06. areva p740

30
740 Technical Data Sheet EN 1 MICOM P740 Numerical Busbar Protection Software Version 40 Hardware Suffix J OR K Technical Data Sheet P740/EN TD/K55 This Document does not replace the Technical Manual

Upload: nandha-kumar

Post on 08-Mar-2015

562 views

Category:

Documents


31 download

TRANSCRIPT

Page 1: 06. AREVA P740

740 Technical Data Sheet EN

1

MICOM P740

Numerical Busbar Protection

Software Version 40 Hardware Suffix J OR K

Technical Data Sheet P740/EN TD/K55

This Document does not replace the Technical Manual

Page 2: 06. AREVA P740
Page 3: 06. AREVA P740

The MiCOM P740 numerical busbar protectionscheme provides complete protection for allvoltages level up to extra / ultra voltage busbarconfigurations.

Innovative techniques, including CT supervisionand saturation detection and dynamic topologyprocessing algorithms, offer a uniquecombination of security, speed and sensitivity.

With a typical operating time of 11-15ms, theP740 protection is one of the fastest in its classand meets the most stringent requirements oftransmission systems.

Fully communicant with IEC61850-8-1 andIEC103 protocols, the P740 is easily integrated in any substation system.

The substation replica processing algorithmsensure that the P740 adapts to the dynamicallychanging topology of the busbar which isdisplayed on any PC with the substation real timedynamic monitoring tool.

The MiCOM P740 busbar differential protectionscheme can be engineered to provide acentralised or distributed architecture. It alsosupports easy maintenance, operation and futureexpansion of the busbar.

Customer benefits• Fast fault trip

(typically 11-15ms)• Adaptable to any busbar

configuration • IEC61850-8-1 compliant• Can operate with different

types of CT.• Programmable function keys

& hotkeys• Flexible tri-colour LEDs• Fibre optic intercommunication:

- Ensures high communicationspeed

- Eliminates insulation problems

AREVA T&D

MiCOM P740 Numerical Busbar Protection

PROTECTION

MiCOM P741 in 80TE

MiCOM P743in 60TE

MiCOM P742 in 40TE

Page 4: 06. AREVA P740

APPLICATION

The MiCOM P740 numerical busbar protection schemehas been designed to protect a wide range of busbarconfigurations. The modular scheme utilises threerelay types:

• Central Unit (CU) - P741

• Peripheral Unit (PU) - P742 / P743These units interconnect using fibre optic cables andtogether with the topology configurator software, allowapplication to all types of busbar configuration.

The Central Unit co-ordinates the scheme, receivingsignals from all the peripheral units associated with theprotected busbars and acting on these signals, initiatesa buszone protection trip when necessary. A singleCentral Unit can accommodate up to,

• 8 Zones

• 28 Peripheral Units

One Peripheral Unit is associated with each CT location, usually one per incomer/feeder and oneor two for each bus coupler/bus section, depending onthe number of CTs. The Peripheral Units acquire theanalogue signals from the associated CT and thebinary signals from the auxiliary contacts of the circuitbreakers and isolators. The Peripheral Units alsoincorporate the main circuit breaker failure logictogether with additional protection functions (Deadzone, overcurrent, etc.).

The P743 allows for increased opto inputs, functionkeys and ethernet board option and is particularlyuseful in double busbar applications. Additionally,where single pole breakers and transfer busbars areemployed, the I/O requirements are large incomparison to those required for a single busbarapplication, where a P742 may be more suitable.

2>3

Complete flexibility to suitany busbar configuration

P740 schemeapplied for protectingdouble busbar with transfer bus

CentralUnit

P741

2 P742 or2 P743

BB5

BB2 BB4

P743P743 P742P742P742P742 P742 P742

Fibre OpticPeripheralUnits

PeripheralUnits

Fibre Optic

ANSI IEC 61850 P741 P742 P743

87BB / P PhsPDIF Phase segregated biased current • - -differential high speed busbar protection

87CZ / P CzPPDIF Check Zone segregated biased phase current • - -differential high speed busbar protection

87BB / N NeuPDIF Sensitive earth fault bias current controlled busbar protection • - -87 CZ / N CzNPDIF Check Zone segregated biased earth current • - -

differential high speed busbar protection busbar protection 50 / 51 / P OcpPTOC Phase overcurrent protection (2 stages) - • •50 / 51 / N EfmPTOC Earth overcurrent protection (2 stages) - • •50ST / P DzPhsPTOC Dead zone phase protection - • •

(short zone between CTs and open CBs)50ST / N DzpEfmPTOC Dead zone earth protection - • •

(short zone between CTs and open CBs)CTS Current transformer supervision • • •50BF RBRF Breaker failure protection (LBB) • • •

ISL Isolator discrepancy alarm - • •Fibre optic signalling channel • • •

OptGGIO Digital inputs 8 16 24RlyGGIO Output relays 8 8 16

Virtual Digital inputs (via fibre communication) 16 16 16Virtual Output relays (via fibre communication) 16 16 16Front communication port (RS232) • • •Rear communication port (Kbus/EIA(RS)485) • • •Rear communication port (Ethernet) * Option - OptionTime synchronisation port (IRIG-B) * Option - -

FnkGGIO Function keys 10 - 10LedGGIO Programmable tri-colour LEDs 18 - 18

* Refer data sheet for model selection

Protection Functions Overview

Page 5: 06. AREVA P740

MANAGEMENT FUNCTIONS

In addition to the protection and control elements, theP740 scheme provides a wide range of measurement,monitoring, post fault analysis and self-diagnosticfeatures:

• Circuit breaker control

• Trip circuit supervision (using PSL)

• On-line measurement

• Plant status monitoring

• 4 alternative setting groups

• Programmable scheme logic (PSL)

• Sequence of event recording (SOE)

• Comprehensive Fault record (including topology)

• Comprehensive disturbance recording (waveformcapture)

• User configurable function keys & hotkeys

• User configurable tri-colour LEDs

• Local and remote communication ports

• Time synchronisation

• Fully customisable menu texts

• Multi level password protection

• Test facilities

• Power-up diagnostics and continuous self-monitoringof relay.

• User friendly setting, analysis and monitoringsoftware

Fast, Sensitive & Secure: P740 the ultimate in busbar protection

X

/

/

/ /

Fault records

Measurements

PSL

Local Communication

Remote comm. port

Busbar protection scheme Peripheral Unit P742 / P743

LEDsBinaryInput / output

Self monitoring

50/51/P

50/51/N

Disturbance Record

Fibre optic signaling channel

50BF50ST CTS

Fault records

Measurements

PSL

Local Communication

Remote comm. port

Busbar protection scheme Central Unit P741

LEDsBinaryInput / output

Self monitoring

87BB/ P

87BB/ N

87CZ / N

87CZ / P

Disturbance Record

Fibre optic signaling channel

50BF CTS

ISL

FUNCTIONAL OVERVIEW

(Description of ANSI code nos. see Protection Function Overview)

Page 6: 06. AREVA P740

The P740 employs biased differential algorithms, inwhich the differential current is compared with a biascurrent. This characteristic ensures stability of theprotection for external faults even with differing CTtolerance and errors which could lead to spuriousoperation.

To increase the security of the differential protection,the biased differential element is supervised by abiased global check zone element. This ensuresstability even under erroneous status of the auxiliarycontact of plant isolators and circuit breakers.

The MiCOM P740 also employs CT supervision andan innovative, ultra high-speed, secure CT saturationdetection algorithm. This ensures stability when CTsbecome saturated, particularly under external faultconditions. This algorithm combines a simulation of the flux built up in the core of the CTs with a recursiveconsistence variation control. This technique candetect CT saturation in less than 2ms.

4>5

Universal on-line topology processing

Bias differential characteristics

CT saturation detection

To ensure adaptability of the relay to any type ofbusbar configuration the P740 is built with a universaltopology processing algorithm. This algorithmdetermines the optimum tripping zone based on the current status of the plant isolators and circuitbreakers.

BUSBAR DIFFERENTIAL PROTECTION

The primary protection element of the P740 scheme is the phase segregated biased current differentialprotection. The technique is based on the numericalapplication of Kirchoff's Law for the selective detectionand ultra high-speed isolation of a faulty section of the busbar.

The analysis is carried out in the Central Unit (CU)which communicates with the Peripheral Unit (PU)to gather current information from individual circuits and to implement the tripping of circuits as required This reliable, high speed communication is achieved via a direct optical connection utilising a 2.5 Mbps data rate.

i (t)diff nodeDifferential current : = + + i n1 2 i i i 3 + ....... +

i (t)diffOperating current : = = i

i (t)bias i 1 i 2 i 3 i nBias current : = + + + ....... + = i n

i (t)diff node Σ

Σ

IDN>2

IDN>1

idiff (t)

iNbias (t)

IDNCZ>2

k2N = 0 to 90%

kN = 0 to 90%

kN1 = 0 to 50%

TrippingArea

RestrainArea

i 1

X

X X

X

i n

i 2

i 3ID>2

ID>1

idiff (t)

ibias (t)

IDCZ>2

k2 = 20 to 90%

k = 0 to 90%

k1 = 0 to 50%

TrippingArea

RestrainAreaX

Page 7: 06. AREVA P740

DUAL CHARACTERISTICS

To provide stability for severe through faults and at thesame time detect low current internal faults, the P740is equipped with dual characteristics. One phasesegregated differential protection and anothersensitive earth current differential protection.

MULTIPLE TRIPPING CRITERIA

The MiCOM P740 maintains the highest level ofstability under all conditions including hardwarefailure and incoherent signals applied from externalplant or generated by the power system. Any tripping order must therefore be made conditionalon the simultaneous occurrence of 7 to 9 criteria:

> Magnitude criteria; confirmation of two simultaneousthresholds per zone:• Exceeding the bias slope characteristic (k2)• Exceeding differential operating current threshold

(ID>2).> Check zone supervision

The zone element(s) are only permitted to trip if theorder is confirmed by the check zone element:• Exceeding the bias slope characteristic (kCZ)• Exceeding differential operating current threshold

(IDCZ>2)> Signal quality criteria:

• No CT saturation detected• Current variation detected on at least two

Peripheral Units (except for dead bus)> Time or angular criterion.

The measurement elements on 2 samples taken at1200 Hz. A first sample for the initial measurementand a second sample for trip confirmation.

