longwood · 2009-08-14 · trs: 711 august 14, 2009 addendum 4 to all bidders: ... 703/908-4502...

39
LONGWOOD U N I V E R S I T Y 201 High Street Farmville, Virginia 23909 tel: 434.395.2093 fax: 434.395.2246 trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: Reference Invitation for Bids: 214-10-JarmanRenovations Commodity: Jarman Auditorium Renovations Project Code: 214-16301 Dated: July 17, 2009 For Delivery To: Longwood University Materiel Management Office Farmville, Virginia 23909-1896 Bid Due: August 25, 2009 at 2:00 p.m. Local Time This Addendum 4 to the Invitation for Bids is being issued to extend the date for receipt of bids to August 25, 2009 at 2:00 p.m. Local Time, extend the date for public opening and reading of bids to August 26, 2009 at 2:00 p.m. Local Time and to publish Addendum No. 4 from the project architect, Little Diversified Architectural Consulting. Addendum consists of the following documents: This Addendum 4 To All Bidders: 1 page Narrative document: 9 pages Project Manual Sections: 14 pages 00 01 15 Statement of VUSBC Special Inspections DGS Form CO-6a 06 16 00 Sketches: 1 page ADD-A-003 Full Size Drawings: 14 pages SP201 E303 SP204 E304 SP501 E402 M301 E403 M302 E701 E001 E901 E302 E903 All other general terms, conditions, and specifications shall remain the same. Please acknowledge receipt of this Addendum 4 on the Bid Form, DGS-30-220, when returning your bid package. Very truly yours, James E. Simpson, CPPB, VCO Director of Materiel Management

Upload: nguyendien

Post on 09-Sep-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

LONGWOOD U N I V E R S I T Y

201 High Street

Farmville, Virginia 23909

tel: 434.395.2093

fax: 434.395.2246 trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: Reference Invitation for Bids: 214-10-JarmanRenovations Commodity: Jarman Auditorium Renovations Project Code: 214-16301 Dated: July 17, 2009 For Delivery To: Longwood University Materiel Management Office Farmville, Virginia 23909-1896 Bid Due: August 25, 2009 at 2:00 p.m. Local Time This Addendum 4 to the Invitation for Bids is being issued to extend the date for receipt of bids to August 25, 2009 at 2:00 p.m. Local Time, extend the date for public opening and reading of bids to August 26, 2009 at 2:00 p.m. Local Time and to publish Addendum No. 4 from the project architect, Little Diversified Architectural Consulting. Addendum consists of the following documents:

This Addendum 4 To All Bidders: 1 page

Narrative document: 9 pages

Project Manual Sections: 14 pages

• 00 01 15 Statement of VUSBC Special Inspections – DGS Form CO-6a

• 06 16 00

Sketches: 1 page

• ADD-A-003

Full Size Drawings: 14 pages

• SP201 • E303

• SP204 • E304

• SP501 • E402

• M301 • E403

• M302 • E701

• E001 • E901

• E302 • E903

All other general terms, conditions, and specifications shall remain the same. Please acknowledge receipt of this Addendum 4 on the Bid Form, DGS-30-220, when returning your bid package.

Very truly yours,

James E. Simpson, CPPB, VCO Director of Materiel Management

Page 2: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 1 of 9

Little Diversified Architectural Consulting 4501 N. Fairfax Drive, Suite 120 Arlington, VA 22203 Phone: 703/908-4501 Fax: 703/908-4502 LITTLE Project No. 213-4546-00

NOTICE TO CONTRACTOR: Items revised on full-size drawings are each designated by a cloud line and a triangle surrounding the revision number corresponding to that addendum. Drawing items revised in the form of 8 ½” x 11” or 11” x 17” sheets will each receive sketch number designations with the prefix of the discipline whose drawing is being modified (example: ADD-A--#, ADD-S-#, ADD-M-#), with changes designated with cloud lines similar to those on full-size drawings. The list below may include items for which a written description alone is sufficient, with no corresponding revised drawings or specification pages attached to the addendum form. The following clarifications, amendments, additions, deletions, revisions and modifications are hereby made a part of the Contract Documents, and change the original documents only in the manner and to the extent stated below.

