gabrielandassociates.comgabrielandassociates.com/support-files/solart60mpu... · translate this...
TRANSCRIPT
5.2 MW Solar Mobile Power Unit
Neutral Grounding Resistor
Lube oil cooler
Leveling jacks & pads
Access stairs & platforms
Exhaust Silencer
Ventilation air intake
Gas & Liquid Fuel Connections
Air inlet & silencer
13.8 to 480 vac Aux. Power Transformer
Ventilationair exhaust
Power Control Room &Trailer-13.8 KV switchgear-CO2 fire system-480 VAC MCCC for turbineaccessories
-120VDC battery systems-Allen Bradley TT4000Monitor/control
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. PackageRapid Setup & CommissioningEase of transport…Land, Sea, & AirTotally self contained, Needs only…
o Gas and/or Liquid Fuel o 13.8kV load connectiono Black Start Requires 480VAC
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. Package
Parts ServiceOverhaulsUpgrades Retrofits
Solar T60 – Engine
Simple Cycle Single shaft axial flow engine Close Coupled to separate Gear Box Twelve-stage axial flow compressor Variable geometry control on inlet guide vanes and first three rows of statorsAnnular combustor with 12 fuel injectorsThree-stage turbine assembly
Standard Solar Taurus 60 Power Gen. Package
Solar T60 – Gear Box
Coupled directly to the turbine engineSpeed Reduciton from 13,800RPM to 1800 RPM
Solar T60 – Generator & Voltage Regulation
Ideal or AlstomSleeve Bearings with pressure fed sumpsSix-lead WYE connectionForm wound stator windingsPermanent magnet pilot exciter12,470 – 13,800 Volt, 3 phase, 60 Hz. 11kV, 3 phase, 50 Hz. Insulation class F with Voltage Regulator CharacteristicsSolid state, Single-phase sensing0.5% steady state voltage regulationReactive load sharing to within 5% nameplate ratingCrosscurrent compensation capability
Solar T60 – Dual Fuel System
Designed to operate on Natural Gas or Distillate Liquid Fuels
NATURAL GASo maximum flow demand rate of 1200 scfmo 250 psig minimum and 300 psig maximum
Distillate Liquid Fuelso maximum flow demand rate of 8.0 gpm. o 20ft. Suction minimum to 25 psig maximum
Solar T60 – Starter, Lube system
Direct drive AC motor with VFD motor controllerLube system provides oil to the Taurus 60 gas turbine engine, gear box and generator.
o Engine driven lube oil pumpo Pre/Post Lube AC Motor Driven Pumpo Pre/Post Lube DC Motor Drive Pumpo Lube Oil Sump (integral part of turbine skid) with
space heater, level controls, and thermostatic control valve.
o Horizontal core lube oil cooler mtd. on Power Control Room
Solar T60 – Auxiliary Systems
On Crank and On Line Water WashWEATHERPROOF ACOUSTIC ENCLOSURE
o Ventilation Silencers and Fans, o Lightso Fire Detection and Gas Monitoring System o High Temperature Detection and Alarmo CO2 Fire Suppression System.
High Efficiency Combustion Air Barrier Filter and Silencer Trailer mounted exhaust silencer
Solar T60 – Allen Bradley PLC5 Control System
Flexibility to change logic or add features
Relay backup in event of PLC failure
Operational summary Alarms, shutdowns, Temperatures, pressures, vibration, Engine performance, Generator kW, voltage, p.f., hz., amps, current.
Remote Video Display (TT4000) interface and monitoring.
Interface and monitoring in power control trailer via
Local operator interface and monitoring.
Sequencing of Starting, Running & shutdown
Package monitoring and protection
Solar Turbotronic Controller
Solar T60 Performance (ISO Conditions)
Table 1. Dual Fuel Performance Data ISO*, XQ5200 Mobile Power Unit
300% for 10 sec.300% for 10 sec.300% for 10 sec.300% for 10 sec.Short Circuit
0.5%0.5%0.5%0.5%Voltage Steady State
60 Hz.60 Hz.60 Hz.60 Hz.Gen. Frequency
12.47 or 13.8 KV12.47 or 13.8 KV12.47 or 13.8 KV12.47 or 13.8 KVGen. Voltage
50 PPMvd50 PPMvd50 PPMvd50 PPMvdCO
96 PPMvd96 PPMvd48 PPMvd25 PPMvd
48 PPMvd25 PPMvd (1.1 lb.)/MW-hr)
Emissions, NOX
61. mmkJ/hr 57.9 mmBTU/hr61.8 mmkJ/hr58.6 mmBTU/hrFuel Flow (LHV)
12,002 kJ/kWe-hr11,376 Btu/kWe-hr11,900 kJ/kWe-hr11,263 Btu/kWe-hrHeat Rate
5,089 kWe5,089 kWe5,200 kWe5,200 kWePower Output
MetricEnglishMetricEnglish
Diesel #2Diesel #2Natural GasNatural Gas
Solar T60 Performance
“TaurusTM 60, 7300 Industrial Gas Turbine
• ISO Conditions (5,200MWe)15o C (59o F) Sea Level, 0 Inlet/Exhaust LossesVaries with Air Temperature and Altitude
• Taurus 60 at 152 M (500 ft.)