> Local criteria (optional)The Peripheral Units can be set to only authorisetripping if there is confirmation by local overcurrentcriteria or undervoltage or zero sequenceovervoltage.

DEAD ZONE OR BLIND SPOT PROTECTION

The current transformers or the open breakerssurrounding the busbars define the limits of the mainzones. When a feeder circuit breaker is opened a deadzone or blind spot is created between the CB and the associated CT. The Peripheral Unit detects thiscondition automatically and provides protection for this zone also.One stage of definite time delayed overcurrent andearth fault protection is provided in each PeripheralUnit to provide this functionality

CONTINUOUS SUPERVISION OF CURRENT CIRCUITS

The P740 detects any abnormality in the current circuitby continuously monitoring it. Under normal operatingconditions the differential current will be negligible. Ananomaly is detected by a threshold, ID>1, which canbe set to alarm from 10 A primary.

DIFFERENTIAL CURRENT SETTING

When switching operations are carried out in thesubstation, incorrect topology replicas may occur. Inthis case, a differential current appears. The differentialelements of the MiCOM P740 are allowed to operateonly if the differential current reaches a threshold ID>2which is normally set above the highest load current.

ADDITIONAL ULTRA HIGH SPEEDEXTERNAL FAULT BLOCKING

Ultra high-speed through fault detection can be carriedout in each PU and can generate a control signal fromthe moment of the first sample (0.4 ms) to block theconnected zone before CT saturation.

Dual characteristics

PU1Feeder not connected

PU2Feeder not connected

CB opened

Isolator closed Isolator closed

CB opened

Dead ZoneDead Zone

BB1

IDN>2

IDN>1

idiff (t)

iNbias (t)

IDNCZ>2

k2 = 20 to 90%

k2N = 0 to 90%

kNCZ = 0 to 50%

kN1 = 0 to 50%

TrippingArea

RestrainArea

ID>2

ID>1

idiff (t)

ibias (t)

IDCZ>2

k2 = 20 to 90%

kCZ = 0 to 90%

k1 = 0 to 50%

TrippingArea

RestrainArea

SEF Block threshold

BlockEnable

Dead zone protection

Page 8: 06. AREVA P740

6>7

Programmable scheme logic editor(MiCOM S1)

PHASE OVERCURRENT AND EARTH FAULT PROTECTION

Two independent stages of phase overcurrent andearth fault protection is provided in the Peripheral Units.These elements provide additional protection for theindividual circuits. The two stages can be programmed as:

> First stage can be programmed as definite time (DT)delay or one of the nine inverse time (IDMT) curves(IEC/UK and IEEE/US).

> Second stage can only be programmed as definitetime.

CIRCUIT BREAKER FAILURE PROTECTION (LBB)

The P740 offers an in-built integrated solution forbreaker failure protection. This requires all PeripheralUnits to receive a duplication of the trip commandsgenerated in their associated bay. In general the Breaker Failure protection is executed ona per phase basis which involves the possibility ofreceiving tripping orders on a per pole basis.

The MiCOM P740 busbar protection scheme can alsowork in co-ordination with external breaker failureprotection relays. In this configuration, the receipt of an external breaker failure command results in trippingof all the adjacent circuit breakers, via the topologicalrecognition system knowing which breaker is connectedto which zone.

CURRENT TRANSFORMERMIXING CORRECTION

The MiCOM P740 can correct a mix between currenttransformer ratios over a very wide range up to 40. Its associated user interface provides a range between1 A and 30 000 A primary.

Since the current transformer ratings in a substationmay be of mixed ratios, the MiCOM P741 uses avirtual CT ratio equal to 1000/1, irrespective of thefeeder section concerned.

ISOLATION AND MAINTENANCEOPERATING MODE

For ease of operation or maintenance of the busbarprotection system, the Central Unit and the PeripheralUnits can receive specific commands designed toallow system testing or other intervention without anydanger of unwanted tripping.In the Central Unit, a centralised command to isolatethe busbars at two levels can be selectively applied perzone:

> Differential protection (87BB) blocked (measurementsactive and 87BB tripping deactivated).The Breaker Failure protection (50BF) remainsoperational.

> Differential protection (87BB) and Circuit BreakerFailure protection (50BF) blocked.The additional local protection functions(51, 51N, etc...) remain operational.

All the protections in the CU and the PUs (87BB, DeadZone, General 50BF, Local 50BF, O/C, etc…) can bealso blocked.

A selective two-level command may be appliedselectively for each Peripheral Units:

> Intervention on another bay protection formaintenance and testing:The local Breaker Failure protection (50BF) is blocked but the busbar protection remains in service.. PU in 50BF blocked mode

> Intervention on the PU for maintenance and testing:PU in Overhaul mode

PROGRAMMABLE SCHEME LOGIC

Powerful programmable scheme logic (PSL) allows theuser to customize the protection and control functions.It is also used to programme the functionality of theoptically isolated inputs, relay outputs and LEDindications (red or tri-colour). The programmablescheme logic comprises of gate logic and generalpurpose timers. The gate logic includes OR, AND andmajority gate functions, with the ability to invert theinputs and outputs, and provide feedback. Theprogrammable scheme logic is configured using thegraphical MiCOM S1 PC based support software.

PLANT STATUS AND MONITORING

Checks and monitoring of the plant status can bemade and an alarm raised for any discrepancycondition between the open and closed auxiliarycontacts of the isolators and circuit breakers. The Dynamic Synoptic software allows the user tomonitor the position of CBs and isolators in the busbarscheme, as well as currents, alarms, etc...

Page 9: 06. AREVA P740

MEASUREMENT AND RECORDING FACILITIES

The P740 series relays are capable of measuring and storing the values associated with a fault. All theevents, faults records and disturbance records are timetagged to 1 ms using an internal real time clock. Anoptional IRIG-B port is also provided for accurate timesynchronization. A lithium battery provides a back upfor the real time clock and all records in the event ofsupply failure.

MEASUREMENTS

The measurements provided, which may be viewed in primary or secondary values, can be accessed via the back lit liquid crystal display. They are alsoaccessible via the communication ports. The followinginstantaneous parameters can be viewed:

> Central unit (P741)• Differential current Idiff / phase / zone• Bias current Ibias / phase / zone• Check zone Idiff / phase

> Peripheral units (P742 & P743)• Phase currents IA IB IC• Neutral current IN• Sequence currents• Frequency

EVENT RECORDER

Up to 512 time tagged event records are stored inbattery backed memory, and can be extracted via thecommunication port or be viewed on the front paneldisplay.

FAULT RECORDER

Records of the last 5 faults are stored in the battery-backed memory of both the Central andPeripheral Units.

Each fault record includes:

> Indication of the faulty zone (CU + PU)

> Protection element operated

> Active setting group

> Fault duration

> Currents and frequency (PU)

> Faulty zone differential and bias current (CU)

> Topology at the fault occurence

DISTURBANCE RECORDER

The Central and Peripheral units of the P740 haveindependent disturbance recording facility. ThePeripheral Units can record 4 analogue and 32 digitalchannels, whereas the Central unit stores 8 analogueand 32 digital channels in addition to 1 time channel.

> Specific analogue channels• Check zone Ibias / Idiff (CU)• IA, IB, IC, IN (PU)

> Maximum duration of one record and number of records • 1.2s per record and 8 records (CU)• up to 10.5s per record and minimum of

50 records 1.5s (PU)

Disturbance records can be extracted from the relayvia the remote communications and saved in theCOMTRADE format. These records may be examinedusing MiCOM S1 or any other standard COMTRADEviewer.

Disturbance record viewed in MiCOM S1

Page 10: 06. AREVA P740

LOCAL AND REMOTE COMMUNICATIONS

Two communication ports are available as standard; a rearport providing remote communications and a front portproviding local communications. As option an Ethernet boardcan be added in the P741 and P743s to use the IEC61850-8-1protocol.

The front RS232 port has been designed for use withMiCOM S1, which fully supports functions within the relay by providing the ability to programme the settings off-line,configure the programmable scheme logic, extract and viewevent, disturbance and fault records, view the measurementinformation dynamically and perform control functions (using Courier protocol).

The default remote communications is Courier / RS 485 orK-bus and can be converted to IEC60870-5-103.

IEC 61850 is available when the optional Ethernet port is ordered. IEC 61850 offers high-speed data exchange, peer-to-peer communication, reporting, disturbance recordextraction and time synchronization.

DIAGNOSTICS

Automatic tests performed including power-on diagnostics andcontinuous self-monitoring ensures a high degree of reliability.The results of the self-test functions are stored in batterybacked memory. Test features available on the user interfaceprovide examination of input quantities, states of the digitalinputs and relay outputs. A local monitor port provides digitaloutputs, selected from a prescribed list of signals, including the status of protection elements.

HARDWARE

All models within the MiCOM P740 series relays include:

> A back-lit liquid crystal display

> LEDs(12 for the P742 and 18 tri-color for the P741 and P743)

> Function keys (P741 and P743)

> Hotkeys

> Optional Ethernet rear communication board (P741 & P743)

> Optional IRIG-B port (CU)

> RS232 (front port) & RS485 / K-bus (rear port)

> Fibre optic connection from the CU to the PUs

> Download/monitor port

> Battery (supervised)

> N/O and C/O watchdog contacts

> Supervised +48 V field voltage

> Dual rated CT inputs 1A/5A

> Universal opto inputs with programmable voltage threshold

The optically isolated inputs are independent and may bepowered from the +48V field voltage.

Our policy is one of continuous development. Accordinglythe design of our products may change at any time. Whilstevery effort is made to produce up to date literature, thisbrochure should only be regarded as a guide and isintended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application ofany product referred to in it. We cannot be held responsiblefor any reliance on any decisions taken on its contentswithout specific advice.

AU

TOM

AT

ION

-L3-

P74

0-B

R-0

6.07

-129

5d-G

B -

© -

AR

EV

A -

200

7. A

RE

VA

, th

e A

RE

VA

logo

and

any

alte

rnat

ive

vers

ion

ther

eof

are

trad

emar

ks a

nd s

ervi

ce m

arks

of

AR

EV

A. M

iCO

M is

a r

egis

tere

d tr

adem

ark

of A

RE

VA

. A

ll tr

ade

nam

es o

r tr

adem

arks

men

tione

d he

rein

whe

ther

reg

iste

red

or n

ot,

are

the

prop

erty

of

thei

r ow

ners

.-

3891

9198

2 R

CS

PA

RIS

- P

rinte

d in

Fra

nce

- S

ON

OV

ISIO

N-I

TE

P

AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070

www.areva-td.com www.areva-td.com/protectionrelays

Device Track Record

>> Low impedance biased differential busbar protection, MBCZ, launched in 1988 and over 800 cubicles sold

>> Over 200 DIFB, medium impedance biased differential busbar protection scheme delivered since its launch in 1992.

