1 air conditioning evaporators for air conditioning

39
1 Air Conditioning Evaporators For Air Conditioning

Upload: charlotte-oliver

Post on 23-Dec-2015

326 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: 1 Air Conditioning Evaporators For Air Conditioning

1

Air ConditioningAir Conditioning

Evaporators For Air Conditioning

Evaporators For Air Conditioning

Page 2: 1 Air Conditioning Evaporators For Air Conditioning

2

EvaporatorsEvaporators

• Discussed in much more detail in HVACR312 the refrigeration term.

• In air conditioning there are two primary types of evaporators used:– Natural Draft– Forced Convection

• Discussed in much more detail in HVACR312 the refrigeration term.

• In air conditioning there are two primary types of evaporators used:– Natural Draft– Forced Convection

Page 3: 1 Air Conditioning Evaporators For Air Conditioning

3

Natural DraftNatural Draft

Page 4: 1 Air Conditioning Evaporators For Air Conditioning

4

Forced DraftForced Draft

Page 5: 1 Air Conditioning Evaporators For Air Conditioning

5

Operating DesignOperating Design

• Direct Expansion– Refrigerant directly cools the air. The evaporator

coil is full of refrigerant and air is blowing across the coil.

• Direct Expansion– Refrigerant directly cools the air. The evaporator

coil is full of refrigerant and air is blowing across the coil.

Page 6: 1 Air Conditioning Evaporators For Air Conditioning

6

Operating DesignOperating Design

• Indirect expansion– Refrigerant cools secondary medium, such as

water or glycol.– The secondary medium flows through a coil in

the air stream and that cools the space.

• Indirect expansion– Refrigerant cools secondary medium, such as

water or glycol.– The secondary medium flows through a coil in

the air stream and that cools the space.

Page 7: 1 Air Conditioning Evaporators For Air Conditioning

7

Indirect ExpansionIndirect Expansion

Page 8: 1 Air Conditioning Evaporators For Air Conditioning

8

Operating DesignOperating Design

• Two types of Direct Expansion coils exist:– Dry Type– Flooded Type

• Two types of Direct Expansion coils exist:– Dry Type– Flooded Type

Page 9: 1 Air Conditioning Evaporators For Air Conditioning

9

Dry TypesDry Types

• Use 25% less refrigerant than the flooded type.

• Have more vapor in the evaporator• Have less chance of floodback to the

compressor.

• Use 25% less refrigerant than the flooded type.

• Have more vapor in the evaporator• Have less chance of floodback to the

compressor.

Page 10: 1 Air Conditioning Evaporators For Air Conditioning

10

Dry TypeDry Type

• The disadvantages of the dry type coil are:– Slower pull-down with heavy loads– System runs with higher head pressures.

• The disadvantages of the dry type coil are:– Slower pull-down with heavy loads– System runs with higher head pressures.

Page 11: 1 Air Conditioning Evaporators For Air Conditioning

11

Evaporator PurposeEvaporator Purpose

• There are two purposes of evaporators:– Cooling– Dehumidification

• There are two purposes of evaporators:– Cooling– Dehumidification

Page 12: 1 Air Conditioning Evaporators For Air Conditioning

12

CoolingCooling

• Changes the sensible heat content in the air.

• This you can actually measure.

• Changes the sensible heat content in the air.

• This you can actually measure.

Page 13: 1 Air Conditioning Evaporators For Air Conditioning

13

DehumidificationDehumidification

• Dehumidification changes the latent heat and the moisture in the air.

• This is the process described in the psychometric chart.

• Must keep indoor humidity under 50%.

• Dehumidification changes the latent heat and the moisture in the air.

• This is the process described in the psychometric chart.

• Must keep indoor humidity under 50%.

Page 14: 1 Air Conditioning Evaporators For Air Conditioning

14

Evaporator DesignEvaporator Design

• Most often done by mechanical engineers.• You will have a catalogue to choose

evaporator and condenser combinations based on cooling requirements and size.

• Most often done by mechanical engineers.• You will have a catalogue to choose

evaporator and condenser combinations based on cooling requirements and size.

Page 15: 1 Air Conditioning Evaporators For Air Conditioning

15

Design FactorsDesign Factors

• There are several factors looked at for evaporator design:– Pressure Drop– Evaporator Capacity

• There are several factors looked at for evaporator design:– Pressure Drop– Evaporator Capacity

Page 16: 1 Air Conditioning Evaporators For Air Conditioning

16

Design FactorsDesign Factors

• Causes of pressure drop:– Long evaporators

• Not actual size, but the length of a run.• Solved by multiple evaporator circuits.

