********************************************************** 01 45 35.pdf · structural observations...

22
************************************************************************** USACE / NAVFAC / AFCEC / NASA UFGS-01 45 35 (February 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-01 45 35 (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement with UMRL dated April 2018 ************************************************************************** SECTION TABLE OF CONTENTS DIVISION 01 - GENERAL REQUIREMENTS SECTION 01 45 35 SPECIAL INSPECTIONS 02/15 PART 1 GENERAL 1.1 REFERENCES 1.2 GENERAL REQUIREMENTS 1.3 DEFINITIONS 1.3.1 Continuous Special Inspections 1.3.2 Periodic Special Inspections 1.3.3 Perform 1.3.4 Observe 1.3.5 Special Inspector (SI) 1.3.6 Associate Special Inspector (ASI) 1.3.7 Third Party 1.3.8 Special Inspector of Record (SIOR) 1.3.9 Contracting Officer 1.3.10 Contractor's Quality Control (QC) Manager 1.3.11 Designer of Record (DOR) 1.3.12 Statement of Special Inspections (SSI) 1.3.13 Schedule of Special Inspections 1.3.14 Designated Seismic System 1.4 SUBMITTALS 1.5 SPECIAL INSPECTOR QUALIFICATIONS 1.5.1 Steel Construction and High Strength Bolting 1.5.1.1 Special Inspector 1.5.1.2 Associate Special Inspector 1.5.2 Welding Structural Steel 1.5.2.1 Special Inspector 1.5.2.2 Associate Special Inspector 1.5.3 Nondestructive Testing of Welds 1.5.3.1 Special Inspector 1.5.3.2 Associate Special Inspector 1.5.4 Cold Formed Steel Framing 1.5.4.1 Special Inspector 1.5.4.2 Associate Special Inspector 1.5.5 Concrete Construction 1.5.5.1 Special Inspector 1.5.5.2 Associate Special Inspector SECTION 01 45 35 Page 1

Upload: dinhkiet

Post on 03-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

**************************************************************************USACE / NAVFAC / AFCEC / NASA UFGS- 01 45 35 ( Febr uar y 2015) - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Pr epar i ng Act i v i t y: USACE Super sedi ng UFGS- 01 45 35 ( August 2008)

UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS

Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2018**************************************************************************

SECTI ON TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

SECTI ON 01 45 35

SPECI AL I NSPECTI ONS

02/15

PART 1 GENERAL

1. 1 REFERENCES 1. 2 GENERAL REQUI REMENTS 1. 3 DEFI NI TI ONS 1. 3. 1 Cont i nuous Speci al I nspect i ons 1. 3. 2 Per i odi c Speci al I nspect i ons 1. 3. 3 Per f or m 1. 3. 4 Obser ve 1. 3. 5 Speci al I nspect or ( SI ) 1. 3. 6 Associ at e Speci al I nspect or ( ASI ) 1. 3. 7 Thi r d Par t y 1. 3. 8 Speci al I nspect or of Recor d ( SI OR) 1. 3. 9 Cont r act i ng Of f i cer 1. 3. 10 Cont r act or ' s Qual i t y Cont r ol ( QC) Manager 1. 3. 11 Desi gner of Recor d ( DOR) 1. 3. 12 St at ement of Speci al I nspect i ons ( SSI ) 1. 3. 13 Schedul e of Speci al I nspect i ons 1. 3. 14 Desi gnat ed Sei smi c Syst em 1. 4 SUBMI TTALS 1. 5 SPECI AL I NSPECTOR QUALI FI CATI ONS 1. 5. 1 St eel Const r uct i on and Hi gh St r engt h Bol t i ng 1. 5. 1. 1 Speci al I nspect or 1. 5. 1. 2 Associ at e Speci al I nspect or 1. 5. 2 Wel di ng St r uct ur al St eel 1. 5. 2. 1 Speci al I nspect or 1. 5. 2. 2 Associ at e Speci al I nspect or 1. 5. 3 Nondest r uct i ve Test i ng of Wel ds 1. 5. 3. 1 Speci al I nspect or 1. 5. 3. 2 Associ at e Speci al I nspect or 1. 5. 4 Col d For med St eel Fr ami ng 1. 5. 4. 1 Speci al I nspect or 1. 5. 4. 2 Associ at e Speci al I nspect or 1. 5. 5 Concr et e Const r uct i on 1. 5. 5. 1 Speci al I nspect or 1. 5. 5. 2 Associ at e Speci al I nspect or

SECTI ON 01 45 35 Page 1

1. 5. 6 Pr est r essed Concr et e Const r uct i on 1. 5. 6. 1 Speci al I nspect or 1. 5. 6. 2 Associ at e Speci al I nspect or 1. 5. 7 Post - t ensi oned Concr et e Const r uct i on 1. 5. 7. 1 Speci al I nspect or 1. 5. 7. 2 Associ at e Speci al I nspect or 1. 5. 8 Masonr y Const r uct i on 1. 5. 8. 1 Speci al I nspect or 1. 5. 8. 2 Associ at e Speci al I nspect or 1. 5. 9 Wood 1. 5. 9. 1 Speci al I nspect or 1. 5. 9. 2 Associ at e Speci al I nspect or 1. 5. 10 Ver i f i cat i on of Si t e Soi l Condi t i on, Fi l l Pl acement and

Load- Bear i ng Requi r ement s 1. 5. 10. 1 Speci al I nspect or 1. 5. 10. 2 Associ at e Speci al I nspect or 1. 5. 11 Deep Foundat i ons 1. 5. 11. 1 Speci al I nspect or 1. 5. 11. 2 Associ at e Speci al I nspect or 1. 5. 12 Spr ayed Fi r e Resi st ant Mat er i al 1. 5. 12. 1 Speci al I nspect or 1. 5. 12. 2 Associ at e Speci al I nspect or 1. 5. 13 Mast i c and I nt umescent Fi r e Resi st ant Coat i ngs 1. 5. 13. 1 Speci al I nspect or 1. 5. 13. 2 Associ at e Speci al I nspect or 1. 5. 14 Ext er i or I nsul at i on and Fi ni sh Syst em ( EI FS) 1. 5. 14. 1 Speci al I nspect or 1. 5. 14. 2 Associ at e Speci al I nspect or 1. 5. 15 Fi r e- Resi st ant Penet r at i ons and Joi nt s 1. 5. 15. 1 Speci al I nspect or 1. 5. 15. 2 Associ at e Speci al I nspect or 1. 5. 16 Smoke Cont r ol 1. 5. 16. 1 Speci al I nspect or 1. 5. 16. 2 Associ at e Speci al I nspect or 1. 5. 17 Speci al I nspect or of Recor d ( SI OR)

PART 2 PRODUCTS

2. 1 FABRI CATOR SPECI AL I NSPECTI ONS

PART 3 EXECUTI ON

3. 1 RESPONSI BI LI TI ES 3. 1. 1 Speci al I nspect or of Recor d 3. 1. 2 Qual i t y Cont r ol Manager 3. 1. 3 Speci al I nspect or s 3. 2 DEFECTI VE WORK

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 01 45 35 Page 2

**************************************************************************USACE / NAVFAC / AFCEC / NASA UFGS- 01 45 35 ( Febr uar y 2015) - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Pr epar i ng Act i v i t y: USACE Super sedi ng UFGS- 01 45 35 ( August 2008)

UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS

Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2018**************************************************************************

SECTI ON 01 45 35

SPECI AL I NSPECTI ONS02/15

**************************************************************************NOTE: Thi s gui de speci f i cat i on cover s t he r equi r ement s f or speci al i nspect i ons when r equi r ed by UFC 3- 301- 01. Thi s speci f i cat i on wi l l appl y onl y t o bui l di ngs.