>> Medium impedance biased differential busbar protection with linear currentcombination, DIFB CL, launched in 1996. Over 70 cubicles delivered.

>> Since the launch of the P740, over 300 systems have been delivered.

Page 11: 06. AREVA P740

P740 Technical Data Sheet EN 10 P740/EN TDS/K55

TECHNICAL DATA MECHANICAL SPECIFICATIONS

DESIGN

Modular MiCOM Px40 platform relay: P741: Size 16“ case (80TE) P742: Size 8“ case (40TE) P743: Size 12“ case (60TE) Mounting is front of panel flush mounting.

ENCLOSURE PROTECTION

Per IEC 60529: 1989 IP 52 Protection (front panel) against dust and dripping water, IPx2 except P741 – Protected against vertically falling drops of water with the product in 4 fixed positions of 15° tilt with a flow rate of 3mm/minute for 2.5 minutes.

WEIGHT

P741 with 7 comm. boards 7.4 kg with 1 comm board 6.2 kg P742 7.5 kg P743 9.2 kg

TERMINALS

AC Current and Voltage Measuring Inputs Located on heavy duty (black) terminal block: Threaded M4 terminals, for ring lug connection. CT inputs have integral safety shorting, upon removal of the terminal block.

General Input/Output Terminals For power supply, opto inputs, output contacts and COM1& COM2* rear communications. Located on general purpose (grey) blocks: Threaded M4 terminals, for ring lug connection. *: Optional copper & fibre Ethernet board.

Case Protective Earth Connection Two rear stud connections (2 P741, 1 P742/3), threaded M4. Must be earthed (grounded) using the protective (earth) conductor for safety, minimum earth wire size 2.5mm2.

Front Port Serial PC Interface EIA RS232 DTE, 9 pin D-type female connector. Courier protocol for interface to MiCOM S1 software. * PEB rated Maximum cable length 15m. Front Download/Monitor Port EIA RS232, 25 pin D-type female connector. For firmware downloads. * PEB rated circuitl.

Rear Communications Port K-Bus/EIA(RS485) signal levels, two wire Connections located on general purpose block, M4 screw. For screened twisted pair cable, multidrop, 1000m max. Courier protocol . * SELV rated circuit. Ethernet (copper & fibre)

Optional Rear Ethernet Connection for IEC 61850 10 BASE T / 100 BASE TX COMMUNICATIONS Interface in accordance with IEEE802.3 and IEC61850 Isolation: 1.5kV Connector type: RJ45 Cable type: Screened Twisted Pair (STP) Max. cable length: 100m 100 BASE FX INTERFACE Interface in accordance with IEEE802.3 and IEC61850 Wavelength: 1300nm Fiber: multi-mode 50/125µm or 62.5/125µm Connector style: BFOC 2.5 -(ST®) Optional Rear IRIG-B Interface modulated or un-modulated P741 only (P742 & P743 synchronised by the P741) BNC socket SELV rated circuit. 50 ohm coaxial cable.

Optical Fiber Connection BFOC 2.5 (ST®) interface for multi-mode glass fibre type 62.5/125µm, as per IEC 874-10, 850nm short-haul fibres, one Tx and one Rx. Optical budget: 5.6dB Data rate:2.5 Mbits Max Length: 1000m * PEB: Protective Equipotential Bonded * SELV: Safety/Separated Extra Low Voltage Both PEB and SELV circuits are safe to touch after a single fault condition.

Page 12: 06. AREVA P740

P740 Technical Data Sheet EN 11 P740/EN TDS/K55

RATINGS

AC Measuring Inputs Nominal frequency: 50 and 60 Hz (settable) Operating range: 45 to 65Hz Phase rotation: ABC or ACB

AC Current Nominal current (In): 1 and 5 A dual rated. (1A and 5A inputs use different transformer tap connections, check correct terminals are wired). Nominal burden per phase 1 A: <0.04VA at rated current Impedance per phase 1 A: <40mΩ over 0 - 30In Nominal burden per phase 5 A: <0.01VA at rated current Impedance per phase 1 A: <8mΩ over 0 - 30In

Thermal withstand: continuous 4 In for 10 s: 30 In for 1 s; 100 In Linear to 64 In (non-offset AC current).

POWER SUPPLY

Auxiliary Voltage (Vx) Three ordering options:

(i) Vx: 24 to 48 Vdc (ii) Vx: 48 to 110 Vdc, and 30 to 100Vac (rms) (iii) Vx: 110 to 250 Vdc, and 100 to 240Vac (rms).

Operating Range (i) 19 to 65V (dc only for this variant) (ii) 37 to 150V (dc), 24 to 110V (ac)

(iii) 87 to 300V (dc), 80 to 265V (ac). With a tolerable ac ripple of up to 12% for a dc supply, per IEC 60255-11: 1979.

Nominal Burden Quiescent burden: P741: 37 to 41 W P742: 16 to 23 W P743: 22 to 32 W Additions for energized binary inputs/outputs: Per opto input: 0.09W…(24 to 54V), 0.12W...(110/125V), 0.19W...(220/250V). Per energized output relay: 0.13W

Power-up Time Time to power up < 30s.

Power Supply Interruption Per IEC 60255-11: 1979

The relay will withstand a 20ms interruption in the DC auxiliary supply, without de-energizing.

Per IEC 61000-4-11: 1994 The relay will withstand a 20ms interruption in an AC auxiliary supply, without de-energizing.

Note: the use of a E124 extends these limits

Battery Backup Front panel mounted Type ½ AA, 3.6V

Field Voltage Output Regulated 48Vdc Current limited at 112mA maximum output

Digital (“Opto”) Inputs Universal opto inputs with programmable voltage thresholds. May be energized from the 48V field voltage, or the external battery supply. Rated nominal voltage: 24 to 250Vdc Operating range: 19 to 265Vdc Withstand: 300Vdc. Nominal pick-up and reset thresholds: Pick-up: approx. 70% of battery nominal set, Reset: approx. 66% of battery nominal set. Recognition time: 7ms

OUTPUT CONTACTS

Standard Contacts General purpose relay outputs for signalling, tripping and alarming: Rated voltage: 300 V Continuous current: 10 A Short-duration current: 30 A for 3 s Making capacity: 250A for 30 ms Breaking capacity: DC: 50W resistive DC: 62.5W inductive (L/R = 50ms) AC: 2500VA resistive (cos φ = unity) AC: 2500VA inductive (cos φ = 0.7) Response to command: < 5ms Durability: Loaded contact: 10 000 operations minimum, Unloaded contact: 100 000 operations minimum.

Watchdog Contacts Non-programmable contacts for relay healthy/relay fail indication: Breaking capacity: DC: 30W resistive DC: 15W inductive (L/R = 40ms) AC: 375VA inductive (cos φ = 0.7)

IRIG-B 12X Interface (Modulated) External clock synchronization per IRIG standard 200-98, format B12X. Input impedance 6kΩ at 1000Hz Modulation ratio: 3:1 to 6:1 Input signal, peak-peak: 200mV to 20V

IRIG-B 00X Interface (Un-modulated) External clock synchronization per IRIG standard 200-98, format B00X. Input signal TTL level Input impedance at dc 10kΩ

Page 13: 06. AREVA P740

P740 Technical Data Sheet EN 12 P740/EN TDS/K55

ENVIRONMENTAL CONDITIONS

Ambient Temperature Range Per IEC 60255-6: 1988 Operating temperature range: -25°C to +55°C (or -13°F to +131°F). Storage and transit: -40°C to +70°C (or -28°F to +158°F).

Ambient Humidity Range Per IEC 60068-2-3: 1969:

56 days at 93% relative humidity and +40 °C Per IEC 60068-2-30: 1980:

Damp heat cyclic, six (12 + 12) hour cycles, 93% RH, +25 to +55 °C

TYPE TESTS

Insulation Per IEC 60255-5: 2000, Insulation resistance > 100MΩ at 500Vdc (Using only electronic/brushless insulation tester).

Creepage Distances and Clearances Per IEC 60255-27: 2005 Pollution degree 3, overvoltage category III, impulse test voltage 5 kV.

High Voltage (Dielectric) Withstand (EIA RS232 ports excepted). (i) Per IEC 60255-27: 2005,

2 kV rms AC, 1 minute: Between all case terminals connected together, and the case earth. Also, between all terminals of independent circuits.

1kV rms AC for 1 minute, across open watchdog contacts. 1kV rms AC for 1 minute, across open contacts of changeover output relays.

(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed 1994): 1.5 kV rms AC for 1 minute, across open contacts of changeover output relays.

Impulse Voltage Withstand Test Per IEC 60255-27: 2005 Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5J Between all terminals, and all terminals and case earth.

ELECTROMAGNETIC COMPATIBILITY (EMC)

1 MHz Burst High Frequency Disturbance Test Per IEC 60255-22-1: 1988, Class III, Common-mode test voltage: 2.5 kV, Differential test voltage: 1.0 kV, Test duration: 2 s, Source impedance: 200 Ω (EIA RS232 ports accepted).

Immunity to Electrostatic Discharge Per IEC 60255-22-2: 1996, Class 4, 15kV discharge in air to user interface, display, and exposed metalwork. Per IEC 60255-22-2: 1996, Class 3, 8kV discharge in air to all communication ports. 6kV point contact discharge to any part of the front of the product.

Electrical Fast Transient or Burst Requirements Per IEC 60255-22-4: 2002. Test severity Class III and IV: Amplitude: 2 kV, burst frequency 5kHz (Class III), Amplitude: 4 kV, burst frequency 2.5kHz (Class IV).

Applied directly to auxiliary supply, and applied to all other inputs. (EIA RS232 ports excepted).

Surge Withstand Capability Per IEEE/ANSI C37.90.1: 2002: 4kV fast transient and 2.5kV oscillatory applied directly across each output contact, optically isolated input, and power supply circuit.

