132228833 seminar on steel plate shear wall

24
REPORT ON STEEL PLATE SHEAR WALL PRACTICAL DESIGN AND CONSTRUCTION Guided by: Submitted by: Prof.P.G.Patel Nilesh H. Saksena EN.NO.:110280715004 Applied mechanics department L.D.College of engineering AHMEDABAD-15

Upload: ilieion12

Post on 21-Oct-2015

57 views

Category:

Documents


5 download

TRANSCRIPT

REPORT ON

STEEL PLATE SHEAR

WALL PRACTICAL DESIGN AND CONSTRUCTION

Guided by: Submitted by:

Prof.P.G.Patel Nilesh H. Saksena

EN.NO.:110280715004

Applied mechanics department

L.D.College of engineering

AHMEDABAD-15

Steel plate shear wall

2

INDEX

SR.NO. TITLE

1. INTRODUCTION

2. SYSTEMS OF STEEL PLATE SHEAR WALL

3. ADVANTAGED OF STEEL PLATE SHEAR

WALL

4. DISADVANTAGES OF STEEL PLATE

SHEAR WALL

5. USE OF STEEL PLATE SHEAR WALL AND

THEIR SESMIC BEHAVIOUR

6. ANALYSIS AND DESIGN APPROACH

7. CONSRUCTION CONSIDERATIONS

Steel plate shear wall

3

1. INTRODUCTION

The main function of steel plate shear wall is to resist horizontal

story shear and overturning moment due to lateral loads. In general, steel

plate shear wall system consists of a steel plate wall, two boundary

columns and horizontal floor beams. Together, the steel plate wall and

two boundary columns act as a vertical plate girder as shown in Figure.

The columns act as flanges of the vertical plate girder and the steel plate

wall acts as its web. The horizontal floor beams act, more-or-less, as

transverse stiffeners in a plate girder.

Components of steel plate shear wall systems

Steel plate

Horizontal floor beam

Boundary column

Steel plate shear wall

4

2.SYSTEMS OF STEEL PLATE SHEAR WALL:

1. Un-stiffened, thin SPSW: In these systems the shear wall is

without provision of stiffeners.

Main component of unstiffened thin SPSW systems:

a. Steel plate: This element is usually a relatively thin steel plate.

Plates thinner than 3/8 inch are not recommended since such thin

plates cannot be easy to handle during fabrication and erection.

b. Boundary column: boundary column in the systems resist the

gravity load and also provide resistance against large amount of

torsional moments and give the anchorage to the steel plate.

Steel plate shear wall

5

c. Horizontal floor beams: The top and bottom beams in a shear

wall act as anchor for tension field action of the steel plate and also

provide support to the floor.

2. Stiffened SPSW: In these systems the shear wall is provided

with horizontal stiffeners on one side and vertical stiffeners on other

side.

3. Composite concrete SPSW: The composite shear walls consist

of a steel plate shear wall with reinforced concrete walls attached to one

side or both sides of the steel plate using mechanical connectors such as

shear studs or bolts.

Steel plate shear wall

6

Main Components of a Composite Shear Wall

Main components of composite shear walls shown in Figure are

steel wall, concrete wall; shear connectors, boundary columns, boundary

beams, connection of steel wall to boundary beams and columns, and

beam-to-column connections.

a. Steel plate shear wall: This element is usually a relatively thin steel

plate. Plates thinner than 3/8 inch are not recommended since such thin

plates cannot be easy to handle during fabrication and erection.

b. Reinforced concrete (R/C) shear wall: Reinforced concrete walls

can be connected to one side of a steel plate shear wall. the R/C wall

Steel plate shear wall

7

provides shear strength and stiffness, through its compression field and

some ductility depending on the amount of reinforcement in the wall.

c. Shear connectors: Shear connectors are used to connect steel

elements of the composite wall to concrete. For cast-in-place concrete

usually welded shear studs are used. Of course other shear connectors

such as channels can also be used although they may not be as

economical as welded shear studs. For pre-cast concrete walls, bolts can

be used to connect the R/C walls to steel plate walls

d. Boundary columns: In addition to gravity loads, the columns on the

sides of a composite shear wall resist the bulk of overturning moments.

