes and requirements.

    B. System Ground (Neutral Ground): The neutral terminal of the site distribution

    transformer shall be grounded. A set of grounding rods, loop interconnected with each

    other, shall be connected with a cable a minimum of 500mm below ground to the

    neutral terminal of the transformer. The rods shall be located a minimum of 3 metersfrom each other or any other electrode and shall be loop interconnected with each other

    by copper conductor brazed, thermit welded or high pressure clamped with a bronze

    Ministry of Higher Education 57838975.DOC - 1

    Qassim University University Hospital

  • 8/6/2019 16060- Grounding & Bonding

    2/4

    SPECIFICATIONS CONT. No.(1)

    ground rod clamp designed expressly for the purpose to each rod below grade. The

    system ground resistance shall be 5 ohms.

    C. Equipment Control: The equipment ground systems shall be designed so that all

    metallic structures, enclosures, raceways, junction boxes, outlet boxes, cabinets,

    machine frames, portable equipment and other conductive items in close proximity withelectrical circuits operate continuously at ground potential and provide a low

    impedance path for possible ground fault currents. The equipment ground resistance

    shall be 5 ohms. If the resistance value of 5 ohms cannot be obtained , more ground

    rods shall be provided to achieve 5 ohms or less. The Contractor will submit alternate

    methods to achieve the required result for review by the Owner.

    D. The system ground and the equipment ground shall be connected to the common

    ground bus.

    2.2 GROUND RODS

    A. Ground rods shall be of bonded copper or copper-clad steel not less than 15 mm (5/8")in diameter; 3m (10 ft) long, driven full length into the earth. The copper-clad steel

    ground rod shall be manufactured by a fusion-weld process resulting in an electrolytic

    copper sheath homogeneously welded to an inner steel core. The thickness of the

    copper sheath shall be approximately 10% of the overall rod diameter. Copper

    electroplated steel is not acceptable.

    2.3 GROUND BUS

    A. Ground bus shall be furnished on all switchgear, panels and motor control centers and

    shall be interconnected as shown in the grounding and bonding layout drawings.

    2.4 CONNECTORS

    The Contractor shall determine the number and size of pressure connectors to be

    provided on all equipment grounding bars required for the termination of equipment

    grounding conductors. In addition to the active circuits, provide pressure connectors for

    all three-phase spares and spaces on switchgears.

    2.5 JUMPERS

    Each electrical expansion fitting shall be provided with an external copper bonding

    jumper secured by approved grounding straps on each end of the fitting. Jumpers shall

    be tin plated copper braided flexible suitable for the required use.

    2.6 GROUNDING ELECTRODE CONDUCTOR

    The grounding electrode conductor shall be of copper. The material selected shall be

    resistant to any corrosive condition existing at the installation and shall be suitably

    protected against corrosion. The conductor shall be solid or stranded and shall be

    installed in one continuous Length without a splice or joint.

    2.7 TYPE OF EQUIPMENT GROUNDING CONDUCTORS

    The equipment grounding conductor run with or enclosing the circuit conductors shall

    be one or more or a combination of the following: (1) a copper conductor. Thisconductor shall be solid or stranded; insualted with green PVC covered, or bare; and in

    the form of a wire or a busbar of any shape; (2) rigid metal conduit; (3) intermediate

    Ministry of Higher Education 57838975.DOC - 2

    Qassim University University Hospital

  • 8/6/2019 16060- Grounding & Bonding

    3/4

    SPECIFICATIONS CONT. No.(1)

    metal conduit; (4) electrical metallic tubing; (5) flexible metal conduit approved for the

    purpose and installed with fittings approved for the purpose; (6) armor of Type AC

    cable; (7) the sheath of ineral-insulated metal- sheathed cable; (8) cable trays as

    permitted in the code for grounding purposes. Exception No. 1: Flexible metal conduit

    and flexible metallic tubing shall be permitted for grounding if all the followingconditions are met:

    A. The total length in any ground return path does not exceed 1.8 m

    B. The circuit conductors contained therein are protected by over current devices rated at

    20 amperes or less.

    C. The conduit or tubing is terminated in fittings approved for the purpose. The above is

    an extract from NEC 70 NFPA.

    2.8 SIZE OF GROUNDING ELECTRODE CONDUCTOR FOR AC SYSTEMS

    LINE CONDUCTOR SIZE

    sq-mm

    GROUND CONDUCTOR SIZE

    sq-mm

    1.5

    2.5

    4

    6

    10

    16

    25

    35

    50

    70

    95120

    150

    185

    240

    300

    400

    1.5

    2.5

    4

    6

    10

    16

    25

    16

    25

    35

    5070

    70

    95

    120

    150

    185

    2.9 MINIMUM SIZE OF BONDING CONDUCTORS FOR. GROUNDING

    RACEWAY AND EQUIPMENT

    Rating or Setting of Automatic

    Overcurrent Device in Circuit Ahead ofEquipment (Amperes)

    Size

    Copper Wire in mm

    15

    20

    30

    40

    60

    100

    200

    500

    600

    600

    2.5

    4

    6

    6

    6

    10

    16

    25

    35

    35

    Ministry of Higher Education 57838975.DOC - 3

    Qassim University University Hospital

  • 8/6/2019 16060- Grounding & Bonding

    4/4

    SPECIFICATIONS CONT. No.(1)

    800

    1,000

    1,200

    1,600

    2,000

    2,500

    50

    70

    95

    120

    150

    185

    2.10 GROUND-FAULT PROTECTION OF EQUIPMENT

    Ground-fault protection of equipment shall be provided for solidly grounded wye

    electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-

    to-phase for each service disconnecting means.

    2.11 TEST

    A. The completed equipment grounding system shall be subjected to a meggered test ateach service disconnect enclosure ground bar to insure that the ground resistance,

    without chemical treatment or other artificial means, does not exceed five (5) ohms.

    Certified test reports of the ground resistance shall be submitted for review by the

    Owner.

    PART - 3 EXECUTION

    3.1 GENERAL

    A. Except as may be described in Part 2 of this Section, refer to the applicable provisions

    of Section (16050)& (02590) and the other sections of specifications, Division16.

    END OF SECTION

    Ministry of Higher Education 57838975.DOC - 4

    Qassim University University Hospital