Surge Immunity Test (EIA RS232 ports excepted). Per IEC 61000-4-5: 2002 Level 4, Time to half-value: 1.2 / 50 µs,

Amplitude: 4kV between all groups and case earth, Amplitude: 2kV between terminals of each group.

Immunity to Radiated Electromagnetic Energy Per IEC 60255-22-3: 2000, Class III: Test field strength, frequency band 80 to 1000 MHz:

10 V/m, Test using AM: 1 kHz / 80%, Spot tests at 80, 160, 450, 900 MHz

Per IEEE/ANSI C37.90.2: 1995: 25MHz to 1000MHz, zero and 100% square wave modulated. Field strength of 35V/m.

Radiated Immunity from Digital Communications Per EN61000-4-3: 2002, Level 4: Test field strength, frequency band 800 to 960 MHz, and 1.4 to 2.0 GHz: 30 V/m, Test using AM: 1 kHz / 80%.

Radiated Immunity from Digital Radio Telephones Per ENV 50204: 1995 10 V/m, 900MHz and 1.89GHz.

Immunity to Conducted Disturbances Induced by Radio Frequency Fields Per IEC 61000-4-6: 1996, Level 3, Disturbing test voltage: 10 V

Power Frequency Magnetic Field Immunity Per IEC 61000-4-8: 1994, Level 5,

100A/m applied continuously, 1000A/m applied for 3s.

Per IEC 61000-4-9: 1993, Level 5, 1000A/m applied in all planes.

Per IEC 61000-4-10: 1993, Level 5, 100A/m applied in all planes at 100kHz/1MHz with a burst duration of 2s.

Page 14: 06. AREVA P740

P740 Technical Data Sheet EN 13 P740/EN TDS/K55

Conducted Emissions Per EN 55022: 1998:

0.15 – 0.5MHz, 79dBµV (quasi peak) 66dBµV (average) 0.5 – 30MHz, 73dBµV (quasi peak) 60dBµV (average).

Radiated Emissions Per EN 55022: 1998:

30 - 230MHz, 40dBµV/m at 10m measurement distance 230 – 1GHz, 47dBµV/m at 10m measurement distance.

EU DIRECTIVES

EMC Compliance Per 89/336/EEC:0 Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route. Product Specific Standards were used to establish conformity: EN50263: 2000

Product Safety Per 2006/95/EC: Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: IEC 60255-27:2005 EN 60255-5:2001.

MECHANICAL ROBUSTNESS

Vibration Test Per IEC 60255-21-1: 1996 Response Class 2 Endurance Class 2

Shock and Bump Per IEC 60255-21-2: 1995 Shock response Class 2 Shock withstand Class 1 Bump Class 1

Seismic Test Per IEC 60255-21-3: 1995 Class 2

TIMINGS AND ACCURACY Busbar trip (including trip relay closing time):

11 ms (min) 13 ms (typical)

PERFORMANCE DATA THREE PHASE OVERCURRENT PROTECTION

All quoted operating times include the closure of the trip output contact.

Accuracy Pick-up: Setting ±5% Drop-off: 0.95 x Setting ±5% Min. trip level of IDMT elements :1.05 x Setting ±5% IDMT characteristic shape: ±5% or 40ms whichever is greater (under reference conditions)* IEEE reset: ±5% or 40ms whichever is greater DT operation: ±2% or 50ms whichever is greater DT reset: Setting ±5% Characteristic UK curves: IEC 60255-3 – 1998 US curves: IEEE C37.112 – 1996

DEAD ZONE PROTECTION

Accuracy Pick-up: Setting ±5% Drop-off: >0.95 x Setting Min.trip level: 1.05 x Setting ±5%

EARTH FAULT PROTECTION

Accuracy Pick-up: Setting ±5% Drop-off: >0.85 x Setting Min.trip level of IDMT elements: 1.05 x Setting ±5% IDMT characteristic shape: ±5% or 40ms whichever is greater (under reference conditions)* IEEE reset: ±10% or 40ms whichever is greater DT operation: ±2% or 50ms whichever is greater DT reset: ±5% or 50ms whichever is greater Repeatability: 7.5%

TRANSIENT OVERREACH AND OVERSHOOT

Accuracy Additional tolerance due to increasing X/R ratios: ±5% over the X/R ratio of 1 to 90 Overshoot of overcurrent elements: <40ms

PROGRAMMABLE SCHEME LOGIC

Accuracy Output conditioner timer:

Setting ±2% or 50ms whichever is greater Dwell conditioner timer:

Setting ±2% or 50ms whichever is greater Pulse conditioner timer:

Setting ±2% or 50ms whichever is greater

Page 15: 06. AREVA P740

P740 Technical Data Sheet EN 14 P740/EN TDS/K55

IRIG-B AND REAL TIME CLOCK

Modulated IRIG-B: Modulation ratio: 1/3 or 1/6 Input signal peak-peak amplitude: 200 mV to 20 V Input impedance at 1000Hz: 6000 Ω External clock synchronization: Conforms to IRIG standard 200-98, format B Un-modulated IRIG-B: Input signal TTL level Input impedance at dc 10kΩ External clock synchronization per IRIG standard 200-98, format B00X.

Performance Accuracy (for modulated and un-modulated versions) Real time clock accuracy: < ±2 seconds/day

MEASUREMENTS

Accuracy Phase current: ±1.0% of reading Phase local current: ±1.0% of reading or ±(f-fn)/fn % Phase remote current: ±1.0% of reading or ±(f-fn)/fn % Phase differential current: ±5.0% Bias current: ±5.0% Frequency: ±1%

DISTURBANCE RECORDS

Accuracy Waveshape : Comparable with applied quantities Magnitude and relative phases: ±5% of applied quantities Duration: ±2% Trigger position: ±2% (minimum trigger 100ms)

REFERENCE CONDITIONS

Ambient temperature: 20°C

FREQUENCY TRACKING RANGE

45 to 65Hz

BREAKER FAILURE

Accuracy Reset time = 25ms from: start to [TBF2 or TBF4] - 30ms 15ms from: [TBF2 or TBF4] - 30ms to [TBF2 or TBF4] ±2% or 10ms whichever is greater Thresholds: settings ±5% Step 5ms

IEC 61850 Ethernet data

10 Base T /100 Base TX Communications Interface in accordance with IEEE802.3 and IEC61850 Isolation 1.5kV Cable type: Screened twisted pair STP Max length: 100m

100 Base FX Interface Interface in accordance with IEEE802.3 and IEC61850 Wavelength: 1300nm Fibre: multi-mode 50/125µm or 62.5/125µm Connector style: ST

Transmitter Optical Characteristics (TA = 0°C to 70°C, VCC = 4.75 V to 5.25 V)

PARAMETER SYM MIN. TYP. MAX UNITOUTPUT OPTICAL POWER BOL 62.5/125 µM, NA = 0.275 FIBER EOL

PO -19 -20 -16.8 -14 DBM

AVG.

OUTPUT OPTICAL POWER BOL 50/125 µM, NA = 0.20 FIBER EOL

PO -22.5 -23.5 -20.3 -14 DBM

AVG.

OPTICAL EXTINCTION RATIO 10

-10 % DB

OUTPUT OPTICAL POWER AT LOGIC “0” STATE

PO (“0”) -45 DBM

AVG.

BOL – Beginning of life

EOL – End of life

Receive Optical Characteristics (TA = 0°C TO 70°C, VCC = 4.75 V TO 5.25 V)

PARAMETER SYM MIN. TYP. MAX. UNIT INPUT OPTICAL POWER MINIMUM AT WINDOW EDGE

PIN MIN. (W)

-33.5 –31 DBM AVG.

INPUT OPTICAL POWER MINIMUM AT EYE CENTER

PIN MIN. (C)

-34.5 -31.8 BM AVG.

INPUT OPTICAL POWER MAXIMUM

PIN MAX.

-14 -11.8 DBM AVG.

Page 16: 06. AREVA P740

P740 Technical Data Sheet EN 15 P740/EN TDS/K55

SETTINGS PROTECTION FUNCTIONS GLOBAL SETTINGS (SYSTEM DATA): Language: English/French/German/Spanish Frequency: 50/60Hz COMMON CONVENTIONAL RATIOS (CU) Primary basis current (virtual) Ibp: 1000A CURRENT TRANSFORMERS (PU) Phase CT Primary: 1A...30.000A Phase CT Secondary In: 1A or 5A PHASE FAULT ELEMENTS (CU) Phase current slope adjustment k2: 0.20...0.90 Phase differential current threshold ID>2: 50A... 30kA Check Zone slope adjustment kCZ: 0.00... 0.90 Check Zone differential current threshold IDCZ >2: 50A... 30kA Circuitry fault slope adjustment ID>1: 10A...500A xIn Circuitry fault threshold k1: 0.00...0.50 Circuitry fault alarm timer ID>1 tCF: 0.1... 600.0 s SENSITIVE EARTH FAULT Option for high neutral impedance: Disabled/Enabled Threshold for sensitive Earth fault with flowing current control:

IbiasPh>Cur.: 50A... 30kA Residual current slope adjustment

kN2: 0.00...0.90 Residual differential current threshold:

IDN>2: 10A... 30kA Residual Check Zone current slope adjustment

kNCZ: 0.00...0.90 Residual Check Zone differential current threshold:

IDNCZ>2: 10A... 30kA Circuitry fault slope adjustment

kN1: 0.00...0.50 Circuitry fault threshold:

IDN>1: 10A...500A Circuitry fault alarm timer

IDN>1 tCF: 0.1... 600.0 s CURRENT TRANSFORMER AND FEEDER CHARACTERISTICS Class: 5P (IEC185) X (BS3958) TPX (IEC 44-6) TPY (IEC 44-6) TPZ (IEC 44-6) Min. Knee point voltage (BS 3958): Vk: 20-5kV Rated Burden (IEC 44-6): S: 5 200 (step 5) Rated Resistive Burden (IEC 44-6): rRB: data calculated from rated burden

Rated short-circuit current factor: KSCC: 10...50 (step 5) Secondary resistance (Ohm): RCT: 0.1... 50Ω (step 0.1) External loop resistance Eff. Burden (Ohm): RB: 0.1... 200 External loop resistance Eff. Burden VA (Data calculated from Eff. Burden Ohm) Blocking of 87BB on phase-phase feeder fault for external ph-ph fault detection - (>1.5 max ph-ph fault current infeed) with Ultra high speed detection <1ms: I>BB: 0.25... 20 xIn Blocking of 87BB on earth/feeder fault (external earth fault detection) - (>1.5 max earth fault current infeed. Ultra high speed detection required <1ms): IN>BB: 0.25... 30 kA Supervision of I0 calculation: Kce: 0.01... 1.00 I0 error alarm time delay: Tce: 0.0...10.0 s DEAD ZONE PROTECTION (PU) Phase threshold : I>DZ: 0.05...4.00 xIn Time delay: 0,00…100,00s Disabled/Enabled Neutral threshold : IN>DZ: 0.05...4.00 xIn Time delay: 0,00…100,00s BREAKER FAILURE PROTECTION (PU) Caution: the following current set values are expressed in multiple of the local CT’s nominal rated current inp (primary) or ins (secondary).