The columns also provide an anchor point for tension field action of

the steel plate and bearing element for compression diagonal element of

the concrete wall. In structures with relatively large columns, the

columns can also transfer a considerable amount of story shear.

e. Boundary beams: The top and bottom beams in a composite shear

wall act as anchor for tension field action of the steel plate and as

compression bearing element for compression diagonal of the concrete

wall.

f. Connections of shear wall to boundary members: The steel shear

wall should be connected to boundary columns and beams either by

bolts or welds. The main role of these connections is to transfer shear

and tension. The concrete wall can also be connected to the boundary

walls using mechanical connectors. These connections transfer shear that

is resisted by the reinforcement inside the wall.

g. Beam-to-column connections: These connections play a major role

in performance of the walls. In a dual system, where the steel frame is

the “back-up” system for the composite shear wall, the connections

should be moment connections

Steel plate shear wall

8

3. ADVANTAGES OF STEEL PLATE SHEAR

WALL:

1. Wall Thickness. SPSW allow for less structural wall thickness in

comparison to the thickness of concrete shear walls. Astudy performed

for The Century project indicated an average wall thickness, including

the furring, of 18” as opposed to a concrete shear wall thickness with an

average of 28”. This resulted in a savings of approximately

2% in gross square footage.

2. Building Weight. SPSW result in ales ser building weight in

comparison to buildings that use concrete shear walls. A study

performed for The Century project indicated that the total weight of the

building as designed using SPSW was approximately 18% less than that

of the building designed using a concrete shear wall core system, which

results in a reduction of foundation loads due to gravity and overall

building seismic loads.

3.Fast Construction. The use of a SPSW system reduces construction

time. Not only is it fast to erect, but there also is no curing period. A

scheduling study performed by a contractor for The Century project

indicated a one-month reduction in construction time. The steel erector

for the U.S. Federal Courthouse indicated that the erection of the SPSW

was much easier than that of the special concentrically braced frames.

4. Ductility. A relatively thin steel plate has excellent post-buckling

capacity. Research performed on the SPSW system indicates that the

system can survive up to 4% drift without experiencing significant

damage, even though most of the tests showed damage outside

the steel plate panel. There was some pinching and tearing close to the

corners of the panel due to bending. However, this tearing did not reduce

the plate capacity and stiffness.

Steel plate shear wall

9

5. Tested System. At least two buildings that use SPSW as their primary

lateral force resisting system have undergone significant earthquake

ground shaking. Both buildings survived with insignificant insignificant

structural damage (Astaneh & Zhao, 2002). The system also has been

tested since the 1970s. The system has been recognized in the National

Building Code of Canada (NBCC) since 1994 and will be included in

the American Institute of Steel Construction (AISC) Seismic Provisions

in 2005.

Steel plate shear wall

10

4.DISADVANTAGES OF STEEL PLATE

SHEAR WALL:

1. Stiffness. SPSW systems are usually more flexible in comparison

to concrete shear walls, primarily due to their flexural flexibility.

Therefore, when using SPSW in tall buildings, the engineer must

Provide additional flexural stiffness. In both The Century and the

U.S. Federal Courthouse projects, large composite concrete infill

steel pipe columns were used at all corners of the core wall to

improve the System’s flexural stiffness as well as its overturning

capacity.

2. Construction Sequence. Excessive initial compressive force in

the steel plate panel may delay the development of the tension-

field action. It is important that the construction sequence be

designed to avoid excessive compression in the panel. In the U.S.

Federal Courthouse project, the welding of the plate splice

connections was delayed until most of the dead load deformation

occurred in order to relieve the pre-compression within the steel

plate shear wall panel.

3.New System. Due to unfamiliarity with the system, a contractor

will typically estimate a relatively high erected cost. This may be

solved by engaging the contractor early in the design phase.