Adher e t o UFC 1- 300- 02 Uni f i ed Faci l i t i es Gui de Speci f i cat i ons ( UFGS) For mat St andar d when edi t i ng t hi s gui de speci f i cat i on or pr epar i ng new pr oj ect speci f i cat i on sect i ons. Edi t t hi s gui de speci f i cat i on f or pr oj ect speci f i c r equi r ement s by addi ng, del et i ng, or r evi s i ng t ext . For br acket ed i t ems, choose appl i cabl e i t em( s) or i nser t appr opr i at e i nf or mat i on.

Remove i nf or mat i on and r equi r ement s not r equi r ed i n r espect i ve pr oj ect , whet her or not br acket s ar e present.

Comment s, suggest i ons and r ecommended changes f or t hi s gui de speci f i cat i on ar e wel come and shoul d be submi t t ed as a Cr i t er i a Change Request ( CCR) .

**************************************************************************

PART 1 GENERAL

**************************************************************************NOTE: Thi s gui de speci f i cat i on wi l l be appl i cabl e t o bot h new bui l di ngs and exi st i ng bui l di ng r ehabi l i t at i ons desi gned accor di ng t o UFC 3- 301- 01 STRUCTURAL ENGI NEERI NG.

I n addi t i on t o t he Speci al I nspect i on and t est i ng speci f i ed r equi r ement s, a r egi st er ed desi gn pr of essi onal must per f or m " st r uct ur al obser vat i ons" dur i ng const r uct i on when r equi r ed by UFC 3- 301- 01. Al l obser ved def i c i enci es wi l l be i mmedi at el y r epor t ed t o t he Cont r act i ng Of f i cer . The r egi st er ed desi gn pr of essi onal per f or mi ng t hese obser vat i ons wi l l be a r epr esent at i ve of t he Desi gner of Recor d ( DOR) f or t he bui l di ng bei ng const r uct ed.

SECTI ON 01 45 35 Page 3

St r uct ur al obser vat i ons ar e r equi r ed f or t he f ol l owi ng pr oj ect condi t i ons per I BC Chapt er 17:

1) Sei smi c Desi gn Cat egor y D, E or F; and assi gned t o Ri sk Cat I I I , I V or V.2) Sei smi c Desi gn Cat egor y D, E or F; and wi t h a hei ght gr eat er t han 22860 mm 75 f t .3) Sei smi c Desi gn Cat egor y E, assi gned t o Ri sk Cat egor y I or I I and t he bui l di ng i s gr eat er t han t wo st or i es above gr ade pl ane.4) Nomi nal desi gn wi nd speed i n excess of 49 m/ sec 110 mph; and assi gned t o Ri sk Cat I I I , I V or V.5) Nomi nal dei sgn wi nd speed i n excess of 49 m/ sec 110 mph; and wi t h a hei ght gr eat er t han 23 m 75 f t .

Coor di nat e wi t h t he Cont r act i ng Of f i cer how St r uct ur al Obser vat i ons wi l l be cover ed f or Desi gn- Bi d- Bui l d pr oj ect s as t hi s ser vi ce wi l l not be cover ed by t he Cont r act or .

Speci al I nspect i ons ar e mi ni mum Qual i t y Assur ance r equi r ement s t hat ar e i n addi t i on t o t he Qual i t y Cont r ol r equi r ement s t hat ar e def i ned i n Sect i ons 01 45 00. 00 10 QUALI TY CONTROL and 01 45 00. 00 20 QUALI TY CONTROL.

The r equi r ement s f or Speci al I nspect i ons, t he speci al i nspect or , and r el at ed t est i ng wi l l be used wher e r equi r ed by UFC 3- 301- 01 and UFC 4- 023- 03.

**************************************************************************

1. 1 REFERENCES

**************************************************************************NOTE: Thi s par agr aph i s used t o l i s t t he publ i cat i ons c i t ed i n t he t ext of t he gui de speci f i cat i on. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by basi c desi gnat i on onl y and l i s t ed i n t hi s par agr aph by or gani zat i on, desi gnat i on, dat e, and t i t l e.

Use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e when you add a Ref er ence I dent i f i er ( RI D) out s i de of t he Sect i on' s Ref er ence Ar t i c l e t o aut omat i cal l y pl ace t he r ef er ence i n t he Ref er ence Ar t i c l e. Al so use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e t o updat e t he i ssue dat es.

Ref er ences not used i n t he t ext wi l l aut omat i cal l y be del et ed f r om t hi s sect i on of t he pr oj ect speci f i cat i on when you choose t o r econci l e r ef er ences i n t he publ i sh pr i nt pr ocess.

**************************************************************************

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

SECTI ON 01 45 35 Page 4

AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)

ASCE 7 ( 2017) Mi ni mum Desi gn Loads f or Bui l di ngs and Ot her St r uct ur es

I NTERNATI ONAL CODE COUNCI L ( I CC)

I CC I BC ( 2018) I nt er nat i onal Bui l di ng Code

U. S. DEPARTMENT OF DEFENSE ( DOD)

UFC 3- 310- 04 ( 2013; wi t h Change 1) Sei smi c Desi gn f or Buildings

1. 2 GENERAL REQUI REMENTS

Per f or m Speci al I nspect i ons i n accor dance wi t h t he St at ement of Speci al I nspect i ons, Schedul e of Speci al I nspect i ons and Chapt er 17 of I CC I BC. The St at ement of Speci al I nspect i ons and Schedul e of Speci al I nspect i ons ar e i ncl uded as an at t achment t o t hi s speci f i cat i on. Speci al I nspect i ons ar e t o be per f or med by an i ndependent t hi r d par t y and ar e i nt ended t o ensur e t hat t he wor k of t he pr i me cont r act or i s i n accor dance wi t h t he Cont r act Document s and appl i cabl e bui l di ng codes. Speci al i nspect i ons do not t ake t he pl ace of t he t hr ee phases of cont r ol i nspect i ons per f or med by t he Cont r act or ' s QC Manager or any t est i ng and i nspect i ons r equi r ed by ot her sect i ons of t he speci f i cat i ons. [

St r uct ur al obser vat i ons wi l l be per f or med by t he Gover nment . The cont r act or must pr ovi de not i f i cat i on t o t he Cont r act i ng Of f i cer 14 days pr i or t o t he f ol l owi ng poi nt s of const r uct i on:

**************************************************************************NOTE: Def i ne t he poi nt s i n const r uct i on t hat st r uct ur al obser vat i ons need t o occur .