– Tubing too small

• Causes of pressure drop:– Long evaporators

• Not actual size, but the length of a run.• Solved by multiple evaporator circuits.

– Tubing too small

Page 17: 1 Air Conditioning Evaporators For Air Conditioning

17

Design FactorsDesign Factors

Page 18: 1 Air Conditioning Evaporators For Air Conditioning

18

Poor Evaporator DesignPoor Evaporator Design

• Low Gas Velocity– Poor oil return– No “scrubbing” effect, refrigerant debris build up

in evaporator tubes.– Oil clogged evaporator

• Low Gas Velocity– Poor oil return– No “scrubbing” effect, refrigerant debris build up

in evaporator tubes.– Oil clogged evaporator

Page 19: 1 Air Conditioning Evaporators For Air Conditioning

19

Evaporator CapacityEvaporator Capacity

• Factors that effect evaporator capacity:– Surface Area– Temperature Difference– Refrigerant Velocity– Conductibility (How fast heat moves through

metal)– Metal thickness– Air Volume

• Factors that effect evaporator capacity:– Surface Area– Temperature Difference– Refrigerant Velocity– Conductibility (How fast heat moves through

metal)– Metal thickness– Air Volume

Page 20: 1 Air Conditioning Evaporators For Air Conditioning

20

SuperheatSuperheat

Page 21: 1 Air Conditioning Evaporators For Air Conditioning

21

SuperheatSuperheat

• A sensible heat added to the vapor refrigerant after the change of state has taken place.

• The difference between the boiling refrigerant and the suction line temperature.

• A sensible heat added to the vapor refrigerant after the change of state has taken place.

• The difference between the boiling refrigerant and the suction line temperature.

Page 22: 1 Air Conditioning Evaporators For Air Conditioning

22

SuperheatSuperheat

• Is used to check if the evaporator has proper level of refrigerant.

• Superheat is gained in the evaporator – refrigerant picks up additional sensible heat after the change in state takes place.

• Is used to check if the evaporator has proper level of refrigerant.

• Superheat is gained in the evaporator – refrigerant picks up additional sensible heat after the change in state takes place.

Page 23: 1 Air Conditioning Evaporators For Air Conditioning

23

SuperheatSuperheat

Page 24: 1 Air Conditioning Evaporators For Air Conditioning

24

SuperheatSuperheat

• Normal superheat is between 8-12 degrees for a TXV system.– Depending on the application this can be much

lower or higher.

• If the superheat is high– Starved coil– Low refrigerant

• Normal superheat is between 8-12 degrees for a TXV system.– Depending on the application this can be much

lower or higher.

• If the superheat is high– Starved coil– Low refrigerant

Page 25: 1 Air Conditioning Evaporators For Air Conditioning

25

SuperheatSuperheat

• If the superheat is low– Flooded coil– To much refrigerant

• DO NOT ADJUST REFRIGERANT WITH JUST SUPERHEAT UNLESS YOU ARE SURE THAT YOU KNOW HOW THE SYSTEM SHOULD WORK!

• If the superheat is low– Flooded coil– To much refrigerant

• DO NOT ADJUST REFRIGERANT WITH JUST SUPERHEAT UNLESS YOU ARE SURE THAT YOU KNOW HOW THE SYSTEM SHOULD WORK!

Page 26: 1 Air Conditioning Evaporators For Air Conditioning

26

SuperheatSuperheat

• Complete vaporization of refrigerant should occur around the last bend of the evaporator.

• Any additional heat absorbed is now referred to as superheat.

• The TXV as a metering device is designed to maintain proper superheat.

• Complete vaporization of refrigerant should occur around the last bend of the evaporator.

• Any additional heat absorbed is now referred to as superheat.

• The TXV as a metering device is designed to maintain proper superheat.

Page 27: 1 Air Conditioning Evaporators For Air Conditioning

27

Measuring superheatMeasuring superheat

• Take the temperature of the suction line with a thermometer.– Best to do within 6 inches of the evaporator.

• Take the suction pressure and convert to the temperature of saturation.

• Take the temperature of the suction line with a thermometer.– Best to do within 6 inches of the evaporator.

• Take the suction pressure and convert to the temperature of saturation.

Page 28: 1 Air Conditioning Evaporators For Air Conditioning

28

Measuring SuperheatMeasuring Superheat

• Subtract the saturation temperature from the suction line temperature.

• Example:– R22 system– Suction Pressure is 68.5psi (40 degrees)– Suction line temp is 50 degrees– 50 – 40 = superheat of 10 degrees

• Subtract the saturation temperature from the suction line temperature.