Steel plate shear wall

11

5. USE OF STEEL SHEAR WALLS AND THEIR SEISMIC BEHAVIOR

Steel plate shear walls (SPSW) have been used, to a limited

extent, as the primary lateral force resisting system in buildings for more

than three decades. There have been numerous SPSW research programs

in this timeframe in the United States, Canada, and Japan to help foster a

better understanding of the system’s behavior, particularly as it relates

to earthquake-resistant design. Some major building projects that

utilized SPSW as the primary lateral force resisting system include the

following:

➜ United States Federal Courthouse, Seattle, WA— 23-story building

(350’)

➜ Sylmar Hospital, Los Angeles, CA— six-story building

➜ Canam-Manac Headquarters Expansion, St. George, Quebec— six-

story building

➜ Hyatt Regency Hotel at Reunion, Dallas, TX— 50-story building

(562’)

➜ The Century, San Francisco, CA— 46- story building (465’; the

project was cancelled after the completion of

design and permit)

➜ Nippon Steel Building, Tokyo, Japan— 20-story building

➜ Shinjuku Nomura Building, Tokyo, Japan— 51-story building (693’)

➜ Kobe Office Building, Kobe, Japan— 35-story building (425’)

Steel plate shear wall

12

1.A 20-story office building in Tokyo, Japan

According to Thorburn et al. (1983) it is believed that this

building, referred to as Nippon Steel Building, was the first major

building using steel plate shear walls. Located in Tokyo, it was

completed in 1970.

The lateral load resisting system in longitudinal direction was

a combination of moment frame and steel plate shear wall units in an H

configuration and in transverse direction consisted of steel plate shear

walls.

Figure 2.1 shows a typical plan. The steel plate wall panels

consisted of 9’ by 12’-2” steel plates with horizontal and vertical steel

channel stiffeners.

Figure 2.2 shows the details of steel plate shear wall system.

The thickness of steel wall plates ranged from 3/16” to ½” . In design,

the gravity load was not given to steel shear walls and the walls were

designed to resist design lateral loads without buckling.

Steel plate shear wall

13

2.53-story high-rise in Tokyo

The structure was initially designed using reinforced concrete

shear walls. However, according to Engineering News Record (1978),

due to patent problem, the R/C walls were converted to steel shear walls.

Figure 2.3 shows a plan view and elevation of the building. According to

ENR article (ENR, 1978), “the contractor rejected a steel braced

building core as too expensive” compared to steel shear wall.

The structure consisted of moment perimeter frame and “T”

shaped stiffened steel shear walls. The wall panels were about 10-ft high

and 16.5 feet long and had vertical stiffeners on one side and horizontal

stiffener on the other side. The panels were connected to boundary box

and H steel columns using bolts. The construction contractor in this case

has made a comment that “ The next high-rise building we do won’t

likely be designed with bolted steel seismic walls” (ENR, 1978).

According to ENR article, the contractor on another high-rise in Tokyo

switched from bolted steel panels to welded panels after failing to

achieve the required precision. .

Steel plate shear wall

14

3. A 30-story hotel in Dallas, Texas

This structure, described in Reference (Troy and Richard, 1988) is

a very good example of efficient use of steel shear walls in areas with

low seismicity but with relatively high wind loads. The 30-story

structure has steel braced frame in longitudinal direction and steel plate

shear walls in the transverse direction. The shear walls in this structure

carry about 60% of the tributary gravity load while the wide flange

columns at the boundary of shear walls resist the remaining 40%.

By using steel plate shear walls as gravity load carrying elements,

the designers have saved a significant amount of steel in beams and

columns and compared to equivalent steel moment resisting frame, the

steel shear wall system has used 1/3 less steel (Troy and Richard, 1988).

Located in Dallas, the wind loads were the governing lateral loads.

Under the design wind load, maximum drift was only 0.0025. The

relatively low drift is due to relatively high in-plane stiffness of steel

plate shear walls. Figure 2.4 shows a view of the building.

Steel plate shear wall

15

4.A 6-story hospital in Los Angeles, California

This structure shown in Figure 2.5 is a good example of the

use of steel shear walls in an “important” structure such as a hospital

in an area of very high seismicity such as California. The hospital

building is a replacement for the reinforced concrete Olive View

Hospital that had partially collapsed during the 1971 San Fernando

earthquake and had to be demolished.