**************************************************************************

a. [ _____]b. [ _____]c. [ _____] ]

1. 3 DEFINITIONS

1. 3. 1 Cont i nuous Speci al I nspect i ons

Cont i nuous Speci al I nspect i ons i s t he const ant moni t or i ng of speci f i c t asks by a speci al i nspect or . These i nspect i ons must be car r i ed out cont i nuousl y over t he dur at i on of t he par t i cul ar t asks.

1. 3. 2 Per i odi c Speci al I nspect i ons

**************************************************************************NOTE: Consi der r evi s i ng t he def i ni t i on of per i odi c i f t her e i s a speci f i c t i me i nt er val t hat i s r equi r ed bet ween per i odi c i nspect i ons. For a speci f i c t i me i nt er val on a speci f i c Speci al I nspect i ons, i ndi cat e t he t i me i nt er val i n t he Schedul e of Speci al I nspect i ons f or t hat t ask.

**************************************************************************

SECTI ON 01 45 35 Page 5

Per i odi c Speci al I nspect i ons i s Speci al I nspect i ons by t he speci al i nspect or who i s i nt er mi t t ent l y pr esent wher e t he wor k t o be i nspect ed has been or i s bei ng per f or med.

1. 3. 3 Perform

Per f or m t hese Speci al I nspect i ons t asks f or each wel ded j oi nt or member .

1. 3. 4 Observe

Obser ve t hese Speci al I nspect i ons i t ems on a r andom dai l y basi s. Oper at i ons need not be del ayed pendi ng t hese i nspect i ons.

1. 3. 5 Speci al I nspect or ( SI )

A qual i f i ed per son r et ai ned by t he cont r act or and appr oved by t he Cont r act i ng Of f i cer as havi ng t he compet ence necessar y t o i nspect a par t i cul ar t ype of const r uct i on r equi r i ng Speci al I nspect i ons. The SI must be an i ndependent t hi r d par t y hi r ed di r ect l y by t he Pr i me Cont r act or .

1. 3. 6 Associ at e Speci al I nspect or ( ASI )

A qual i f i ed per son who assi st s t he SI i n per f or mi ng Speci al I nspect i ons but must per f or m i nspect i on under t he di r ect super vi s i on of t he SI and cannot per f or m i nspect i ons wi t hout t he SI on s i t e.

1. 3. 7 Thi r d Par t y

A t hi r d par t y i nspect or must not be company empl oyee of t he Cont r act or or any Sub- Cont r act or per f or mi ng t he wor k t o be i nspect ed.

[ 1. 3. 8 Speci al I nspect or of Recor d ( SI OR)

**************************************************************************NOTE: The Speci al I nspect or of Recor d i s r equi r ed f or t he f ol l owi ng pr oj ect condi t i ons per UFC 3-301-01:

1) Sei smi c Desi gn Cat egor y D, E or F; and assi gned t o Ri sk Cat I I I , I V or V.2) Sei smi c Desi gn Cat egor y D, E or F; and wi t h a hei ght gr eat er t han 22860 mm 75 f t .3) Sei smi c Desi gn Cat egor y E, assi gned t o Ri sk Cat egor y I or I I and t he bui l di ng i s gr eat er t han t wo st or i es above gr ade pl ane.4) Nomi nal desi gn wi nd speed i n excess of 49 m/ sec 110 mph; and assi gned t o Ri sk Cat I I I , I V or V.5) Nomi nal dei sgn wi nd speed i n excess of 49 m/ sec 110 mph; and wi t h a hei ght gr eat er t han 23 m 75 f t .

I n addi t i onal t o t hese condi t i ons, t he DOR i s encour aged t o consi der usi ng an SI OR on l ar ge magni t ude or cr i t i cal pr oj ect s wher e t hi s addi t i onal l evel of qual i t y cont r ol i s af f or dabl e.

**************************************************************************

A l i censed engi neer i n r esponsi bl e char ge of super vi s i on al l speci al i nspect or s f or t he pr oj ect and appr oved by t he Cont r act i ng of f i cer . The

SECTI ON 01 45 35 Page 6

SI OR must be an i ndependent t hi r d par t y hi r ed di r ect l y by t he Pr i me Contractor.

] 1. 3. 9 Cont r act i ng Of f i cer

The Gover nment of f i c i al havi ng over al l aut hor i t y f or admi ni st r at i ve cont r act i ng act i ons. Cer t ai n cont r act i ng act i ons may be del egat ed t o t he Cont r act i ng Of f i cer ' s Repr esent at i ve ( COR) .

1. 3. 10 Cont r act or ' s Qual i t y Cont r ol ( QC) Manager

An i ndi v i dual r et ai ned by t he pr i me cont r act or and qual i f i ed i n accor dance wi t h t he Sect i on [ 01 45 00. 00 20 QUALI TY CONTROL] [ DESI GN- BUI LD Sect i on 01 45 00. 05 20 DESI GN AND CONSTRUCTI ON QUALI TY CONTROL] havi ng t he over al l r esponsi bi l i t y f or t he cont r act or ' s QC or gani zat i on.

1. 3. 11 Desi gner of Recor d ( DOR)

A r egi st er ed desi gn pr of essi onal [ empl oyed by t he Gover nment ] [ cont r act ed by t he Gover nment as an A/ E] r esponsi bl e f or t he over al l desi gn and r evi ew of submi t t al document s pr epar ed by ot her s. The DOR i s r egi st er ed or l i censed t o pr act i ce t hei r r espect i ve desi gn pr of essi on as def i ned by t he st at ut or y r equi r ement s of t he pr of essi onal r egi st r at i on l aws i n st at e i n whi ch t he desi gn pr of essi onal wor ks. The DOR i s al so r ef er r ed t o as t he Engi neer of Recor d ( EOR) i n desi gn code document s.