Breaker Failure 1ST phase O/C threshold (dead pole detection for 50BF): I<: 0.05...1.00 xIn Confirmation I>: Disabled/Enabled 2nd phase O/C threshold: I>: 0.05...4.00 xIn Confirmation IN>: Disabled/Enabled 2nd residual O/C threshold: IN>: 0.05...4.00 xIn

Timers for 50BF internal tripping CB fail 1 timer: tBF1: 0.00 s...10.00 s CB fail 2 timer: tBF2: 0.00 s...10.00 s Timers for 50BF external tripping (orders from 21 or 87Tetc…) CB fail 1 timer: TBF3: 0.00 s......10.00 s CB fail 2 timer: TBF4: 0.00 s......10.00 s

Page 17: 06. AREVA P740

P740 Technical Data Sheet EN 16 P740/EN TDS/K55

OVERCURRENT PROTECTION (PU) Phase Fault Protection (50/51) 3 phase Overcurrent Function Status I>1: • Disabled • DT • IEC S Inverse or IEC V Inverse or IEC E Inverse • UK LT Inverse • IEEE M Inverse or IEEE V Inverse or IEEE E Inverse • US Inverse or US ST Inverse Current Set if “function status” ≠0 I>1: 0.10...32.00 xIn Time delay if “function status”=1 I>1: 0.00...100.00 xIn TMS if 2≤”function status”≤5 I>1: 0.025...1.200 xIn (step 0.025) Time dial if “function status”≥6 I>1: 0.5...15.0 xIn Reset Char. if “function status”≥6 I>1: • DT • Inverse tReset if 2≤”function status”≤5 OR if “Reset Char.”=1 AND “function status”≥6 I>1: 0.0...100.0 xIn 3 phase Overcurrent threshold function status I>2: • Disabled • Blocking 87BB • High set I>2 • Both Current Set I>2: 0.10... 32.00 Time Delay if “function status”=1 I>2: 0.00...100.00 s Earth Fault Protection (50N/51N) Residual Overcurrent Function Status IN>1: • Disabled • DT • IEC S Inverse or IEC V Inverse or IEC E Inverse • UK LT Inverse • IEEE M Inverse or IEEE V Inverse or IEEE E Inverse • US Inverse or US ST Inverse Current Set if “function status” ≠0 IN >1: 0.10...32.00 xIn Time delay if “function status”=1 IN >1: 0.00...100.00 xIn TMS if 2≤”function status”≤5 IN >1: 0.025...1.200 xIn (step 0.025) Time dial if “function status”≥6 IN >1: 0.5...15.0 xIn Reset Char. if “function status”≥6 IN >1: 0 DT 1 Inverse tReset if 2≤”function status”≤5 OR if “Reset Char.”=1 AND “function status”≥6 IN >1: 0.0...100.0

Residual Overcurrent threshold function status IN >2: • Disabled • Blocking 87BB • High set I>2 • Both Current Set IN >2: 0.10 xIn...32.00 xIn Time Delay if “function status”=1 IN >2: 0.00...100.00 s CB CONTROL (PU) Prot Trip Pulse: 0.05...2.00 s Trip Latched: Disabled/Enabled Rest Trip Latch: Yes/No CB Control by: Disabled/Enabled Man Close Pulse: 0.1...5.0 s Man Trip Pulse: 0.1...5.0 s Man Close Delay: 0... 60 s DATE AND TIME IRIG-B Sync: Disabled/Enabled Battery Alarm: Disabled/Enabled CONFIGURATION Setting Group: Select via Menu Select via Opto Active Settings: Group 1/2/3/4 Setting Group 1: Disabled/Enabled Setting Group 2: Disabled/Enabled Setting Group 3: Disabled/Enabled Setting Group 4: Disabled/Enabled CU Only Diff Busbar Prot: Disabled/Enabled PU Only BB Trip Confirm: Disabled/Enabled Overcurrent Prot: Disabled/Enabled Earth Fault Prot: Disabled/Enabled CB Fail & I>: Disabled/Enabled CU & PU Setting Values: Primary/Secondary LCD Contrast: (Factory pre-set) FAULT RECORDER Records for the last 5 faults Central Unit: • Active Setting group • Faulty phase • Protection started/operated (87BB, 50BF, Dead Zone…) • Fault occurrence time and duration • Check Zone values (Diff & Bias for A, B, C, N) • Faulty zone(s) • Topology prior the fault occurrence Peripheral Unit: • Active setting group • Indication of the tripped phases • Protection started/operated (87BB, 50BF, Dead Zone…) • Relay Trip Time and duration • Relay Trip Time • Faulty phase currents (A, B, C, N)

Page 18: 06. AREVA P740

P740 Technical Data Sheet EN 17 P740/EN TDS/K55

EVENT RECORDER Records for the last 512 events

OSCILLOGRAPHY (DISTURBANCE RECORDER) Central Unit: Duration: Fixed value 1.2s Trigger Position: 0...50 (step 200ms) Analog Channel 1: (up to 8): Digital Input 1: (up to 32): Peripheral Unit: Duration: Settable from 0.1 to 10.5s Trigger Position: 0...50 (step 200ms) Trigger Mode: Single/Extended Analog Channel 1: (up to 8): Digital Input 1: (up to 32): Selected binary channel assignment from any DDB status point within the relay (opto input, output contact, alarms, starts, trips, controls, logic…). Sampling frequency: 600Hz

COMMUNICATIONS RP1 Protocol: Courier RP1 Address (courier) 6…34 Inactivity Timer: 1…30 minutes IEC870-5-103 via KITZ 274 RP1 Address: (Courier): 6…34 RP1 InactivTimer: 1…30mins RP1 Port Config: (Courier): K Bus EIA485 (RS485) RP1 Comms Mode (EIA485 (RS485)): IEC60870 FT1.2 Frame IEC60870 10-Bit FrameRP1 Baud Rate (EIA485 (RS485)): 9600/19200/38400 bits/s

Optional Ethernet Port NIC Tunl Timeout: 1...30mins NIC Link Report: Alarm/Event/None NIC Link Timeout: 0.1...60s

COMMISSION TESTS Monitor Bit 1(up to 8):: Binary function link strings, selecting which DDB signals have their status visible in the Commissioning menu, for test purposes Test Mode: (CU) Enabled or Disabled

• 87BB trip blocked but 50BF (back trip) enable per zone

• 87BB and 50BF trip blocked per zone • All the protections (87BB, Dead Zone, General 50BF,

Local 50BF, O/C) disabled • 87BB disable but 50BF (back trip) enable for all zones

Test Mode: (PU) Enabled or Disabled

• 50BF Blocked • Overhaul

Test Pattern: Configuration of which output contacts are to be energized when the contact test is applied. Static Test Mode: Disabled/Enabled Opto input voltage range: 24-27V 30-34V 48-54V 110-125V 220-250V Custom Opto Input 1 (up to # = max. opto no. fitted) Custom options allow independent thresholds to be set per opto, from the same range as above

OPTO INPUT LABELS Opto Input 1 up to:

8 for P741 16 for P742 24 for P743

User defined text string to describe the function of the particular opto input.

OUTPUT LABELS Relay 1 up to:

8 for P741 & P742 16 for P743

User defined text string to describe the function of the particular relay output contact.

IED CONFIGURATOR Switch Conf.Bank: No Action/Switch Banks

IEC61850 GOOSE GoEna: Disabled/Enabled Test Mode: Disabled/Pass Through/Forced VOP Test Pattern: 0x00000000... 0xFFFFFFFF Ignore Test Flag: No/Yes

Page 19: 06. AREVA P740

P740 Technical Data Sheet EN 18 P740/EN TDS/K55

CONNECTION DIAGRAMS

P05

38E

Nc

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

21

to2

4P

U*

21

to2

4P

U*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

17

to2

0P

U*

17

to2

0P

U*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

13

to1

6P

U*

13

to1

6P

U*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

9to

12

PU

*9

to1

2P

U*

TX

2T

X2

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

Po

sitio

nB

Po

sitio

nB

5to

8P

U*

5to

8P

U*

1to

4P

U*

1to

4P

U*

Po

sitio

nA

Po

sitio

nA

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

TX

4T

X4

RX

4R

X4

RX

2

RX

3

TX

3

TX

2

RX

1

TX

1

RX

3

RX

4

TX

4

TX

3

RX

2

RX

2

RX

3

TX

3P

ositio

nF

Po

sitio

nF

TX

2

TX

1

RX

1

RX

3

RX

4

TX

4

TX

3

RX

2

Po

sitio

nE

Po

sitio

nE

CO

NN

EC

TIO

N

OP

TO

5O

PT

O5

OP

TO

7O

PT

O7

OP

TO

6O

PT

O6

OP

TO

8O

PT

O8

OP

TO

4O

PT

O4

OP

TO

1O

PT

O1

OP

TO

2O

PT

O2

OP

TO

3O

PT

O3

CO

MM

ON

+

K8

+

RX

1

TX

1

K1

8

K1

7

+

K1

2

K1

6

K1

5

K1

4

K1

3

+ --

K11

K1

0

K9

+ --

Po

sitio

nD

Po

sitio

nD

RX

1

TX

1

TX

4

RX

4

RX

3

RX

1

RX

2

TX

3

TX

2

TX

1

RX

4

MiC

OM

P741

(PA

RT

)M

iCO

MP

741

(PA

RT

)

K4

K6

K7

K5

+ -+ -

K2

K3

K1

+ --

RX

3

TX

4

TX

3P

ositio

nC

Po

sitio

nC

TX

2

RX

2

RX

1

TX

1

AC

OR

DC

AC

OR

DC

V

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

9-W

AY

&25-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T9-W

AY

&25-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T

2.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001

2.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

AU

XS

UP

PLY

AU

XS

UP

PLY

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

48

VD

CF

IEL

D4

8V

DC

FIE

LD

NO

TE

1.