ADDENDUM NO. 4 Addendum No.4 consists of the following: Narrative document: 9 pages Project Manual Sections: 14 pages

• 00 01 15 Statement of VUSBC Special Inspections - DGS Form CO-6a

• 06 16 00 Sheathing Sketches: 1

• ADD-A-003

Full Size Drawings: 14

• SP-201

• SP-204

• SP-501

• M301

• M302

• E001

• E302

• E303

• E304

• E402

• E403

• E701

• E901

• E903

Page 3: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 2 of 9

Response to Bidder Questions:

1. C. L. Lewis: How are we supposed to address notes 6, 7, and 8 on C3.0? Most subs who bid the utility work would not have the appropriate time or probably authority to investigate these items before the bid date. If a value to perform these items needs to be included in the cost of the work, a more appropriate suggestion would be for an allowance to be included in the bid. Please advise. Response: bid the work regarding note 6 on C3.0 as ‘abandoned’. Bid the work regarding note 7 on C3.0 as ‘Investigate the existing service lateral, protect it during construction, replace in-kind if damaged, and relocate the meter behind the curb’. Bid the work regarding note 8 on C3.0 as shown with the information provided that this line is solely a storm sewer.

2. Creative Electrical Contractors Inc. 1) Drawing E101 says “provide 6-4” Ductbank with 3 sets of 4-500KCMIL + 1 #2 Ground”. Drawing E701, Note 2 says “run 4 sets of 4-350KCMIL 1 1-1/0 Ground in 6-4” Conduit Ductbank Minimum of 36” Below Grade to C/T Cabinet. Which is correct? Response: Drawing E101 is correct. Will revise drawing E701 to read the same conductor size as indicated on E101.

3. Creative Electrical Contractors Inc. 2) Drawing E301 shows the Dressing Room Areas. Does the Fixture Type FF Wrap around the Mirror on three sides at each individual station of the makeup counter or does it wrap around the mirror on three sides for the entire length of the makeup counter: Response: Fixture type FF is to run continuously across the top of the mirror.

4. Donald Lane, EMC Mechanical Services 1) General note #1 on sheet M501 states that all ductwork in the mechanical room will be lined with 2” liner. Will that include the fresh air and exhaust duct also and if so would that include the exhaust outside of the mechanical room as well? Response: Yes, all ductwork will require the 2” liner mentioned above.

5. Donald Lane, EMC Mechanical Services 2) General note #2 on sheet M301 states that all ductwork for the auditorium and lobby area from AHU-1 is to have 2” liner. Will the round duct shown on drawing M303 in the balcony area be lined as well? I can’t seem to find a spec on double wall duct anywhere. Response: Yes, all ductwork will require the 2” liner mentioned above.

6. Donald Lane, EMC Mechanical Services 3) Spec 23 31 13 – 11, section 3.9 Duct Schedule, paragraph B. 2 says that ducts connected to constant volume air handling units will be 3 inch wg. Typically low pressure is 1 and 2 inch wg and medium pressure would be 3 and 4 inch wg. Will this duct be considered to be medium pressure? Also paragraph B. 3 for ducts connected to variable volume air handling units shows a wg of 23 inch’s. Should this be 2 or 3 inch wg? Response: ductwork must be constructed in accordance with SMACNA duct construction standards for the pressure classification, seal class and leakage class listed in the specification. The “low pressure” and “medium pressure” distinctions are no longer recognized by SMACNA. The pressure class for supply ducts on VAV systems should be 3-inch wg.

Page 4: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 3 of 9

7. Steve Tyree, Moores Electrical & Mechanical Construction: 1) Sheet E001, Light fixtures shown to be selected by architect. Are we to include an allowance for them or just labor to install them. Response: Please see attached revised fixture schedule.

8. Steve Tyree, Moores Electrical & Mechanical Construction: 2): Are we allowed to run surface raceway (wiremold) on existing walls not getting furred out? Response: Yes, surface raceway may be utilized in a workman like manner, only where existing walls are not furred out.

9. Ron McManamay, Gaston Wyatt Inc. Question After a careful review of the specifications, we have decided to propose quoting the Kingsview Single Hung by Hurd Windows on the project. These four specification section presented issues. Are these acceptable exceptions to the specifications: SECTION 085200 WOOD WINDOWS Section 1.5 B, 1.6 C – Hurd does not manufacture products with FSC certified lumber. Section 2.3 F – Currently, Hurd has not conducted STC testing on the Kingsview Single Hung. Hurd has achieved an STC 33 rating on the Premium Clad Double Hung utilizing the same glass as the Kingsview. The Kingsview is scheduled for STC testing in the near future and Hurd is confident the test report will confirm an STC rating exceeding the requirement of this project. Section 2.3 I, J – Hurd has not conducted Life Cycle and Durability tests on the Kingsview Single Hung SECTION 088000 GLAZING Section 2.2 F.5 – Insulating glass spacer will be mill finish aluminum in lieu or black anodized as specified Response: The University is open to alternative manufactures who can meet the performance requirements indicated in the specification. Provided windows need to meet or exceed the specified performance standards.