• Example:– R22 system– Suction Pressure is 68.5psi (40 degrees)– Suction line temp is 50 degrees– 50 – 40 = superheat of 10 degrees

Page 29: 1 Air Conditioning Evaporators For Air Conditioning

29

Measuring SuperheatMeasuring Superheat

• Add 2 psi to your suction line if:– Condenser is in remote location.– Suction line is well over 8 feet.– You are working on a split system.

• Add 2 psi to your suction line if:– Condenser is in remote location.– Suction line is well over 8 feet.– You are working on a split system.

Page 30: 1 Air Conditioning Evaporators For Air Conditioning

30

Trouble shooting with superheatTrouble shooting with superheat• Domestic and commercial units:– 8 to 12 degrees of superheat is the rule of

thumb.

• Whatever must be done to superheat the opposite must be done to the refrigerant.

• Domestic and commercial units:– 8 to 12 degrees of superheat is the rule of

thumb.

• Whatever must be done to superheat the opposite must be done to the refrigerant.

Page 31: 1 Air Conditioning Evaporators For Air Conditioning

31

Troubleshooting with superheatTroubleshooting with superheat

• If you have a superheat of 20 degrees– Superheat must be lowered– Increase refrigerant charge (or flow).

• If you have a superheat of 2 degrees– Superheat must be raised– Decrease refrigerant charge (or flow).

• If you have a superheat of 20 degrees– Superheat must be lowered– Increase refrigerant charge (or flow).

• If you have a superheat of 2 degrees– Superheat must be raised– Decrease refrigerant charge (or flow).

Page 32: 1 Air Conditioning Evaporators For Air Conditioning

32

Troubleshooting with superheatTroubleshooting with superheat

• Anytime you make a superheat adjustment you must wait 10 to 15 minutes prior to making next adjustment.

• This wait is so the system will stabalize.

• Anytime you make a superheat adjustment you must wait 10 to 15 minutes prior to making next adjustment.

• This wait is so the system will stabalize.

Page 33: 1 Air Conditioning Evaporators For Air Conditioning

33

Superheat Superheat

• With a fixed orifice metering device or a cap tube:– Adding charge lowers superheat– Removing charge raises superheat

• With a fixed orifice metering device or a cap tube:– Adding charge lowers superheat– Removing charge raises superheat

Page 34: 1 Air Conditioning Evaporators For Air Conditioning

34

Additional NotesAdditional Notes

• The difference between the temperature of the refrigerant boiling in the evaporator and the temperature at the evaporator outlet is known as the evaporator superheat.

• The difference between the temperature of the refrigerant boiling in the evaporator and the temperature at the evaporator outlet is known as the evaporator superheat.

Page 35: 1 Air Conditioning Evaporators For Air Conditioning

35

Additional NotesAdditional Notes

• When measuring evaporator superheat on a commercial system with a long suction line the pressure reading should be taken at the evaporator outlet, not the compressor inlet.

• When measuring evaporator superheat on a commercial system with a long suction line the pressure reading should be taken at the evaporator outlet, not the compressor inlet.

Page 36: 1 Air Conditioning Evaporators For Air Conditioning

36

Additional NotesAdditional Notes

• Superheat measurements are best taken with the system operating at design conditions.

• Superheat measurements are best taken with the system operating at design conditions.

Page 37: 1 Air Conditioning Evaporators For Air Conditioning

37

Additional notesAdditional notes

• Evaporators can by multi-pass. This means the coil has been folded over on itself or is actually 2 or three coils clamped together and fed by a distributor.

• Evaporators can by multi-pass. This means the coil has been folded over on itself or is actually 2 or three coils clamped together and fed by a distributor.

Page 38: 1 Air Conditioning Evaporators For Air Conditioning

38

Additional NotesAdditional Notes

• When an evaporator coil is multi pass and has a superheat that is higher than others this can be caused by un-even air distribution, a blocked distributor, or even a dirty coil section.

• When an evaporator coil is multi pass and has a superheat that is higher than others this can be caused by un-even air distribution, a blocked distributor, or even a dirty coil section.

Page 39: 1 Air Conditioning Evaporators For Air Conditioning

39

Additional NotesAdditional Notes

• Evaporators that are used to chill liquids, like the ones found in slurpey machines and soda dispensers can have a normal superheat measurement but not be cooling properly. This is caused by deposits built up on the liquid side of the evaporator or poor circulation of the liquid.

• Evaporators that are used to chill liquids, like the ones found in slurpey machines and soda dispensers can have a normal superheat measurement but not be cooling properly. This is caused by deposits built up on the liquid side of the evaporator or poor circulation of the liquid.