NO

TE

1.

x

EA

RT

H

*

-L

9

-

CA

SE

L1

0

++ +L

7

L8

L2

CO

MM

SC

OM

MS

NO

TE

2N

OT

E2

MiC

OM

P741

(PA

RT

)M

iCO

MP

741

(PA

RT

)

J1

J1

2R

EL

AY

6

RE

LA

Y8

-L

1

J1

8

RE

LA

Y7

J1

5

J1

6

J1

7

J1

3

J1

4

*

J7

RE

LA

Y5

RE

LA

Y4

J1

0

J11

J9

J8

RE

LA

Y2

RE

LA

Y3

RE

LA

Y1

J4

J5

J6

J2

J3

CO

NTA

CT

WA

TC

HD

OG

WA

TC

HD

OG

CO

NTA

CT

L11

L1

4

L1

2

L1

3

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

25

to2

8P

U*

25

to2

8P

U*

CU

RR

DIF

FC

UR

RD

IFF

FIB

RE

OP

TIC

FIB

RE

OP

TIC

Po

sitio

nG

Po

sitio

nG

TX

4

RX

4

RX

3

RX

2

TX

3

TX

2

RX

1

TX

1

Terminal connection diagram for MiCOM P741 case 80TE – Central Unit

Page 20: 06. AREVA P740

P740 Technical Data Sheet EN 19 P740/EN TDS/K55

P2

S2

S1

P1

CBA

(2)

AI

(2)

BI

(2)

CI

I N

NO

TE

2.N

OT

E2.

C.T

.S

HO

RT

ING

LIN

KS

C.T

.S

HO

RT

ING

LIN

KS

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1

AC

ON

NE

CT

ED

AN

DA

RE

TY

PIC

AL

ON

LY.

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1

AC

ON

NE

CT

ED

AN

DA

RE

TY

PIC

AL

ON

LY.

9-W

AY

&25-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T9-W

AY

&25-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

(b)

(a)

B1

B2

B3

MiC

OM

P7

42

(PA

RT

)M

iCO

MP

74

2(P

AR

T)

MiC

OM

P7

42

(PA

RT

)M

iCO

MP

74

2(P

AR

T)

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

*

RE

LA

Y8

RE

LA

Y8

RE

LA

Y7

RE

LA

Y7

CO

NTA

CT

TR

IPB

TR

IPB

TR

IPA

TR

IPA

WA

TC

HD

OG

CO

NTA

CT

WA

TC

HD

OG

CO

MM

ON

CO

NN

EC

TIO

NC

ON

NE

CT

ION

+ - +- - +- +

PH

AS

ER

OTA

TIO

NP

HA

SE

RO

TA

TIO

N

A

CB

+-

C2

OP

TO

4O

PT

O4

OP

TO

1O

PT

O1

OP

TO

2O

PT

O2

OP

TO

3O

PT

O3

+-

A6

+

A4

A5

-- +

A1

A3

A2

+-

48

VD

CF

IEL

D4

8V

DC

FIE

LD

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

AU

XS

UP

PLY

AU

XS

UP

PLY

AC

OR

DC

AC

OR

DC

xV

DIR

EC

TIO

NO

FF

OR

WA

RD

CU

RR

EN

TF

LO

WD

IRE

CT

ION

OF

FO

RW

AR

DC

UR

RE

NT

FL

OW

C1

EA

RT

HC

AS

E

B4

B5

B6

B7

B8

B9

B1

0

B11

B1

2

TR

IPC

RE

LA

Y4

RE

LA

Y4

RE

LA

Y5

RE

LA

Y5

TX

1

RX

1R

X1

RX

2

TX

2

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

CU

RR

DIF

FC

UR

RD

IFF

OP

TO

11

OP

TO

11

OP

TO

10

OP

TO

10

OP

TO

14

OP

TO

14

OP

TO

13

OP

TO

13

OP

TO

12

OP

TO

12

OP

TO

16

OP

TO

16

OP

TO

15

OP

TO

15

OP

TO

9O

PT

O9

CO

NN

EC

TIO

NC

OM

MO

N

OP

TO

5O

PT

O5

OP

TO

8O

PT

O8

OP

TO

7O

PT

O7

OP

TO

6O

PT

O6

+ ++ ---+-

+-

C3

C4

+-

C6

C5

+-

C8

C7

+ -+ -+-

*

CO

MM

SC

OM

MS

NO

TE

3N

OT

E3

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001.

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001.

RE

LA

Y6

RE

LA

Y6 P05

39E

Nc

E1

4

D1

8

D1

5

D16

D1

6

D1

7

D1

4

D1

3

D11

D1

2D

12

D1

0

D9

D1

D3

D4

D5

D6

D2

D7

D8

E13

E1

2

E11

E1

0

E9

E7

E8

E1

E2

C1

8

C1

7

C1

5

C1

4

C1

3

C1

6

C11

C1

0

C1

2

C9

A1

2

A13

A1

4

A15

A18

A17

A1

6

A1

0

A11

A9

A7

A8

Terminal connection diagram for MiCOM P742 case 40TE – Peripheral Unit

Page 21: 06. AREVA P740

P740 Technical Data Sheet EN 20 P740/EN TDS/K55

(2)

AI

(2)

BI

(2)

CI

NO

TE

2.

NO

TE

2.

C.T

.S

HO

RT

ING

LIN

KS

C.T

.S

HO

RT

ING

LIN

KS

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1A

CO

NN

EC

TE

DA

ND

AR

ET

YP

ICA

LO

NLY.

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1A

CO

NN

EC

TE

DA

ND

AR

ET

YP

ICA

LO

NLY.

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

(b)

(a)

NO

TE

S1.

NO

TE

S1.

CO

NN

EC

TIO

NC

ON

NE

CT

ION

OP

TO

24

OP

TO

24

CO

MM

ON

OP

TO

23

OP

TO

23

OP

TO

22

OP

TO

22

OP

TO

21

OP

TO

21

OP

TO

20

OP

TO

20

OP

TO

19

OP

TO

19

OP

TO

18

OP

TO

18

5A

MiC

OM

P7

43

(PA

RT

)M

iCO

MP

74

3(P

AR

T)

MiC

OM

P7

43

(PA

RT

)M

iCO

MP

74

3(P

AR

T)

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24

-48

V(N

OM

INA

L)

D.C

.O

NLY

*

- -++- +

*

EA

RT

HC

AS

E

OP

TO

9O

PT

O9

OP

TO

12

OP

TO

12

OP

TO

13

OP

TO

13

OP

TO

10

OP

TO

10

OP

TO

11

OP

TO

11

+ + +-+-+ ---+-+-+-

+ +-+-+ --

+

D1

5

D1

7

D1

6

D1

8

+-

D1

3

D1

2

D1

4

D11

+-+-

D1

0

D9

D8

D7

+-+-

D6

D5

D4

D3

+ +---

B1

5

OP

TO

8O

PT

O8

+-

B1

6

OP

TO

7O

PT

O7

+-

B1

4

+-+-

B1

8

B1

7

CO

NN

EC

TIO

NC

OM

MO

NC

OM

MO

N

3.F

OR

CO

MM

SO

PT

ION

SS

EE

DR

AW

ING

10P

x4001

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001

CO

MM

SN

OT

E3

NO

TE

3

RE

LA

Y8

RE

LA

Y7

TR

IPB

TR

IPA

WA

TC

HD

OG

WA

TC

HD

OG

CO

NTA

CT

TR

IPC

RE

LA

Y4

RE

LA

Y5

RE

LA

Y6

WA

TC

HD

OG

CO

NTA

CT

F3

F1

4

F1

7

F1

6

F1

8

F1

5

F4

F5

F6

F8

F9

F7

F1

0

F1

2

F11

F1

3

G1

4

F1

F2

G1

3

G1

2

G11

TX

1

RX

1

RX

2

TX

2

G1

0

G9

G7

G8

G1

G2

48

VD

CF

IEL

D4

8V

DC

FIE

LD

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

AU

XS

UP

PLY

AU

XS

UP

PLY

AC

OR

DC

AC

OR

DC

xV

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

CU

RR

DIF

FC

UR

RD

IFF

E1

2

E1

7

E1

8

E1

3

E1

5

E1

4

E1

6

E1

E7

E8

E1

0

E11

E9

E2

E3

E5

E4

E6

RE

LA

Y1

6

RE

LA

Y1

5R

EL

AY

15

RE

LA

Y1

3

RE

LA

Y1

4

RE

LA

Y1

2

RE

LA

Y1

0

RE

LA

Y11

RE

LA

Y9

P2

S2

S1

P1

CBA

PH

AS

ER

OTA

TIO

NP

HA

SE

RO

TA

TIO

N

A

CB

DIR

EC

TIO

NO

FF

OR

WA

RD

CU

RR

EN

TF

LO

WD

IRE

CT

ION

OF

FO

RW

AR

DC

UR

RE

NT

FLO

W

1A

5A

1A

5A

1A

5A

A1

A2

A3

A4

A5

A6

A7

A8

A9

I N

1A

A11

A1

2

A1

0

OP

TO

3O

PT

O3

OP

TO

2O

PT

O2

OP

TO

1O

PT

O1

OP

TO

4O

PT

O4

B8

B7

B6

B5

B4

B3

B2

B1

B11

OP

TO

6O

PT

O6

B1

3

B1

2

OP

TO

5O

PT

O5

B1

0

B9

OP

TO

17

OP

TO

17

OP

TO

15

OP

TO

15

OP

TO

16

OP

TO

16

OP

TO

14

OP

TO

14

CO

NN

EC

TIO

NC

ON

NE

CT

ION

CO

MM

ON

CO

MM

ON

C1

7

C1

8

C1

6

C1

5

C1

4

C1

3

C1

2

C11

D2

D1

C1

0

C9

C4

C6

C7

C8

C5

C2

C3

C1

P05

40E

Nc

Terminal connection diagram for MiCOM P743 case 60TE – Peripheral Unit

Page 22: 06. AREVA P740

P740 Technical Data Sheet EN 21 P740/EN TDS/K55

COMMUNICATION OPTIONS

100

BA

SE-T

X10

BA

SE-T

/

7 8

100

BA

SE-F

XRX

10 B

ASE

-FL

TX

OR

RJ45 2 4 5 631

RX-

RX+

TX+

TX-

REA

R C

OM

MS

BO

ARD

6 8 9753 4

SK5 1 2

0V

4

(OPT

ION

AL)

IRIG

-B IN

PUT

97 85 64

SK4 2 31

987

N.C

.CTS

RTS

5 6

-0V

N.C

.DTR

#

T

XRX

B

N.C

.