10. Creative Electrical Contractors, Inc: The lighting fixture schedule has a Type K fixture in it. This fixture does not appear on the drawings. is this fixture supposed to be used and if so what lengths? What circuits fed this fixture? How is the fixture supposed to be mounted? Response: The type K fixture is a low voltage LED fixture that comes in 18”, 36” and 54”. The fixture is to be provided in five 36” lengths mounted under the 15’5” transaction counter at the front reception desk. The lighting fixture is to be connected to the nearest 277v lighting branch circuit.

Narrative of Modifications: Project Manual Modifications:

1. Invitation For Bids (IFB) – Bid period is extended: Sealed bids will be received until August 25, 2009 at 2:00 P.M. Local Time for furnishing the good/services described herein and then opened in public and read aloud on August 26, 2009 at 2:00 local time at the same location.

2. Section 00 01 15 - Statement of VUSBC Special Inspections - DGS Form CO-6a – replace 6 page from with attached 6 page form.

3. Section 06 16 00 Sheathing - Replace specification section with the attached section.

Page 5: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 4 of 9

4. Section 230958 – Add paragraphs 3.03.G.1 and 3.03.G.2 as follows:

1. When the OA temperature falls below 39°F (adj.), the heating coil circulating pump shall be energized.

2. When the OA temperature is above 40°F (adj.), the heating coil circulating pump shall be de-energized.

5. Section 230958 – Replace paragraph 3.06.E and 3.06.F with the following:

E. Heating Coil Valve: N.O. heating coil valve shall modulate by a DA PID loop to maintain return air setpoint. Heating coil valve shall open 100% upon freezestat trip.

1. When the OA temperature falls below 39°F (adj.), the heating coil circulating pump shall be energized.

2. When the OA temperature is above 40°F (adj.), the heating coil circulating pump shall be de-energized.

F. Cooling Coil Valve: N.C. cooling coil valve shall modulate by a DA PID loop to maintain return air setpoint. Cooling coil valve shall open 100% upon freezestat trip.

6. Section 23 09 58 – Add paragraph 3.06.H as follows:

H. Total Energy Wheel (AHU-1 only): The total energy wheel shall operate whenever the unit is operating in Occupied mode.

7. Section 23 09 58 – Replace paragraph 3.08 JARMAN HALL MISCELLANEOUS FANS

with the following:

3.08 JARMAN HALL MISCELLANEOUS FANS

A. EF-1 (Toilet Exhaust Fan)

1. The fan shall be controlled by FMS and interlocked with the operation of AHU-2.

2. When the exhaust fan is energized, the motorized damper associated with the exhaust fan shall open. When damper operation is proven through the end-switch, the fan shall be started. When the exhaust fan is de-energized, the fan shall stop and the motorized damper shall close.

3. FMS shall prove fan operation and use the status indication to accumulate runtime. Upon failure of the exhaust fan, FMS shall report a Level 3 alarm.

B. EF-2 (Mechanical Annex Ventilation and Refrigerant Purge Fan)

1. The fan shall be controlled by FMS.

2. When the room temperature as sensed by the wall-mounted temperature sensor exceeds the room temperature set point (78°F (adj.)), the fan shall be energized. When the fan is energized, the motorized damper at the outdoor air intake plenum shall open and the motorized damper associated with the fan shall open. When the damper operation is proven through the end-switch, the fan shall be started at low speed.

Page 6: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 5 of 9

3. When the room temperature falls 3°F (adj.) below the room temperature set point, the fan shall stop and the motorized damper shall close.

4. When the refrigerant leak detection system reports an alarm condition, the FMS shall override the fan on, open the outdoor air intake motorized damper, open the motorized damper associated with the fan and start the fan at high speed. Operation of the fan shall continue until the refrigerant leak detection system alarm clears.

5. FMS shall prove fan operation and use the status indication to accumulate runtime. Upon failure of the exhaust fan, FMS shall report a Level 3 alarm.