1. 3. 12 St at ement of Speci al I nspect i ons ( SSI )

**************************************************************************NOTE: The St at ement of Speci al I nspect i ons wi l l be devel oped by t he DOR and must cover t he f ol l owi ng items:1) Li st of t he Ar chi t ect ur al Desi gnat ed Sei smi c Syst ems. a. These component s ar e i n or at t ached t o a Ri sk Cat egor y I V or V st r uct ur e and ar e needed f or cont i nued oper at i on of t he f aci l i t y or t hei r f ai l ur e coul d i mpai r t he cont i nued oper at i on of t he f aci l i t y .2) Li st of t he Mechani cal Desi gnat ed Sei smi c Syst ems. a. For Sei smi c Desi gn Cat egor y C or Ri sk Cat egor y V l i s t t he f ol l owi ng: i . Heat i ng, vent i l at i on and ai r - condi t i oni ng ( HVAC) duct wor k cont ai ni ng hazar dous mat er i al s and anchor age of such duct wor k. i i . Pi pi ng syst ems and mechani cal uni t s cont ai ni ng f l ammabl e, combust i bl e or hi ghl y t oxi c mat er i al s. b. For Sei smi c Desi gn Cat egor y D, E or F or Ri sk Cat egor y V l i s t mechani cal syst em t hat meet one of t he f ol l owi ng: i . Li f e saf et y component r equi r ed t o f unct i on af t er an ear t hquake i i . Component t hat cont ai ns hazar dous cont ent i i i . Al l component s i n an essent i al f aci l i t y needed f or cont i nued oper at i on af t er an ear t hquake3) Li st of t he El ect r i cal Desi gnat ed Sei smi c

SECTI ON 01 45 35 Page 7

Syst ems. a. For Sei smi c Desi gn Cat egor y C or Ri sk Cat egor y V l i s t t he f ol l owi ng: i . Anchor age of el ect r i cal equi pment used f or emer gency or st andby power syst ems. b. For Sei smi c Desi gn Cat egor y D, E or F l i s t el ect r i cal syst em t hat meet one of t he f ol l owi ng: i . Li f e saf et y component r equi r ed t o f unct i on af t er an ear t hquake i i . Component t hat cont ai ns hazar dous cont ent i i i . Al l component s i n an essent i al f aci l i t y needed f or cont i nued oper at i on af t er an ear t hquake4) Def i ne t he per i odi c wal k- down i nspect i ons r equi r ed by UFC 3- 301- 01.5) Li st of el ement s t hat ar e par t of t he pr ogr essi ve col l apse r esi st ance syst em. a. Pr ovi de a descr i pt i on of t he f ol l owi ng as t hey appl y: i . El ement s of t he t i e f or ce syst em consi st i ng of i nt er nal l ongi t udi nal and t r ansver se, ver t i cal , and per i pher al t i es. i i . El ement s of t he al t er nat e pat h syst em. i i i . El ement s havi ng enhanced l ocal r esi st ance.

The St at ement of Speci al I nspect i ons and t he Schedul e of Speci al I nspect i ons wi l l be i ncl uded as an at t achment t o t hi s speci f i cat i on.

**************************************************************************

A document devel oped by t he DOR i dent i f y i ng t he mat er i al , syst ems, component s and wor k r equi r ed t o have Speci al I nspect i ons.

1. 3. 13 Schedul e of Speci al I nspect i ons

**************************************************************************NOTE: A t empl at e f or t he Schedul e of Speci al I nspect i ons can be f ound on t he Whol e Bui l di ng Desi gn Gui de websi t e at https://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf .

**************************************************************************

A schedul e whi ch l i s t s each of t he r equi r ed Speci al I nspect i ons, t he ext ent t o whi ch each Speci al I nspect i ons i s t o be per f or med, and t he r equi r ed f r equency f or each i n accor dance wi t h I CC I BC Chapt er 17.

[ 1. 3. 14 Desi gnat ed Sei smi c Syst em

**************************************************************************NOTE: I ncl ude t hi s par agr aph when Desi gnat ed Sei smi c Syst ems ar e r equi r ed i n accor dance wi t h UFC 3-310-04.

**************************************************************************

Those nonst r uct ur al component s t hat r equi r e desi gn i n accor dance wi t h ASCE 7 Chapt er 13 and f or whi ch t he component i mpor t ance f act or , I p, i s gr eat er t han 1. 0. Thi s desi gnat i on appl i es t o syst ems t hat ar e r equi r ed t o be oper at i onal f ol l owi ng t he Desi gn Ear t hquake f or RC I - I V st r uct ur es and

SECTI ON 01 45 35 Page 8

f ol l owi ng t he MCER f or RC V st r uct ur es. Al l syst ems i n RC V f aci l i t i es desi gnat ed as MC- 1 i n accor dance wi t h UFC 3- 310- 04 ar e consi der ed par t of t he Desi gnat ed Sei smi c Syst ems. [ Desi gnat ed Sei smi c Syst ems wi l l be i dent i f i ed by Owner and wi l l have an I mpor t ance Fact or I p = 1. 5] .

] 1. 4 SUBMITTALS

**************************************************************************NOTE: Revi ew submi t t al descr i pt i on ( SD) def i ni t i ons i n Sect i on 01 33 00 SUBMI TTAL PROCEDURES and edi t t he f ol l owi ng l i s t t o r ef l ect onl y t he submi t t al s r equi r ed f or t he pr oj ect .

The Gui de Speci f i cat i on t echni cal edi t or s have desi gnat ed t hose i t ems t hat r equi r e Gover nment appr oval , due t o t hei r compl exi t y or cr i t i cal i t y , wi t h a " G. " Gener al l y, ot her submi t t al i t ems can be r evi ewed by t he Cont r act or ' s Qual i t y Cont r ol Syst em. Onl y add a “ G” t o an i t em, i f t he submi t t al i s suf f i c i ent l y i mpor t ant or compl ex i n cont ext of t he pr oj ect .

For submi t t al s r equi r i ng Gover nment appr oval on Ar my pr oj ect s, a code of up t o t hr ee char act er s wi t hi n t he submi t t al t ags may be used f ol l owi ng t he " G" desi gnat i on t o i ndi cat e t he appr ovi ng aut hor i t y. Codes f or Ar my pr oj ect s usi ng t he Resi dent Management Syst em ( RMS) ar e: " AE" f or Ar chi t ect - Engi neer ; " DO" f or Di st r i c t Of f i ce ( Engi neer i ng Di v i s i on or ot her or gani zat i on i n t he Di st r i c t Of f i ce) ; " AO" f or Ar ea Of f i ce; " RO" f or Resi dent Of f i ce; and " PO" f or Pr oj ect Of f i ce. Codes f ol l owi ng t he " G" t ypi cal l y ar e not used f or Navy, Ai r For ce, and NASA pr oj ect s.