In the new Sylmar Hospital, shown in Figure 2.5, the gravity load is

resisted entirely by a steel space frame and the lateral load is resisted by

the reinforced concrete shear walls in the first two stories and steel plate

shear walls in the upper four stories. The steel shear wall panels in this

building are 25 ft wide and 15.5 feet high with thickness of wall plate

being 5/8” and ¾”.

Steel plate shear wall

16

The walls have window openings in them and stiffeners as shown

in Figure 2.6. The steel plate panels are bolted to the fin plates on the

columns. The horizontal beams as well as the stiffeners are double

channels welded to the steel plate to form a box shape as shown in

Figure 2.6. According to the designers, (Youssef, 2000) and (Troy and

Richard, 1988) the double channel box sections were used to form

torsionally stiff elements at the boundaries of steel plates and to increase

buckling capacity of the plate panels.

The walls were designed for global buckling capacity of the

stiffened walls as well as local buckling capacity of the panels bounded

by the stiffeners. The tension field action capacity was not used although

the designers acknowledge its presence and consider the strength of

tension field action as a “second line of defense” mechanism in the event

of a maximum credible earthquake.

Steel plate shear wall

17

5.A 35-story office building in Kobe, Japan

One of the most important buildings with steel plate shear walls

in a very highly seismic area is the 35-story high-rise in Kobe, Japan.

The structure was constructed in 1988 and was subjected to the 1995

Kobe earthquake. The structural system in this building consists of a

dual system of steel moment frames and shear walls. The shear walls in

the three basement levels are reinforced concrete and in the first and

second floors the walls are composite walls and above the 2nd floor the

walls are stiffened steel shear walls. Figure 2.9 shows framing plan and

typical frames. The author visited this building about two weeks after

the 1995 Kobe earthquake and found no visible damage.

Steel plate shear wall

18

6.A 52-story residential building in San Francisco,

California

Currently, the tallest building with steel plate shear walls in a very

highly seismic area of the United States is a 52-story building in San

Francisco. The structure is designed by Skilling, Ward, Magnusson,

Barkshire of Seattle and is currently under construction. The building is

a residential tower and when completed will have 48 stories above

ground and four basement parking levels. A rendering of the building

and a typical floor plan are shown in Figure 2.12.

Steel plate shear wall

19

The gravity load carrying system in this building consists of four

large concrete-filled steel tubes at the core and sixteen concrete-filled

smaller steel tube columns in the perimeter. The floors outside the core

consist of post-tensioned flat slabs and inside the core and lower floors

are typical composite steel deck-concrete slab. The foundation consists

of a single reinforced concrete mat foundation.

The main lateral load resisting system of the structure consists of a

core made of four large concrete field steel tubes, one at each corner of

the core, and steel shear walls and coupling beams. There are built-up H

columns between the two corner pipe columns. The steel shear walls

are connected to concrete filled steel tubes by coupling beams. The shear

wall units are primarily shop-welded and bolt spliced at the site at each

floor mid-height. The only field welding is the connection of the girders

and steel plate shear wall to the large concrete-filled steel tube columns.

Steel plate shear wall

20

7. A 22-story office building in Seattle, Washington

A view of this building is shown in Figure 2.13. At this writing,

(summer of 2000) the structure is being designed by Skilling Ward

Magnusson Barkshire. A typical floor framing consists of typical steel

deck/concrete floors supported on wide flange beams and columns.

The lateral load resisting system consists of a core with four

large concrete filled tubes on its corners and steel plate shear walls and

coupling beams connecting the tubes to each other in one direction and

steel braced frame in the other.

Similar to the 52-story structure discussed in previous section, the

steel plate shear wall system in this building also is primarily shop-

welded, field bolted with only steel plates and girders welded to the

round columns in the field. Four round concrete-filled tubes carry the

bulk of gravity in the interior of the building. The I-shaped columns

within the steel box core do not participate in carrying gravity and are

primarily part of the lateral load resisting system which can be

considered to be a dual system of steel shear wall and special moment-

resisting frames.