C. EF-3 and EF-4 (Toilet Exhaust Fans)

1. The fans shall be controlled by FMS and interlocked with the operation of AHU-1.

2. When the exhaust fan is energized, the motorized damper associated with the exhaust fan shall open. When damper operation is proven through the end-switch, the fan shall be started. When the exhaust fan is de-energized, the fan shall stop and the motorized damper shall close.

3. FMS shall prove fan operation and use the status indication to accumulate runtime. Upon failure of the exhaust fan, FMS shall report a Level 3 alarm.

D. EF-5 (Stage Relief Fan)

1. The fan shall be controlled by FMS and interlocked with the operation of AHU-3.

2. When the exhaust fan is energized, the motorized damper associated with the exhaust fan shall open. When damper operation is proven through the end-switch, the fan shall be started. When the exhaust fan is de-energized, the fan shall stop and the motorized damper shall close.

3. FMS shall prove fan operation and use the status indication to accumulate runtime. Upon failure of the exhaust fan, FMS shall report a Level 3 alarm.

E. EF-6 (Mezzanine Mechanical Room Ventilation Fan)

1. The fan shall be controlled by FMS.

2. When the room temperature as sensed by the wall-mounted temperature sensor exceeds the room temperature set point (78°F (adj.)), the fan shall be energized. When the fan is energized, the motorized damper at the outdoor air intake plenum shall open and the motorized damper associated with the fan shall open. When the damper operation is proven through the end-switch, the fan shall be started at low speed.

3. When the room temperature falls 3°F (adj.) below the room temperature set point, the fan shall stop and the motorized damper shall close.

4. FMS shall prove fan operation and use the status indication to accumulate runtime. Upon failure of the exhaust fan, FMS shall report a Level 3 alarm.

Drawing Modifications:

1. Sheets FP101 thru FP103 – add the following general note: Provide one fire extinguisher at each FEC indicated. Minimum rated single extinguisher shall be type 2-A per specification section 10 44 16.

Page 7: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 6 of 9

2. Sheets FP101 thru FP103 – add the following general note: provide posted occupancy signs in all spaces with an occupant load of 50 or more people to meet the requirements of VCC 1004.3. Provide stairway floor number signs to meet the requirements of 1020.1.6 in stairway number 4.

3. Sheet A901 – Finish Schedule – Revised comment note at rooms 221A, 221B, 221C, 222A, & 222B, to read - provide new fire-retardant treated plywood subfloor per specification section 06 16 00.

4. Sheet A601 – Drawing 3 – see attached detail for indicated 1 hour fire resistive joint assembly UL Joint System HW-D-0026.

5. Sheet A701 – Drawing 1 – vertical spacing dimension of wall sconce fixtures is indicated on sketch ADD-A-003

6. SP201 – Added two Detail 5 call-outs for inspector’s test.

7. SP204 – Added Key Note 2 to floor plan.

8. SP501 – Deleted references to Sheet SP201 on Details 2, 3 and 4.

9. Sheet M301 - Fire dampers have been added to the transfer ducts penetrating 1-hour fire barriers in eight (8) locations.

10. Sheet M302 - Fire dampers have been added to the transfer ducts penetrating 1-hour fire barriers in four (4) locations.

11. Sheet E001 – Replaced description of Fixture F on the Lighting Fixture Schedule.

12. Sheet E302 – Deleted KeyNote #5. Added General Notes #1 and #2. Revised various circuits related to the ELTS.

13. Sheet E303 – Added KeyNote #6. Added General Note #2. Revised aisle lighting at balcony. Revised lighting for speaker boxes. Revised various circuits related to the ELTS.

14. Sheet E304 – Added General Notes #1 and #2. Revised various circuits related to the ELTS.

15. Sheet E402 – Revised various circuit designations. Added receptacles at front of stage. Moved four receptacles from west side of stage to east side of stage. Added two cable TV outlets.

16. Sheet E403 – Added isolated ground receptacle in each Speaker Closet. Revised various circuit designations.

17. Sheet E701 – Added Housing Lighting Dimmer Rack.

18. Sheet E901 – Revised Panel PMA. Revised Panel PMC. Added General Sheet Notes.

19. Sheet E903 – Revised Panel PMB. Added General Sheet Notes.

Page 8: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 7 of 9

System No. HW-D-0026

April 16, 2009

Assembly Rating — 1, 2, 3 and 4 Hr (See Item 2)

Nominal Joint Width — 3/4 In.