Use t he " S" c l assi f i cat i on onl y i n SD- 11 Cl oseout Submi t t al s. The " S" f ol l owi ng a submi t t al i t em i ndi cat es t hat t he submi t t al i s r equi r ed f or t he Sust ai nabi l i t y eNot ebook t o f ul f i l l f eder al l y mandat ed sust ai nabl e r equi r ement s i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG.

Choose t he f i r st br acket ed i t em f or Navy, Ai r For ce and NASA pr oj ect s, or choose t he second br acket ed i t em f or Ar my pr oj ect s.

**************************************************************************

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on; submi t t al s not havi ng a " G" desi gnat i on ar e f or [ Cont r act or Qual i t y Cont r ol appr oval . ] [ i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . ] Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

SI OR Let t er of Accept ance; G[ , [ _____] ]

SECTI ON 01 45 35 Page 9

Speci al I nspect i ons Pr oj ect Manual ; G[ , [ _____] ]Speci al I nspect i ons Agency' s Wr i t t en Pr act i cesNDT Pr ocedur es and Equi pment Cal i br at i on Recor ds

SD- 06 Test Repor t s

Speci al I nspect i ons Dai l y Repor t sSpeci al I nspect i ons Bi weekl y Repor t s

SD- 07 Cer t i f i cat es

Fabr i cat i on Pl antSt eel Tr uss Pl antWood Tr uss Pl antAC472 Accr edi t at i onSt eel Joi st I nst i t ut e Member shi pPr ecast Concr et e I nst i t ut e ( PCI ) Cer t i f i ed Pl antCer t i f i cat e of Compl i anceSpeci al I nspect or of Recor d Qual i f i cat i ons; G[ , [ _____] ]Speci al I nspect or Qual i f i cat i ons; G[ , [ _____] ]Qual i f i cat i on Recor ds f or NDT t echni c i ans

SD- 11 Cl oseout Submi t t al s

**************************************************************************NOTE: I ncl ude t hi s submi t t al f or l ar ge compl ex projects.

**************************************************************************

I nt er i m Fi nal Repor t of Speci al I nspect i onsCompr ehensi ve Fi nal Repor t of Speci al I nspect i ons; G[ , [ _____] ]

1. 5 SPECI AL I NSPECTOR QUALI FI CATI ONS

Submi t qual i f i cat i ons f or each speci al i nspect or [ and t he speci al i nspect or of r ecor d] .

Cer t i f y i ng Associ at i ons

AABC Associ at ed Ai r Bal ance Counci l

ACI Amer i can Concr et e I nst i t ut e

AWCI Associ at i on of t he Wal l and Cei l i ng I ndust r y

AWS Amer i can Wel di ng Soci et y

FM Fact or y Mut ual

ICC I nt er nat i onal Code Counci l

NDT Nondest r uct i ve Test i ng

NICET Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es

SECTI ON 01 45 35 Page 10

Cer t i f y i ng Associ at i ons

PCI Pr ecast / Pr est r essed Concr et e I nst i t ut e

PTI Post - Tensi oni ng I nst i t ut e

UL Under wr i t er s Labor at or i es

1. 5. 1 St eel Const r uct i on and Hi gh St r engt h Bol t i ng

1. 5. 1. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. I CC St r uct ur al St eel and Bol t i ng Speci al I nspect or cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 1. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 2 Wel di ng St r uct ur al St eel

1. 5. 2. 1 Speci al I nspect or

**************************************************************************NOTE: For hi ghl y compl ex st eel pr oj ect s use onl y AWS Cer t i f i ed Wel di ng I nspect or s.

**************************************************************************

a. I CC St r uct ur al Wel di ng Speci al I nspect or cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. AWS Cer t i f i ed Wel di ng I nspect or

1. 5. 2. 2 Associ at e Speci al I nspect or

AWS Cer t i f i ed Associ at e Wel di ng I nspect or

1. 5. 3 Nondest r uct i ve Test i ng of Wel ds

1. 5. 3. 1 Speci al I nspect or

NDT Level I I I Cer t i f i cat e

1. 5. 3. 2 Associ at e Speci al I nspect or

NDT Level I I Cer t i f i cat e pl us one year of r el at ed exper i ence

SECTI ON 01 45 35 Page 11

1. 5. 4 Col d For med St eel Fr ami ng

1. 5. 4. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c and d” .

**************************************************************************

a. I CC St r uct ur al St eel and Bol t i ng Speci al I nspect or cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. I CC Commer ci al Bui l di ng I nspect or wi t h one year of exper i ence, or

c. I CC Resi dent i al Bui l di ng I nspect or wi t h one year of exper i ence, or

d. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 4. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 5 Concr et e Const r uct i on

1. 5. 5. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c and d” .

**************************************************************************

a. I CC Rei nf or ced Concr et e Speci al I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. ACI Concr et e Const r uct i on Speci al I nspect or , or

c. NI CET Concr et e Techni c i an Level I I I Cer t i f i cat e i n Const r uct i on Mat er i al s Test i ng, or

d. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 5. 2 Associ at e Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. ACI Concr et e Const r uct i on Speci al I nspect or i n Tr ai ni ng, or

b. Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

SECTI ON 01 45 35 Page 12

1. 5. 6 Pr est r essed Concr et e Const r uct i on

1. 5. 6. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c” .

**************************************************************************

a. I CC Pr e- st r essed Speci al I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. PCI Qual i t y Cont r ol Techni c i an/ I nspect or Level I I Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 6. 2 Associ at e Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. PCI Qual i t y Cont r ol Techni c i an/ I nspect or Level I Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

1. 5. 7 Post - t ensi oned Concr et e Const r uct i on

1. 5. 7. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. PTI Level 2 Unbonded PT I nspect or Cer t i f i cat e, or

b. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 7. 2 Associ at e Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. PTI Level 1 Unbonded PT I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

SECTI ON 01 45 35 Page 13

1. 5. 8 Masonr y Const r uct i on

1. 5. 8. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. I CC St r uct ur al Masonr y Speci al I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 8. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 9 Wood

1. 5. 9. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ b” .

**************************************************************************

a. I CC Commer ci al Bui l di ng I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. I CC Resi dent i al Bui l di ng I nspect or wi t h on year of exper i ence, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 9. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 10 Ver i f i cat i on of Si t e Soi l Condi t i on, Fi l l Pl acement and Load- Bear i ng Requirements

1. 5. 10. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ d and e” .

**************************************************************************

a. I CC Soi l s Speci al I nspect or Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

b. NI CET Soi l s Techni c i an Level I I Cer t i f i cat e i n Const r uct i on Mat er i al Test i ng, or

c. NI CET Geot echni cal Engi neer i ng Techni c i an Level I I Const r uct i on or Gener al i st Cer t i f i cat e, or

SECTI ON 01 45 35 Page 14

d. Geol ogi st - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence, or

e. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 10. 2 Associ at e Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c” .