5367 kWe @ 4.4o C (40o F)4345 kWe @ 32o C (90o F)
• Taurus 60 at 457M (1500 ft.)
5165 kWe @ 4.4o C (40o F)4182 kWe @ 32o C (90o F)
Mobile Turbine Design Goals
Standard Solar Taurus 60 Power Gen. PackageEase of transport…Land, Sea, & AirTotally self contained, Needs only…..
o Gas and/or Liquid Fuel o 13.8kV load connectiono Black Start Requires 480VAC
Ease of transport…Land, Sea, & Air
• Turbine Generator Trailer & 2-Axle Booster Unit
18.9M (62 ft.) Weight: 57MT (125,000 lbs.)
• Power Control Room Trailer14M (46 ft.) Weight: 25MT (55,000 lbs.)
• Shipped LooseStep deck or 12.2M (40 ft.) High Cube 8.2MT (18,000 lbs.)
• Designed for All U.S. States and Canadian Provinces
Self Contained Power Plant
Neutral Grounding Resistor
Lube oil cooler
Leveling jacks & pads
Access stairs & platforms
Exhaust Silencer
Ventilation air intake
Gas & Liquid Fuel Connections
Air inlet & silencer
13.8 to 480 vac Aux. Power Transformer
Ventilationair exhaust
Power Control Room &Trailer-13.8 KV switchgear-CO2 fire system-480 VAC MCCC for turbineaccessories
-120VDC battery systems-Allen Bradley TT4000Monitor/control
Easy Siting Requirements
• Low Profile7.3M (24 ft.) Stack Height
• Sound Attenuation Package85 dba @ 1 meterCSA/NRTL
Solar T60 MPU Product Features
Power Control Room
400 or 480 400 or 480 Volt Motor Volt Motor
Control Control CenterCenter
MetalMetal--Clad Clad 15Kv 15Kv
SwitchgearSwitchgear
Turbine & Turbine & Switchgear Switchgear
Battery Battery SystemsSystems
Beckwith Beckwith Programmable Programmable
Protective Protective Relay ModuleRelay Module
Generator Generator Voltage: Voltage:
11,000 or 11,000 or 13,800 Class F 13,800 Class F
Insulation/Insulation/Class FClass F
TemperatureTemperatureRiseRiseStepStep--down transformer &down transformer &
Neutral Grounding Neutral Grounding ResistorResistor
BaslerBasler Over Over Current RelaysCurrent Relays
Remote Dial-up (Modem)Historical Data
Solar T60 MPU Product Features
Turbotronic Controller, Allen Bradley PLC5(Turbine and Generator)
Auto SynchVoltage AdjustkW ControlKVAR/Power Factor Control
TT4000Remote Control and Monitoring:
Solar T60 MPU Installation Requirements
• Minimum Soil Loading• (2,500 lb./ft2) 12.2MT/M2
Flat and Level Surface
• Gas Supply (240-300 psig) 1725- 2068 KPAG Gas Supply
Distillate Liquid Fuelso maximum flow demand rate of 8.0 gpm. o 20ft. Suction minimum to 25 psig maximum
• 15kV load connections to PCRTurbine AC and DC auxiliary loads powered Internally
• Grounding to Grid• 480VAC, 400A Black Start
Solar T60 MPU Installation Requirements (cont’)
• Small Drain Tank, 70 L (20 gal.)
• Crane with Lifting Capability of 2.5MT (5,500 lbs.)
• Installation and Commissioning
3 Man Crew to InstallStandard Hand Tools5-7 Days to Commission
• Input Signal From Utility Tie Breaker
Island Mode Operation
Solar T60 MPU Operations and Service
• Rental Rate Covers all Maintenance, inspections and Failure Repair.
• Routine Daily Maintenance by End User or Peterson Operators (if provided)
• Typical Overhaul Interval is 30,000 Hours
• Overhaul by Exchange of Entire Turbine
• Limited Field Maintenance, 2 Inspections/Year
Maintenance and Operation