Class II Movement Capabilities — 33% Compression or Extension

1. Floor Assembly — The fluted steel deck/concrete floor assembly shall

be constructed of the materials and in the manner described in the

individual Floor-Ceiling Design in the UL Fire Resistance Directory. The

hourly rating of the floor assembly shall be equal to or greater than the

hourly rating of the wall assembly and shall include the following

construction features:

A. Steel Floor and Form Units* — Max 3 in. (76 mm)

deep galv steel fluted units.

B. Concrete — Min 2-1/2 in. (64 mm) thick reinforced

concrete, as measured from the top plane of the floor units.

1A. Roof Assembly — (Not Shown)—As an alternate to the floor

assembly, a fire rated fluted steel deck roof assembly may be used. The

roof assembly shall be constructed of the materials and in the manner

described in the individual P900 Series Roof-Ceiling Design in the UL

Fire Resistance Directory. The hourly rating of the roof assembly shall be

equal to or greater than the hourly rating of the wall assembly and shall

include the following construction features:

Page 9: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 8 of 9

A. Steel Roof Deck — Max 3 in. (76 mm) deep galv steel

fluted roof deck.

B. Roof Insulation — Min 2-1/4 in. (57 mm) thick poured

insulating concrete, as measured from the top plane of the

floor units.

C. Roof Covering* — Hot-mopped or cold-application

materials compatible with insulating concrete.

2. Wall Assembly — Min 4-7/8, 6-1/8, 7-3/8 and 8-5/8 in. (124, 156, 187

and 219 mm) thick reinforced lightweight or normal weight (100-150 pcf

or 1600-2400 kg/m3) structural concrete for 1, 2, 3 and 4 hr rated

assemblies, respectively. Wall may also be constructed of any UL

Classified Concrete Blocks*.

See Concrete Blocks (CAZT) category in the Fire Resistance Directory

for names of manufacturers.

3. Joint System — Max separation between bottom of floor and top of

wall is 3/4 in. (19 mm). The joint system is designed to accommodate a

max 33 percent compression or extension from its installed width. The

joint system consists of a forming material and a fill material as follows:

A. Forming Material* — Min 4-7/8 in. (124 mm)

thickness of min 4 pcf (64 kg/m3) density mineral wool batt

insulation cut to the shape of the fluted deck, approx 25

percent larger than the area of the flutes with additional min

4-7/8 in. (124 mm) thick by 1 in. (25 mm) high sections at

the bottom of the shapes to completely fill the 3/4 in. (19

mm) gap between the top of the wall and bottom of the

steel floor units. Mineral wool to be compressed and firmly

packed into the flutes and the gap between the top of the

wall and bottom of the steel floor units, flush with both

sides of wall.

FIBREX INSULATIONS INC — FBX Safing Insulation

IIG MINWOOL L L C — MinWool-1200 Safing

ROCK WOOL MANUFACTURING CO — Delta Board

ROXUL INC — Safe

THERMAFIBER INC — Type SAF

Page 10: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

ADDENDUM NO. 4 LITTLE 14 August 2009 Jarman Auditorium Renovation Longwood University Farmville, Virginia BCOM Project ID No 214-16301-000

ADDENDUM No. 4 9 of 9

B. Fill, Void or Cavity Material* — Min 1/8 in. (3.2 mm)

wet thickness (min 1/16 in. or 1.6 mm dry thickness) of fill

material sprayed or brushed on each side of the wall in the

flutes of the steel floor units and between the top of the

wallboard and the bottom of the steel floor units to

completely cover mineral wool and to overlap a min of 1

in. (25 mm) onto wall and steel deck on both sides of wall.

PASSIVE FIRE PROTECTION PARTNERS —

3500SI, 5100SP

*Bearing the UL Classification Mark

END OF ADDENDUM NARRATIVE

Page 11: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 12: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 13: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 14: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 15: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 16: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 17: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 1

SECTION 06 16 00 - SHEATHING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1. Procedures for compliance with certain US Green Building Council’s (USGBC) LEED prerequisites and credits needed for the Project to obtain LEED certification apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Wall sheathing. 2. Subfloor sheathing. 3. Underlayment. 4. Building wrap. 5. Sheathing joint-and-penetration treatment. 6. Flexible flashing at openings in sheathing.

1.3 SUBMITTALS

A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.

1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements. Indicate type of preservative used and net amount of preservative retained.

2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements. Include physical properties of treated materials.