T

XRX

A

-0V

N.C

.

EIA

232

321N

.C.

EIA

485

N.C

.

SK6

CO

MM

UN

ICA

TIO

N(O

PTIO

NA

L)

IRIG

-B IN

PUT

RX (OPT

ION

AL)

FIB

RE O

PTIC

TX

DO

WN

LOA

D

SK2

SK1

DO

WN

LOA

DTE

ST/

9

CTS

RTS

0VRX

7 864 5317 2-9

11,1

2,15

,13,

1419,1

8,22

,25

20,2

1,23

,24

0V

CON

NEC

TED

TX

1 2

NO

T

TO-T

7

COM

MA

ND

DO

-D7

ACK

NO

WLE

DG

E10 16

EXTE

RNA

LRE

SET

DA

TA R

EAD

Y

DA

TA

1

PORT

KB

US

EIA

485/

16 SCN

+18

-17

ETH

ERN

ET B

OA

RD

OR

IRIG

-B B

OA

RD

NO

TE:

FOR

TERM

INA

L B

LOC

K C

ON

NEC

TIO

N

REFE

R TO

REL

EVA

NT

EXTE

RNA

L C

ON

NEC

TIO

N D

IAG

RAM

.

RXD

TXD

N.C

.

N.C

.

N.C

.

RXD

TXD

DCD

DTR

#

N.C

.

SERI

AL

PORT

RTS#

N.C

.

N.C

.

SERI

AL

PORT

EIA

232

# PE

RMA

NEN

TLY

AC

TIV

E

N.C

.

SERI

AL

PORT

EIA

232

OR

IRIG

-B IN

PUT

(OPT

ION

AL)

Sht:

Nex

tSh

t:

Drg

No

:

Issu

e:Re

visi

on

:

Dat

e:

Dat

e:

Nam

e:

Ch

kd:

DO

NO

T SC

ALE

CAD

DA

TA 1

:1 D

IMEN

SIO

NS:

mm

Titl

e:

Ener

gy A

utom

atio

n &

Info

rmat

ion

AR

EV

A T

&D

UK

Ltd

(STA

FFO

RD)

29/0

3/06

S.W

OO

TTO

N

IRIG

-B in

pu

t ad

ded

to

eth

ern

et c

om

ms.

CD

NR5

944.

10Px

4001

1 -

EXTE

RNA

L C

ON

NEC

TIO

N D

IAG

RAM

: CO

MM

S O

PTIO

NS

MIC

OM

Px4

0 PL

ATF

ORM

G

R PR

ICE

P06

94E

Na

Page 23: 06. AREVA P740

P740 Technical Data Sheet EN 22 P740/EN TDS/K55

CASES & DIMENSIONS

CO

MM

UN

ICATI

ON

BO

ARD

CO

PRO

CESSO

R

BO

ARD

ETH

ERN

ET

BO

ARD

I/O

BO

ARD

S

12

17

18

116.5

574.9

159.0

62.0

155.4

408.9

129.5

4.5

168.0

30

.0

406.9

41

3.2

17

7.0

24

0.0

15

7.5

MA

X.

P37

13E

Nd

CH1

TXRX

TX

CH2

RX

CH3

RX

CH4

TX TX RX

VVIII VV

SE

RN

o.

SE

RN

o.

No

.

DIA

GN

o.

DIA

GD

IAG

No

.N

o.

SK

1S

K1

SK

2S

K2

SK

3S

K3

50

/60

Hz

50

/600

Hz

Hz

VVxx nn

VV

AAnn

VV

TR

IPT

RI

TR

IPP

=E

NT

ER

==E

NT

ER

EN

TE

R

OU

TO

FS

ER

VIC

EO

UT

OU

TO

FO

FS

ER

SE

RV

ICE

VIC

E

HE

ALT

HY

HE

AL

HE

ALT

HY

TH

Y

=R

EA

D==

RE

AD

RE

AD

=C

LE

AR

==C

LE

AC

LE

ARR

AL

AR

MA

LA

RM

44 55332211

99 10

10

887766

P741

P741

SC

RA

PV

IEW

SC

RA

PV

IEW

VIE

WS

HO

WIN

GA

CC

ES

SS

HO

WIN

GA

CC

ES

SA

CC

ES

SC

OV

ER

CL

OS

ED

CO

VE

RC

LO

SE

DC

LO

SE

D

TE

RM

INA

LB

LO

CK

DE

TA

IL

EA

CH

TE

RM

INA

TIO

NA

CC

EP

TS

:-S

TC

ON

NE

CT

OR

/M

ULT

I-M

OD

EF

IBR

E

EA

CH

TE

RM

INA

TIO

NA

CC

EP

TS

:-2

xM

4R

ING

TE

RM

INA

LS

TX

TX

RX

RX

SK

6S

K6

LIN

KLIN

LIN

KK

AC

TIV

ITY

AC

TIV

ITY

00.02.84.9F.FF.90 00.02.84.9F.FF .FF.90 .90

RR

2014809

82014809

88

xW

ork

sxW

xW

ork

sork

s

IRIG

-B12x

IRIG

-B12x

IRIG

-B12x

Win

dR

ive

rW

indR

ive

Win

dR

ive

rrRRR

XR

XC

H1

CH

1

RX

RX

CH

2C

H2

TX

TX

TX

TX

12

OF

FH

OLE

SD

ia.3.4

142.4

5

FLU

SH

MO

UN

TIN

GP

AN

EL

CU

T-O

UT

DE

TA

IL

FR

ON

TV

IEW

WIT

HA

CC

ES

SC

OV

ER

SO

PE

N

MO

UN

TIN

GS

CR

EW

S:M

4x

12

SE

MU

NIT

ST

EE

LT

HR

EA

DF

OR

MIN

GS

CR

EW

.

TE

RM

INA

LS

CR

EW

S:M

4x

7B

RA

SS

CH

EE

SE

HE

AD

SC

RE

WS

WIT

HLO

CK

WA

SH

ER

SP

RO

VID

ED

.

TY

PE

OF

FIB

RE

OP

TIC

CO

NN

EC

TO

R:S

T

SE

CO

ND

AR

YC

OV

ER

(WH

EN

FIT

TE

D)

INC

L.W

IRIN

G

SID

EV

IEW

MiCOM P741 case 80TE – Central Unit

Page 24: 06. AREVA P740

P740 Technical Data Sheet EN 23 P740/EN TDS/K55

.

1

18

2

17

161

19

3 24

18

4

P3

71

4E

Nd

CH1

TXRX

TX

CH2

RX

SC

RA

PV

IEW

SH

OW

ING

AC

CE

SS

CO

VE

RC

LO

SE

D

P7

42

SE

RN

o.

DIA

GN

o.

VI Vx nn

50/6

0H

z

V

V

A

V

==R

EA

DR

EA

DR

EA

D

CLE

AR

CLE

AR

CLE

AR

==E

NT

ER

EN

TE

EN

TE

RR==

TR

IP

OU

TO

FS

ER

VIC

E

HE

ALT

HY

ALA

RM

TE

RM

INA

LB

LO

CK

DE

TA

IL

AN

AL

OG

&I/

OB

OA

RD

SC

OP

RO

CE

SS

OR

BO

AR

D

HE

AV

YD

UT

YM

ED

IUM

DU

TY

EA

CH

TE

RM

INA

TIO

NA

CC

EP

TS

:-

ST

CO

NN

EC

TO

R/

MU

LT

I-M

OD

EF

IBR

E

EA

CH

TE

RM

INA

TIO

NA

CC

EP

TS

:-

2x

M4

RIN

GT

ER

MIN

AL

S

MO

UN

TIN

GS

CR

EW

S:

M4

x1

2S

EM

UN

ITS

TE

EL

TH

RE

AD

FO

RM

ING

SC

RE

WS

.

TE

RM

INA

LS

CR

EW

S:

M4

x6

ST

EE

LC

OM

BIN

AT

ION

PA

NH

EA

DM

AC

HIN

ES

CR

EW

.

TY

PE

OF

FIB

RE

OP

TIC

CO

NN

EC

TO

R:S

T

FU

SH

MO

UN

TIN

GP

AN

EL

CU

T-O

UT

DE

TA

IL

8O

FF

HO

LE

Sf

3.4

16

8.0

4.5

18

1.3

20

2.0

20

0.0

20

6.0

17

7.0

30

.0

15

7.5

MA

X.

10

.35

15

9.0

23

.31

55

.4

FR

ON

TV

IEW

WIT

HA

CC

ES

SC

OV

ER

SO

PE

N

SE

CO

ND

AR

YC

OV

ER

(WH

EN

FIT

TE

D)

24

0.0

INC

L.

WIR

ING

SID

EV

IEW

MiCOM P742 case 40TE – Peripheral Unit

Page 25: 06. AREVA P740

P740 Technical Data Sheet EN 24 P740/EN TDS/K55

1

18

2

17

161

19

3 24

18

4C

H1

TXRX

TX

CH2

RX

TE

RM

INA

LB

LO

CK

DE

TA

IL

AN

AL

OG

&I/

OB

OA

RD

SC

OP

RO

CE

SS

OR

BO

AR

D

HE

AV

YD

UT

YM

ED

IUM

DU

TY

EA

CH

TE

RM

INA

TIO

NA

CC

EP

TS

:-

ST

CO

NN

EC

TO

R/M

ULT

I-M

OD

EF

IBR

EE

AC

HT

ER

MIN

AT

ION

AC

CE

PT

S:-

2x

M4

RIN

GT

ER

MIN

ALS

MO

UN

TIN

GS

CR

EW

S:

M4

x1

2S

EM

UN

ITS

TE

EL

TH

RE

AD

FO

RM

ING

SC

RE

W.