**************************************************************************

a. NI CET Soi l s Techni c i an Level I Cer t i f i cat e i n Const r uct i on Mat er i al Test i ng wi t h one year of r el at ed exper i ence, or

b. NI CET Geot echni cal Engi neer i ng Techni c i an Level I Const r uct i on or Gener al i st Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

c. Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

1. 5. 11 Deep Foundat i ons

1. 5. 11. 1 Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c and d” .

**************************************************************************

a. NI CET Soi l s Techni c i an Level I I Cer t i f i cat e i n Const r uct i on Mat er i al Test i ng, or

b. NI CET Geot echni cal Engi neer i ng Techni c i an Level I I Const r uct i on or Gener al i st Cer t i f i cat e, or

c. Geol ogi st - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence, or

d. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 11. 2 Associ at e Speci al I nspect or

**************************************************************************NOTE: For pr oj ect s wi t h Sei smi c Desi gn Cat egor y D, E or F or nomi nal desi gn wi nd speed i n excess of 49 m/ s 110 mph, consi der el i mi nat i ng “ c” .

**************************************************************************

a. NI CET Soi l s Techni c i an Level I Cer t i f i cat e i n Const r uct i on Mat er i al Test i ng wi t h one year of r el at ed exper i ence, or

b. NI CET Geot echni cal Engi neer i ng Techni c i an Level I Const r uct i on or Gener al i st Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

c. Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

SECTI ON 01 45 35 Page 15

1. 5. 12 Spr ayed Fi r e Resi st ant Mat er i al

1. 5. 12. 1 Speci al I nspect or

a. I CC Spr ay- appl i ed Fi r epr oof i ng Speci al I nspect or Cer t i f i cat e, or

b. I CC Fi r e I nspect or I Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 12. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence

1. 5. 13 Mast i c and I nt umescent Fi r e Resi st ant Coat i ngs

1. 5. 13. 1 Speci al I nspect or

a. I CC Spr ay- appl i ed Fi r epr oof i ng Speci al I nspect or Cer t i f i cat e, or

b. I CC Fi r e I nspect or I Cer t i f i cat e wi t h one year of r el at ed exper i ence, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 13. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 14 Ext er i or I nsul at i on and Fi ni sh Syst em ( EI FS)

1. 5. 14. 1 Speci al I nspect or

a. AWCI EI FS I nspect or Cer t i f i cat e, or

b. Ext er i or Desi gn I nst i t ut e Cer t i f i cat e, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 14. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

1. 5. 15 Fi r e- Resi st ant Penet r at i ons and Joi nt s

1. 5. 15. 1 Speci al I nspect or

a. Passed t he UL Fi r est op Exam wi t h one year of r el at ed exper i ence, or

b. Passed t he FM Fi r est op Exam wi t h one year of r el at ed exper i ence, or

c. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 15. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

SECTI ON 01 45 35 Page 16

1. 5. 16 Smoke Cont r ol

1. 5. 16. 1 Speci al I nspect or

a. AABC Techni c i an Cer t i f i cat i on wi t h one year of r el at ed exper i ence, or

b. Regi st er ed Pr of essi onal Engi neer wi t h r el at ed exper i ence

1. 5. 16. 2 Associ at e Speci al I nspect or

Engi neer - I n- Tr ai ni ng wi t h one year of r el at ed exper i ence.

[ 1. 5. 17 Speci al I nspect or of Recor d ( SI OR)

Regi st er ed Pr of essi onal Engi neer

] PART 2 PRODUCTS

2. 1 FABRI CATOR SPECI AL I NSPECTI ONS

Speci al I nspect i ons of f abr i cat or ' s wor k per f or med i n t he f abr i cat or ' s shop i s r equi r ed t o be i nspect ed i n accor dance wi t h t he St at ement of Speci al I nspect i ons and t he Schedul e of Speci al I nspect i ons unl ess t he f abr i cat or i s cer t i f i ed by t he appr oved agency t o per f or m such wor k wi t hout Speci al I nspect i ons. Submi t t he f ol l owi ng cer t i f i cat i on [ cer t i f i cat i ons] t o t he Cont r act i ng Of f i cer f or i nf or mat i on t o al l ow wor k per f or med i n t he f abr i cat or ' s shop t o not be subj ect ed t o Speci al I nspect i ons.

**************************************************************************NOTE: The f ol l owi ng cer t i f i cat i ons meet t he r equi r ement s f or f abr i cat or appr oval i n accor dance wi t h par agr aph 1704. 2. 5. 2 of I BC.

**************************************************************************

[ Amer i can I nst i t ut e of St eel Const r uct i on ( AI SC) Cer t i f i ed Fabr i cat i on Pl ant , Cat egor y STD.

][ Tr uss Pl at e I nst i t ut e ( TPI ) st eel t r uss pl ant qual i t y assur ance pr ogr am certification.

][ Tr uss Pl at e I nst i t ut e ( TPI ) wood t r uss pl ant qual i t y assur ance pr ogr am certification. ]

**************************************************************************NOTE: AC472 Accr edi t at i on i s t he accr edi t at i on cr i t er i a f or i nspect i on pr ogr ams f or manuf act ur er s of met al bui l di ng syst ems.

**************************************************************************

[ I nt er nat i onal Accr edi t at i on Ser vi ce, AC472 Accr edi t at i on][ St eel Joi st I nst i t ut e Member shi p][ Pr ecast Concr et e I nst i t ut e ( PCI ) Cer t i f i ed Pl ant , Gr oup C]

At t he compl et i on of f abr i cat i on, submi t a cer t i f i cat e of compl i ance, t o be i ncl uded wi t h t he compr ehensi ve f i nal r epor t of Speci al I nspect i ons, st at i ng t hat t he mat er i al s suppl i ed and wor k per f or med by t he f abr i cat or ar e i n accor dance t he const r uct i on document s.

SECTI ON 01 45 35 Page 17

PART 3 EXECUTI ON

3. 1 RESPONSIBILITIES

[ 3. 1. 1 Speci al I nspect or of Recor d

**************************************************************************NOTE: I ncl ude t hi s par agr aph when t he SI OR i s required.

**************************************************************************

a. Super vi se al l Speci al I nspect or s r equi r ed by t he cont r act document s and t he I BC.

b. Submi t a SI OR Let t er of Accept ance t o t he Cont r act i ng Of f i cer at t est i ng t o accept ance of t he dut i es of SI OR, s i gned and seal ed by t he SI OR.

c. Ver i f y t he qual i f i cat i ons of al l of t he Speci al I nspect or s.

d. Ver i f y t he qual i f i cat i ons of f abr i cat or s.

**************************************************************************NOTE: I ncl ude t he f ol l owi ng br acket ed r equi r ement s when t he st r uct ur al desi gn i s r equi r ed t o f ol l ow AI SC 341 f or sei smi c desi gn of st eel st r uct ur es.