3. For fire-retardant treatments specified to be High-Temperature (HT) type, include physical properties of treated plywood both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency according to ASTM D 5516.

Page 18: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 2

4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.

5. Include copies of warranties from chemical treatment manufacturers for each type of treatment.

6. For building wrap, include data on air-/moisture-infiltration protection based on testing according to referenced standards.

B. LEED Submittals:

1. Credit EQ 4.1: Manufacturers' product data for construction adhesive, including printed statement of VOC content.

2. Credit EQ 4.4: Composite wood manufacturer's product data for each composite wood product used on the interior of building indicating that bonding agent used contains no urea formaldehyde.

3. Credit MR 7: Certificates of chain-of-custody signed by manufacturers certifying that products specified to be made from certified wood were made from wood obtained from forests certified by an FSC-accredited certification body to comply with FSC 1.2, "Principles and Criteria." Include evidence that mill is certified for chain-of-custody by an FSC-accredited certification body.

C. Research/Evaluation Reports: For the following, showing compliance with building code in effect for Project:

1. Preservative-treated plywood. 2. Fire-retardant-treated plywood. 3. Building wrap.

1.4 QUALITY ASSURANCE

A. Fire-Test-Response Characteristics: For assemblies with fire-resistance ratings, provide materials and construction identical to those of assemblies tested for fire resistance per ASTM E 119 by a testing and inspecting agency acceptable to authorities having jurisdiction.

1. Fire-Resistance Ratings: Indicated by design designations from UL's "Fire Resistance Directory."

B. Forest Certification: For the following wood products, provide materials produced from wood obtained from forests certified by an FSC-accredited certification body to comply with FSC 1.2, "Principles and Criteria":

1. Plywood.

Page 19: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 3

1.5 DELIVERY, STORAGE, AND HANDLING

A. Stack plywood and other panels flat with spacers between each bundle to provide air circulation. Provide for air circulation around stacks and under coverings.

PART 2 - PRODUCTS

2.1 WOOD PANEL PRODUCTS, GENERAL

A. Plywood: Either DOC PS 1 or DOC PS 2, unless otherwise indicated.

B. Thickness: As needed to comply with requirements specified, but not less than thickness indicated.

C. Factory mark panels to indicate compliance with applicable standard.

2.2 PRESERVATIVE-TREATED PLYWOOD

A. Preservative Treatment by Pressure Process: AWPA C9.

1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium.

B. Mark plywood with appropriate classification marking of an inspection agency acceptable to authorities having jurisdiction.

C. Application: Treat items indicated on Drawings and plywood in contact with masonry or concrete or used with roofing, flashing, vapor barriers, and waterproofing.

2.3 FIRE-RETARDANT-TREATED PLYWOOD

A. General: Comply with performance requirements in AWPA C27.

1. Use treatment that does not promote corrosion of metal fasteners. 2. Use Exterior type for exterior locations and where indicated.

B. Kiln-dry material after treatment to a maximum moisture content of 15 percent. Do not use material that is warped or does not comply with requirements for untreated material.

C. Identify fire-retardant-treated plywood with appropriate classification marking of UL, U.S. Testing, Timber Products Inspection, or another testing and inspecting agency acceptable to authorities having jurisdiction.

D. Application: Treat plywood indicated on Drawings.

Page 20: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 4

2.4 WALL SHEATHING

A. Plywood Wall Sheathing: Exterior, Structural I sheathing.

1. Span Rating: Not less than 24/0. 2. Nominal Thickness: Not less than 1/2 inch.

B. Glass-Mat Gypsum Wall Sheathing: ASTM C 1177/1177M.

1. Basis of Design Product: Subject to compliance with requirements, provide "Dens-Glass Gold" by G-P Gypsum Corporation.

2. Type and Thickness: Type X, 5/8 inch thick. 3. Size: 48 by 108 inches for vertical installation.

2.5 SUBFLOOR SHEATHING

A. Plywood Subflooring: Exterior, Structural I, fire treated floor panels.

1. Span Rating: Not less than 24 o.c. 2. Nominal Thickness: 1 inch.

2.6 FASTENERS

A. General: Provide fasteners of size and type indicated that comply with requirements specified in this Article for material and manufacture.

B. Power-Driven Fasteners: NES NER-272.

C. Screws for Fastening Gypsum Sheathing to Cold-Formed Metal Framing: Steel drill screws, in length recommended by sheathing manufacturer for thickness of sheathing board to be attached, with organic-polymer or other corrosion-protective coating having a salt-spray resistance of more than 800 hours according to ASTM B 117.

