  • Stator Earth Fault Protection100 % Protection RangeDr. Hans-Joachim Herrmann

    Power Transmission and Distribution

  • Copyright Siemens Siemens. Innovation for generations.

    Content

    Basics of stator earth fault protection Fault locations Disturbances from the high voltage side

    100%-stator-earth-fault protection with 20-Hz-injection method Basic idea Practical design Numerical measuring technique Frequency operating range

    Design of the protection schemes

    Examples of real practical failures

  • Copyright Siemens Siemens. Innovation for generations.

    Basics of Stator Earth Fault ProtectionFault Location

    Region of earth faults Earth fault locations in the stator

    U0

    Low displacement voltage at earth faults close to the star point

  • Copyright Siemens Siemens. Innovation for generations.

    Basics of Stator Earth Fault ProtectionDisturbances from the High Voltage Side

    An additional load resistor limits the disturbance influence The design of the load resistor determines the protective range

    (80% or 90 % or 95%)

  • Copyright Siemens Siemens. Innovation for generations.

    100%-Stator-Earth-Fault Protection with 20-Hz-Injection Method Goal and Basic Idea

    Goal

    Protection principle should cover 100 % protection range

    Different measuring principles

    20 HzRE

    max.200 V

    I

    Basic idea

    With injection of a 20-Hz-voltage into the star point a e.m.f. is available in case of an earth fault

  • Copyright Siemens Siemens. Innovation for generations.

    100%-Stator-Earth-Fault Protection with 20-Hz-Injection Method Practical Design

    The protection measures the injected 20-Hz-voltage and current

    Two connectionsare possible

  • Copyright Siemens Siemens. Innovation for generations.

    100%-Stator-Earth-Fault Protection with 20-Hz-Injection Method Numerical Measuring Technique

    Replica:isSEF

    iSEF VSEF

    20HzRE RBCERE = Fault resistance

    CE = Ground capacitance in stator circuit

    VSEF

    iSEF

    1) Filtering

    3) Impedance replica of fault 4) Calculation of fault resistor from 2) and 3)

    2) Calculation of the real part

    Yers CE RE Yers =1

    RE+ j CE RE =

    V2r + V2iVr . Ir + Vi . Ii

    ReVr . Ir + Vi . Ii

    V2r + V2i

    Fourierfilter(20Hz)

    V20 = Vr + jViI20 = Ir + jIi

    =

    20

    20VI

  • Copyright Siemens Siemens. Innovation for generations.

    100%-Stator-Earth-Fault Protection with 20-Hz-Injection Method Relay Settings (secondary values)

    Two StagesBackupovercurrentSupervision

    Calibration

    Primary fault resistances:1 to 3 k Trip stage5 to 8 k Alarm stage

  • Copyright Siemens Siemens. Innovation for generations.

    100%-Stator-Earth-Fault Protection with 20-Hz-Injection Method Frequency Operating Range

    Stand still Rated frequency

    Protection uses a frequency tracking for all protection functions 20-Hz-generator is activated before starting the generator Due to disturbances from zero sequence system during starting (e.q. static

    frequency converter) or braking of the generator an internal blocking avoids an overfunction of the injection method

    100%-Stator earth fault protection with 20 Hz injection

    0Hz 10Hz 40Hz 70Hz

    90% Stator earth fault protection with displacement voltage

    50Hz

  • Copyright Siemens Siemens. Innovation for generations.

    Design of the Protection SchemesApplication used in Three Gorges

    100% stator earth fault protection

    90% stator earth fault protection

    Option:90% stator earth fault protection with calculated U0

  • Copyright Siemens Siemens. Innovation for generations.

    Design of the Protection SchemesRedundancy of 100%-Stator Earth Fault Protection

    Neutral

    transformer

    7UM62

    UL

    UE

    IEE1

    7UM62

    UL

    UE

    IEE1

    Group1 Group2

    100% SEF-2

    100% SEF-1

    90% U0calculated

    90% U0calculated

  • Copyright Siemens Siemens. Innovation for generations.

    CommissioningPrimary Tests on a Generator (stand still and running)

    The secondary signals are very small

    The capacitivecurrent is visible.This disturbance current will be eliminated by the algorithm.

    Phase to groundvoltage

    Displacementvoltage

    Ground current

  • Copyright Siemens Siemens. Innovation for generations.

    Real Practical FailuresExternal insulation test equipment failed

  • Copyright Siemens Siemens. Innovation for generations.

    Real Practical FailuresCalculated Secondary Fault Resistance

    100 200 300 400 500 600 7000

    50

    100

    150

    200

    ResistanceTripPickup

    t in ms

    R

    i

    n

    O

    h

    m

    200

    0

    60

    86

    REmk

    SES100Ausk

    GAnrk

    687.5100 k ta.

    Pickup

    Drop off

  • Copyright Siemens Siemens. Innovation for generations.

    Real Practical FailuresEarth Fault in the Cable of Static Frequency Converter

    Starting of the generator withstatic frequency converterSFC

    G

    Permanently pickup by 100%-stator earth fault protection

  • Copyright Siemens Siemens. Innovation for generations.

    Real Practical FailuresEarth Fault in the Cable of Static Frequency ConverterFault Record

    Inputsignalsof the100%SEF

    frequency appr. 1,7 Hz

  • Copyright Siemens Siemens. Innovation for generations.

    Real Practical FailuresEarth Fault in the Cable of Static Frequency Converter Calculated Secondary Fault Resistance

    0 100 200 300 400 500 600 7000

    20

    40

    60

    80

    100

    ResistanceTripPickup

    t in ms

    R

    i

    n

    O

    h

    m

    100

    0

    48

    57REmk 10

    SES100Ausk

    GAnr k

    686.9599.92 k ta

    Drop off

    Pickup