Steel plate shear wall

21

6. ANALYSIS AND DESIGN APPROACH

The typical SPSW system is comprised of steel plate panels,

vertical boundary elements, and horizontal boundary elements.

The general procedure in the design of the SPSW system is as follows:

1. Gravity Framing:

The building frames, including the SPSW boundary elements, should

be designed to carry gravity loadings while neglecting the contribution

of the SPSW panels. This is an important factor, done to ensure that the

building frames have sufficient capacity to support the gravity loads

during seismic events, during which the plate experiences buckling due

to the development of its tension field action

2. Steel Plate Panel:

The steel plate panel is designed to handle both wind and seismic

loads. All lateral shear loads in the SPSW panel are resisted by the steel

plate, utilizing tension- field action. There are many different approaches

that can be used to analyze the plate. The most common approach is the

tension-field strut model, oriented in the direction of the tension field

“a.” Plate elements with orthotropic properties oriented in the “a”

direction may be used in the lateral model as a substitute for the struts.

These tension struts are designed as tension members. This approach is

represented by the following equation:

.

Where:

L = steel plate panel length

h = steel plate panel height

w = steel plate thickness

Ac, Ic = vertical boundary

element member

area and moment of inertia

Ab = horizontal boundary

element member area.

member area

Steel plate shear wall

22

The suggested maximum height/length aspect ratio (h/L) is 1. A

large height/length ratio means the vertical boundary elements’ stiffness

and capacity will have more influence on the system quality. The

suggested minimum length/thickness ratio is 180. Thicker plates will

delay the development of tension-field action.

3. Boundary Elements:

The boundary elements are very important to the proper

performance of SPSW systems. For boundary elements with plate walls

on one side only (edge boundary elements), the boundary element

should be designed based on the capacity of the steel plate wall. This

demand is based on the panel’s aspect ratio, the steel plate’s thickness,

and the steel plate’s expected strength.

The vertical boundary elements, whether built-up or comprised of

standard “W” shapes, should meet the AISC compactness criteria.

4. Hinging Sequence:

The desirable hinging sequence for the SPSW system is as follows:

1. Steel plate walls

2. Coupling beams

3. Horizontal boundary elements

4. Vertical boundary elements

Steel plate shear wall

23

7. CONSRUCTION CONSIDERATIONS

There are several important factors that need to be considered by

the engineer in order to produce good SPSW behavior and an efficient

construction process.

1. SPSW Fabricated Panel Size and Details.

SPSW panels can consist of large steel panels with low out-of-

plane stiffness, which can create difficulties for stick building/erection

of the system. The engineer should plan the panel segment size and

details to mitigate this construction issue. Sufficient out-of-plane

stiffness should be provided.

2. Careful Construction Sequence Plan.

The engineer, with assistance from the contractor, should plan the

construction sequence to alleviate gravity-load induced axial

compression in the steel plate panels. Axial pre-compression in the steel

plate wall may delay the development of the tension-field action. One

Approach to overcome this is to delay the tightening/fixing of the steel

plate splice connection. This will allow shortening of the vertical

elements prior to fixing the steel plate splice

3. Stability during Construction.

One of the advantages of using the SPSW system is speed of

Construction. The engineer needs to make sure that the assembled

system has sufficient out-of-plane stiffness during construction. The

SPSW has less out-of-plane stiffness in comparison to a concrete wall.

Steel plate shear wall

24

REFERENCES

1. “Steel plate shear wall: practical design and construction”

By Ignasius F. Seilie, P.E. and John D. Hooper, P.E.,

Published in The steel conference.

2. “Seismic Behavior and Design of Steel Shear Walls”

By Abolhassan Astaneh-Asl, Ph.D., P.E.

Professor Department of Civil and Environmental Engineering

University of California, Berkeley.

Published in structural steel educational council.

3. “seismic Behaviour and Design of composite shear wall”

By Abolhassan Astaneh-Asl, Ph.D., P.E.

Professor Department of Civil and Environmental Engineering

University of California, Berkeley.

Published in structural steel educational council.