1. For steel framing less than 0.0329 inch thick, attach sheathing to comply with ASTM C 1002.

2. For steel framing from 0.033 to 0.112 inch thick, attach sheathing to comply with ASTM C 954.

D. Screws for Fastening Oriented-Strand-Board-Surfaced, Polyisocyanurate-Foam Sheathing to Metal Roof Deck: Steel drill screws, in type and length recommended by sheathing manufacturer for thickness of sheathing board to be attached, with organic-polymer or other corrosion-protective coating having a salt-spray resistance of more than 800 hours according to ASTM B 117. Provide washers or plates if recommended by sheathing manufacturer.

Page 21: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 5

2.7 WEATHER-RESISTANT SHEATHING PAPER

A. Building Paper: ASTM D 226, Type 1 (No. 15 asphalt-saturated organic felt), unperforated.

B. Building Wrap: ASTM E 1677, Type I air retarder, non-woven, spun-bonded, non perforated polyolefin film; with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, when tested according to ASTM E 84; UV stabilized; and acceptable to authorities having jurisdiction.

1. Products: Subject to compliance with requirements, provide one of the following:

a. Dow Chemical Company (The); Styrofoam Weathermate Plus Brand Housewrap.

b. DuPont (E. I. du Pont de Nemours and Company); Tyvek CommercialWrap.

c. Ludlow Coated Products; Barricade Building Wrap.

2. Water-Vapor Permeance: Not less than 20 perms when tested per ASTM E 96 Method B.

3. Allowable UV Exposure Time: Not less than three months.

C. Building-Wrap Tape: Pressure-sensitive plastic tape recommended by building-wrap manufacturer for sealing joints and penetrations in building wrap.

D. Building Wrap Fasteners: Mechanical fasteners with plastic-cap washers spaced as recommended by building-wrap manufacturer for attaching building wrap.

2.8 MISCELLANEOUS MATERIALS

A. Flexible Flashing: Composite, self-adhesive, flashing product consisting of a pliable, rubberized-asphalt compound, bonded to a high-density, cross-laminated polyethylene film to produce an overall thickness of not less than 0.030 inch.

1. Products: Subject to compliance with requirements, provide one of the following:

a. Carlisle Coatings & Waterproofing; CCW-705-TWF Thru-Wall Flashing.

b. Grace Construction Products, a unit of W. R. Grace & Co. - Conn.; Vycor Plus Self-Adhered Flashing.

c. Polyguard Products, Inc.; Polyguard 300.

B. Primer for Flexible Flashing: Product recommended by manufacturer of flexible flashing for substrate.

Page 22: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 6

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Do not use materials with defects that impair quality of sheathing or pieces that are too small to use with minimum number of joints or optimum joint arrangement.

B. Cut panels at penetrations, edges, and other obstructions of work; fit tightly against abutting construction, unless otherwise indicated.

C. Securely attach to substrate by fastening as indicated, complying with the following:

1. NES NER-272 for power-driven fasteners. 2. Table 2304.9.1, "Fastening Schedule," in ICC's "International Building

Code."

D. Use common wire nails, unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections. Install fasteners without splitting wood.

E. Coordinate wall sheathing installation with flashing and joint-sealant installation so these materials are installed in sequence and manner that prevent exterior moisture from passing through completed assembly.

F. Do not bridge building expansion joints; cut and space edges of panels to match spacing of structural support elements.

G. Coordinate sheathing installation with installation of materials installed over sheathing so sheathing is not exposed to precipitation or left exposed at end of the workday when rain is forecast.

3.2 GYPSUM SHEATHING INSTALLATION

A. Comply with GA-253 and with manufacturer's written instructions.

1. Fasten gypsum sheathing to cold-formed metal framing with screws. 2. Install boards with a 3/8-inch gap where non-load-bearing construction

abuts structural elements. 3. Install boards with a 1/4-inch gap where they abut masonry or similar

materials that might retain moisture, to prevent wicking.

B. Apply fasteners so heads bear tightly against face of sheathing boards but do not cut into facing.

Page 23: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 7

C. Horizontal Installation: Install sheathing with V-grooved edge down and tongue edge up. Interlock tongue with groove to bring long edges in contact with edges of adjacent boards without forcing. Abut ends of boards over centers of studs, and stagger end joints of adjacent boards not less than one stud spacing. Attach boards at perimeter and within field of board to each steel stud.