**************************************************************************

[ e. Submi t Speci al I nspect i ons agency' s wr i t t en pr act i ces f or t he moni t or i ng and cont r ol of t he agency' s oper at i ons t o i ncl ude t he following:

( 1) The agency' s pr ocedur es f or t he sel ect i on and admi ni st r at i on of i nspect i on per sonnel , descr i bi ng t he t r ai ni ng, exper i ence and exami nat i on r equi r ement s f or qual i f i cat i ons and cer t i f i cat i on of i nspect i on per sonnel .

( 2) The agency' s i nspect i on pr ocedur es, i ncl udi ng gener al i nspect i on, mat er i al cont r ol s, and v i sual wel di ng i nspect i on.

f . Submi t qual i f i cat i on r ecor ds f or nondest r uct i ve t est i ng ( NDT) t echni c i ans desi gnat ed f or t he pr oj ect .

g. Submi t NDT pr ocedur es and equi pment cal i br at i on r ecor ds f or NDT t o be per f or med and equi pment t o be used f or t he pr oj ect . ]

h. Pr epar e a Speci al I nspect i ons Pr oj ect Manual , whi ch wi l l cover t he following:

( 1) Rol es and r esponsi bi l i t i es of t he f ol l owi ng i ndi v i dual s dur i ng Speci al I nspect i ons: SI OR, SI , Gener al Cont r act or , Subcont r act or s, QC Manager , and DOR.

( 2) Or gani zat i onal char t and/ or communi cat i on pl an, i ndi cat i ng l i nes of communi cat i on.

( 3) Cont r act or ' s i nt er nal pl an f or schedul i ng i nspect i ons. Addr ess i t ems such as t i mel i ness of i nspect i on r equest s, who t o cont act f or i nspect i on r equest s, and avai l abi l i t y of al t er nat e i nspect or s.

SECTI ON 01 45 35 Page 18

( 4) I ndi cat e t he gover nment r epor t i ng pr ocedur es.

( 5) Pr opose f or ms or t empl at es t o be used by SI and SI OR t o document inspections.

( 6) I ndi cat e pr ocedur es f or t r acki ng nonconf or mi ng wor k and ver i f i cat i on t hat cor r ect i ve wor k i s compl et e.

( 7) I ndi cat e how t he SI OR and/ or SI wi l l par t i c i pat e i n weekl y QC meetings.

( 8) I ndi cat e how Speci al I nspect i ons of shop f abr i cat ed i t ems wi l l be handl ed when t he f abr i cat or ' s shop i s not cer t i f i ed per par agr aph FABRI CATOR SPECI AL I NSPECTI ONS.

( 9) I ncl ude a sect i on i n t he manual t hat cover s each speci f i c i t em r equi r i ng Speci al I nspect i ons t hat i s i ndi cat ed on t he Schedul e of Speci al I nspect i ons. Pr ovi de names and qual i f i cat i ons of each speci al i nspect or who wi l l be per f or mi ng t he Speci al I nspect i ons f or each speci f i c i t em. Pr ovi de det ai l on how t he Speci al I nspect i ons ar e t o be car r i ed out f or each i t em so t hat t he expect at i ons ar e c l ear f or t he Gener al Cont r act or and t he Subcont r act or per f or mi ng t he wor k.

Make a copy of t he Speci al I nspect i ons Pr oj ect Manual avai l abl e on t he j ob s i t e dur i ng const r uct i on. Submi t a copy of t he Speci al I nspect i ons Pr oj ect Manual f or appr oval .

i . At t end coor di nat i on and mut ual under st andi ng meet i ng wher e t he i nf or mat i on i n t he Speci al I nspect i ons Pr oj ect Manual wi l l be r evi ewed t o ver i f y t hat al l par t i es have a c l ear under st andi ng of t he Speci al I nspect i ons pr ovi s i ons and t he i ndi v i dual dut i es and r esponsi bi l i t i es of each par t y.

j . Mai nt ai n a 3- r i ng bi nder f or t he Speci al I nspect or ' s dai l y and bi weekl y r epor t s and t he Speci al I nspect i ons Pr oj ect Manual . Thi s f i l e must be l ocat ed i n a conspi cuous pl ace i n t he pr oj ect t r ai l er / of f i ce t o al l ow r evi ew by t he Cont r act i ng Of f i cer and t he DOR.

k. Submi t a copy of t he Speci al I nspect or ' s dai l y r epor t s t o t he QC Manager.

l . Di scr epanci es t hat ar e obser ved dur i ng Speci al I nspect i ons must be r epor t ed t o t he QC Manager f or cor r ect i on. I f di scr epanci es ar e not cor r ect ed bef or e t he speci al i nspect or l eaves t he s i t e t he obser ved di scr epanci es must be document ed i n t he dai l y r epor t .

m. Submi t a bi weekl y Speci al I nspect i ons r epor t unt i l al l wor k r equi r i ng Speci al I nspect i ons i s compl et e. A r epor t i s r equi r ed f or each bi weekl y per i od i n whi ch Speci al I nspect i ons act i v i t y occur s, and must i ncl ude t he f ol l owi ng:

( 1) A br i ef summar y of t he wor k per f or med dur i ng t he r epor t i ng t i me frame.

**************************************************************************NOTE: I ncl ude t he br acket ed por t i on of t he f ol l owi ng l i ne when t her e ar e desi gnat ed sei smi c syst ems f or mechani cal and el ect r i cal .

SECTI ON 01 45 35 Page 19

**************************************************************************

( 2) Changes and/ or di scr epanci es wi t h t he dr awi ngs, speci f i cat i ons [ and mechani cal or el ect r i cal component cer t i f i cat i on, ] t hat wer e obser ved dur i ng t he r epor t i ng per i od.

( 3) Di scr epanci es whi ch wer e r esol ved or cor r ect ed.

( 4) A l i s t of nonconf or mi ng i t ems r equi r i ng r esol ut i on.

( 5) Al l appl i cabl e t est r esul t s i ncl udi ng nondest r uct i ve t est i ng reports.

**************************************************************************NOTE: I ncl ude t hi s par agr aph on l ar ge compl ex projects.

**************************************************************************

[ n. At t he compl et i on of each Def i nabl e Feat ur e of Wor k ( DFOW) r equi r i ng Speci al I nspect i ons, submi t an i nt er i m f i nal r epor t of Speci al I nspect i ons t hat document s t he Speci al I nspect i ons compl et ed f or t hat DFOW and cor r ect i ons of al l di scr epanci es not ed i n t he dai l y r epor t s. The i nt er i m f i nal r epor t of Speci al I nspect i ons must be s i gned, dat ed and bear t he seal of t he SI OR. ]

o. At t he compl et i on of t he pr oj ect submi t a compr ehensi ve f i nal r epor t of Speci al I nspect i ons t hat document s t he Speci al I nspect i ons compl et ed f or t he pr oj ect and cor r ect i ons of al l di scr epanci es not ed i n t he dai l y r epor t s. The compr ehensi ve f i nal r epor t of Speci al I nspect i ons must be s i gned, dat ed and bear t he seal of t he SI OR.