TE

RM

INA

LS

CR

EW

S:

M4

x6

ST

EE

LC

OM

BIN

AT

ION

PA

NH

EA

DM

AC

HIN

ES

CR

EW

.

TY

PE

OF

FIB

RE

OP

TIC

CO

NN

EC

TO

R:

ST

SE

CO

ND

AR

YC

OV

ER

(WH

EN

FIT

TE

D)

24

0.0

INC

L.

WIR

ING

15

7.5

MA

X.

SID

EV

IEW

30

.03

09

.6

30

3.5

16

8.0 4.5

10

.3

15

9.0

23

.25

11

6.5

51

42

.45

12

OF

FH

OL

ES

3.4

f

FLU

SH

MO

UN

TIN

GP

AN

EL

CU

T-O

UT

DE

TA

IL

15

5.4

30

3.5

12

9.5

FR

ON

TV

IEW

TX

TXAC

TIV

ITY

AC

TIV

ITYY

LIN

KL

INL

INKK

RX

RXSK

6S

K6

00.02.84.9F.FF.90 00.02.84.9F 00.02.84.9F.FF .FF.90 .90

20148098 20148098

VxWorks VxW VxWorks orksRR

WindRiver WindRiverRR

P3715E

Nd

ET

HE

RN

ET

BO

AR

D

MiCOM P743 case 60TE – Peripheral Unit

Page 26: 06. AREVA P740

P740 Technical Data Sheet EN 25 P740/EN TDS/K55

MICOM P740 GUIDE FORM SPECIFICATION

The differential busbar protection has to be of entirely numerical technology and allow a centralised or distributed architecture via fibre optic communication. The distance between the acquisition (feeder) unit and the measurement unit must be able to reach 1000 metres.

The protection will include differential elements with phase segregation, biased check zone elements and a separate sensitive earth fault element for networks with high impedance earthing.

The sensitive earth fault element will be controlled by through current to guarantee its stability on external faults and in the presence of significant errors in measurement transducers (CTs).

Protection must have a low burden to enable it to be installed in series with other equipment on common secondary cores of the current transformers.

It has to allow the use of different class and type of CTs made by different manufacturers. In particular, it will have to be able to accept mixes of plant, satisfying different standards (e.g. British Standard 3938: Class X, IEC 185: Class 5P20, IEC 44-6 Class TPX, TPY or TPZ).

Owing to these various standards, calculation algorithms have to provide an effective compensation for transitory errors of amplitude and phase from the CTs in presence of a strong continuous dc component in the short-circuit current.

The protection has to be stable for all types of external faults and in particular under CT saturation conditions. This saturation has to be able to be detected in less than 2 ms.

In addition to signal processing algorithms for the detection of saturation, it will be able to be activated for very low rated feeders equipped with low ratio CTs, a fault criterion able to provide information of an external short-circuit in a time which does not exceed 0.5 ms.

The topological processing algorithms have to allow for the dynamic consideration of primary plant position changes in a period which does not exceed 30 ms for complex architectures going up to 8 zones and 28 Peripheral Units.

A peripheral unit must be capable of monitoring one breaker and six isolators.

The trip decision for the busbar zone has to comply with multiple criteria at the top level (i.e. in the Central Unit) and additional criterion at local level (i.e. in the Peripheral Unit).

One of the criteria has to be such that the system cannot be permitted to operate on a significant load current in a zone

temporarily or incorrectly opened by the topological analysis algorithm.

The differential busbar protection has to implement also an effective protection against circuit breaker failures.

Each peripheral unit will be equipped with local circuit breaker failure. When such a condition is initiated all the circuit breakers adjacent to the faulty circuit breaker will be identified and tripped selectively by way of the scheme topology and via the busbar differential protection.

The circuit breaker failure sequence has to include a re-trip, which can be initiated via another protection on the same circuit i.e. for the same circuit breaker. This sequence must be user configurable and either instantaneous or time delayed.

On overhead lines where single-pole tripping will be carried out, monitoring has to be carried out on a per phase basis.

The open circuit breaker poles will be checked by means of an under current detector and by monitoring auxiliary contact positions.

To avoid all risk of maloperation during work on the LV protection circuits that communicate with the circuit breaker failure controller, a local criterion can be activated in order to permit only a tripping instruction to the central unit in the event of a fault on the feeder concerned.

Maintenance and testing must be able to be conducted safely by means of control via several levels of isolation.

In particular, it will have to be possible, without interfering with wiring, to configure the system in the following reduced modes of operation:

> Monitoring Mode – differential element de-activated, tripping prohibited but measurements still active.

> Complete isolation of the central functions with the local functions remaining operational.

> Local isolation of a peripheral unit without affecting the rest of the system.

Time tagged events, faults and disturbance records must be saved in battery backed memory. The internal disturbance recorder shall have a capacity to store 20 records, each record shall store data from 8 analogue channels and 32 digital channels.

It must be possible, using a graphical PC based software to monitor the plant status: • Position of CBs and isolators in the busbar scheme, • Differential and bias currents of all the zones & CZ, • Alarms (raised for any discrepancy condition between the

open and closed auxiliary contacts of the isolators and circuit breakers, CT failure, etc…).

The protocol IEC61850-8-1 must be available through a copper and fibre optic Ethernet communication ports

Page 27: 06. AREVA P740

P740 Technical Data Sheet EN 26 P740/EN TDS/K55

ORDERING INFORMATION

RELAY TYPE (BUSBAR PROTECTION RELAY) P741 AUXILIARY VOLTAGE RATING

24 – 48V DC ONLY 48 – 125V DC (30 – 110V AC) 110 – 250V DC (100 – 240V AC)

1 2 3

COMMUNICATION BOARDS

1 COMMUNICATION BOARD (2 TO 4 PERIPHERAL UNIT) 2 COMMUNICATION BOARD (2 TO 8 PERIPHERAL UNIT) 3 COMMUNICATION BOARD (2 TO 12 PERIPHERAL UNIT) 4 COMMUNICATION BOARD (2 TO 16 PERIPHERAL UNIT) 5 COMMUNICATION BOARD (2 TO 20 PERIPHERAL UNIT) 6 COMMUNICATION BOARD (2 TO 24 PERIPHERAL UNIT) 7 COMMUNICATION BOARD (2 TO 28 PERIPHERAL UNIT)

1 2 3 4 5 6 7

HARDWARE OPTIONS

NOTHING IRIG-B MODULATED ONLY IRIG-B DEMODULATED ONLY ETHERNET (100MBPS) ONLY ETHERNET (100MBPS)+IRIG-B (MODULATED) ETHERNET (100MBPS) IRIG-B (DEMODULATED)

1 2 C 6 A B

PRODUCT SPECIFIC

FIXED A

PROTOCOL OPTIONS

K-BUS/COURIER IEC60870-5-103 (VIA KITZ274) IEC 61850-8-1 (NEEDS ETHERNET BOARD)

1 1 6

MOUNTING

PANEL MOUNTING M

LANGUAGE

MULTILINGUAL – ENGLISH, FRENCH, GERMAN, SPANISH MULTILINGUAL – ENGLISH, FRENCH, GERMAN, RUSSIAN

0 5

SOFTWARE VERSION

UNLESS SPECIFIED THE LATEST VERSION WILL BE DELIVERED

* *

SETTINGS FILE

DEFAULT CUSTOMER SPECIFIC

0 1

HARDWARE SUFFIX

ORIGINAL K

Page 28: 06. AREVA P740

P740 Technical Data Sheet EN 27 P740/EN TDS/K55

RELAY TYPE (BUSBAR PROTECTION RELAY) P742 AUXILIARY VOLTAGE RATING

24 – 48V DC ONLY 48 – 125V DC (30 – 110V AC) 110 – 250V DC (100 – 240V AC)

1 2 3

HARDWARE OPTIONS

WITHOUT CT INPUT WITH CT INPUT

0 1

COMMUNICATION OPTIONS

NOTHING 1

PRODUCT SPECIFIC

FIXED A

PROTOCOL OPTIONS

K-BUS/COURIER IEC60870-5-103 (VIA KITZ274)

1 1

MOUNTING

PANEL MOUNTING M

LANGUAGE

MULTILINGUAL – ENGLISH, FRENCH, GERMAN, SPANISH MULTILINGUAL – ENGLISH, FRENCH, GERMAN, RUSSIAN

0 5

SOFTWARE VERSION

UNLESS SPECIFIED THE LATEST VERSION WILL BE DELIVERED

* *

SETTINGS FILE

DEFAULT CUSTOMER SPECIFIC

0 1

HARDWARE SUFFIX

ORIGINAL J

Page 29: 06. AREVA P740

P740 Technical Data Sheet EN 28 P740/EN TDS/K55

RELAY TYPE (BUSBAR PROTECTION RELAY) P743 AUXILIARY VOLTAGE RATING

24 – 48V DC ONLY 48 – 125V DC (30 – 110V AC) 110 – 250V DC (100 – 240V AC)

1 2 3

HARDWARE OPTIONS

WITHOUT CT INPUT WITH CT INPUT

0 1

COMMUNICATION OPTIONS

NOTHING ETHERNET (100MBPS) ONLY

1 6

PRODUCT SPECIFIC

FIXED A

PROTOCOL OPTIONS

K-BUS/COURIER IEC60870-5-103 (VIA KITZ274) IEC 61850-8-1 (NEEDS ETHERNET BOARD)

1 1 6

MOUNTING

PANEL MOUNTING M

LANGUAGE

MULTILINGUAL – ENGLISH, FRENCH, GERMAN, SPANISH MULTILINGUAL – ENGLISH, FRENCH, GERMAN, RUSSIAN

0 5

SOFTWARE VERSION

UNLESS SPECIFIED THE LATEST VERSION WILL BE DELIVERED

4 0

SETTINGS FILE

DEFAULT CUSTOMER SPECIFIC

0 1

HARDWARE SUFFIX

ORIGINAL K

Page 30: 06. AREVA P740

AREVA T&D's Automation & Information Systems Business www.areva-td.com T&D Worldwide Contact Centre online 24 hours a day: +44 (0) 1785 25 00 70 http://www.areva-td.com/contactcentre/

Pu

blic

atio

n:

P7

40

/EN

TD

S/K

55