1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of boards.

2. For sheathing under stucco cladding, boards may be initially tacked in place with screws if overlying self-furring metal lath is screw-attached through sheathing to studs immediately after sheathing is installed.

D. Vertical Installation: Install board vertical edges centered over studs. Abut ends and edges of each board with those of adjacent boards. Attach boards at perimeter and within field of board to each stud.

1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of boards.

3.3 SUBFLOOR SHEATHING INSTALLATION

A. Comply with AHA’s “Application Instructions for Basic Hardboard Products” and with manufacturer’s written instructions for preparing and applying subfloor.

B. Space panels 1/8 inch apart at edges and ends.

1. Fastening Method: Nailing of subfloor.

3.4 WEATHER-RESISTANT SHEATHING-PAPER INSTALLATION

A. General: Cover sheathing with weather-resistant sheathing paper as follows:

1. Cut back barrier 1/2 inch on each side of the break in supporting members at expansion- or control-joint locations.

2. Apply barrier to cover vertical flashing with a minimum 4-inch overlap, unless otherwise indicated.

B. Building Paper: Apply horizontally with a 2-inch overlap and a 6-inch end lap; fasten to sheathing with galvanized staples or roofing nails.

C. Building Wrap: Cover exterior wall sheathing with building wrap as indicated with properly shingled overlap in compliance with manufacturer’s written instructions.

1. Cover upstanding metal flashing with a minimum of 4 inch overlap. 2. Cover vertical and horizontal seams with a minimum of 6 inch overlap.

Page 24: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

August 14, 2009 Jarman Auditorium Renovation Project Code 214-16301-000 Addendum No. 4 Little Project No. 213-4546-00

SHEATHING 06 16 00 - 8

3. Fasten building wrap with mechanical fasteners with plastic cap washers at spacing required by manufacturer and local authorities having jurisdiction.

4. Seal seams with pressure-sensitive plastic tape as recommended by building wrap manufacturer.

5. Extend building wrap into jamb openings and flash with manufacturer approved flashing tape.

6. Wrap and flash terminations and penetrations in shingle fashion per manufacturer’s written instructions.

3.5 FLEXIBLE FLASHING INSTALLATION

A. Apply flexible flashing where indicated to comply with manufacturers written instructions.

1. Prime substrates as recommended by flashing manufacturer. 2. Lap seams and junctures with other materials at least 4 inches, except

that at flashing flanges of other construction, laps need not exceed flange width.

3. Lap flashing over weather-resistant building paper at bottom and sides of openings.

4. After flashing has been applied, roll surfaces with a hard rubber or metal roller to ensure that flashing is completely adhered to substrates.

END OF SECTION 06 16 00

Page 25: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)

NEW DOOR55 STCASSEMBLY

ACOUSTIC CONTROLCURTAIN (ACC)

ACC-3

PT-3

PT-0

PT-0

WC-1WC-1

PT-3

11"

11"

1' -

6"

MIN

7'-0"

4

w w w . l i t t l e o n l i n e . c o m

This drawing and the design shown are theproperty of Little Diversified ArchitecturalConsulting. The reproduction, copying orother use of this drawing without their writtenconsent is prohibited and any infringementwill be subject to legal action.T: 703.908.4501 F: 703.908.4502

4501 North Fairfax Drive Suite 120Arlington, VA 22203

PROJECT MANAGER

DESIGN TEAM

PRINCIPAL IN CHARGE

PROJECT NAME BCOM PROJECT ID NO.

ISSUE DATE

BETH BUFFINGTON

RICHARD NAAB

WILL NORTON

REFERENCE

SKETCH NUMBER

DESCRIPTION

214-16301-000Longwood UniversityFarmville, Virginia

Jarman Auditorium Renovation

08.14.2009

ADD-A-003

1/A701 - Auditorium InteriorElevation East - light fixturesdimentioned

ADDENDUM 4

Page 26: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 27: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 28: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 29: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 30: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 31: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 32: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 33: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 34: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 35: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 36: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 37: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 38: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)
Page 39: LONGWOOD · 2009-08-14 · trs: 711 August 14, 2009 ADDENDUM 4 TO ALL BIDDERS: ... 703/908-4502 LITTLE Project No ... (Mechanical Annex Ventilation and Refrigerant Purge Fan)