] 3. 1. 2 Qual i t y Cont r ol Manager

**************************************************************************NOTE: I ncl ude t he br acket ed i t ems when t her e i s no SIOR.

**************************************************************************

[ a. Super vi se al l Speci al I nspect or s r equi r ed by t he cont r act document s and t he I BC.

b. Ver i f y t he qual i f i cat i ons of al l of t he Speci al I nspect or s.

c. Ver i f y t he qual i f i cat i ons of f abr i cat or s.

d. Mai nt ai n a 3- r i ng bi nder f or t he Speci al I nspect or ' s dai l y and bi weekl y r epor t s. Thi s f i l e must be l ocat ed i n a conspi cuous pl ace i n t he pr oj ect t r ai l er / of f i ce t o al l ow r evi ew by t he Cont r act i ng Of f i cer and t he DOR.

] [ a. ] [ e. ] Mai nt ai n a r ewor k i t ems l i s t t hat i ncl udes di scr epanci es not ed on t he Speci al I nspect or s dai l y r epor t .

3. 1. 3 Speci al I nspect or s

a. I nspect al l el ement s of t he pr oj ect f or whi ch t he speci al i nspect or i s qual i f i ed t o i nspect and ar e i dent i f i ed i n t he Schedul e of Speci al Inspections.

SECTI ON 01 45 35 Page 20

b. At t end pr epar at or y phase meet i ngs r el at ed t o t he Def i nabl e Feat ur e of Wor k ( DFOW) f or whi ch t he speci al i nspect or i s qual i f i ed t o i nspect .

**************************************************************************NOTE: I ncl ude subpar agr aphs “ c” t hr ough “ j ” when t he SI OR i s NOT r equi r ed.

**************************************************************************

**************************************************************************NOTE: I ncl ude subpar agr aphs “ c” t hr ough “ e” r equi r ement s when t he st r uct ur al desi gn i s r equi r ed t o f ol l ow AI SC 341 f or sei smi c desi gn of st eel structures.

**************************************************************************

[ c . Submi t Speci al I nspect i ons agency' s wr i t t en pr act i ces f or t he moni t or i ng and cont r ol of t he agency' s oper at i ons t o i ncl ude t he following:

( 1) The agency' s pr ocedur es f or t he sel ect i on and admi ni st r at i on of i nspect i on per sonnel , descr i bi ng t he t r ai ni ng, exper i ence and exami nat i on r equi r ement s f or qual i f i cat i ons and cer t i f i cat i on of i nspect i on per sonnel .

( 2) The agency' s i nspect i on pr ocedur es, i ncl udi ng gener al i nspect i on, mat er i al cont r ol s, and v i sual wel di ng i nspect i on.

d. Submi t qual i f i cat i on r ecor ds f or nondest r uct i ve t est i ng ( NDT) t echni c i ans desi gnat ed f or t he pr oj ect .

e. Submi t NDT pr ocedur es and equi pment cal i br at i on r ecor ds f or NDT t o be per f or med and equi pment t o be used f or t he pr oj ect . ]

f . Submi t a copy of t he dai l y r epor t s t o t he QC Manager .

g. Di scr epanci es t hat ar e obser ved dur i ng Speci al I nspect i ons must be r epor t ed t o t he QC Manager f or cor r ect i on. I f di scr epanci es ar e not cor r ect ed bef or e t he speci al i nspect or l eaves t he s i t e t he obser ved di scr epanci es must be document ed i n t he dai l y r epor t .

h. Submi t a bi weekl y Speci al I nspect i on Repor t unt i l al l i nspect i ons ar e compl et e. A r epor t i s r equi r ed f or each bi weekl y per i od i n whi ch Speci al I nspect i ons act i v i t y occur s, and must i ncl ude t he f ol l owi ng:

( 1) A br i ef summar y of t he wor k per f or med dur i ng t he r epor t i ng t i me frame.

**************************************************************************NOTE: I ncl ude t he br acket ed por t i on when t her e ar e desi gnat ed sei smi c syst ems f or mechani cal and electrical.

**************************************************************************

( 2) Changes and/ or di scr epanci es wi t h t he dr awi ngs, speci f i cat i ons [ and mechani cal or el ect r i cal component cer t i f i cat i on, ] t hat wer e obser ved dur i ng t he r epor t i ng per i od.

( 3) Di scr epanci es whi ch wer e r esol ved or cor r ect ed.

SECTI ON 01 45 35 Page 21

( 4) A l i s t of nonconf or mi ng i t ems r equi r i ng r esol ut i on.

5) Al l appl i cabl e t est r esul t i ncl udi ng nondest r uct i ve t est i ng reports.

**************************************************************************NOTE: I ncl ude t hi s par agr aph f or l ar ge compl ex projects.

**************************************************************************

[ i . At t he compl et i on of each DFOW r equi r i ng Speci al I nspect i ons, submi t an i nt er i m f i nal r epor t of Speci al I nspect i ons t hat document s t he Speci al I nspect i ons compl et ed f or t hat DFOW. I dent i f y t he i nspect or r esponsi bl e f or each i t em i nspect ed and cor r ect i ons of al l di scr epanci es not ed i n t he dai l y r epor t s. The i nt er i m f i nal r epor t of Speci al I nspect i ons must be s i gned, dat ed and i ndi cat e t he cer t i f i cat i on of t he speci al i nspect or qual i f y i ng t hem t o conduct t he inspection. ]

j . At t he compl et i on of t he pr oj ect submi t a compr ehensi ve f i nal r epor t of Speci al I nspect i ons t hat document s t he Speci al I nspect i ons compl et ed f or t he pr oj ect and cor r ect i ons of al l di scr epanci es not ed i n t he dai l y r epor t s. The compr ehensi ve f i nal r epor t of Speci al I nspect i ons must be s i gned, dat ed and i ndi cat e t he cer t i f i cat i on of t he speci al i nspect or qual i f y i ng t hem t o conduct t he i nspect i on.

**************************************************************************NOTE: I ncl ude t he f ol l owi ng r equi r ement when t he SI OR i s r equi r ed.

**************************************************************************

[ k . Submi t dai l y r epor t s t o t he SI OR.

] 3. 2 DEFECTI VE WORK

Check wor k as i t pr ogr esses, but f ai l ur e t o det ect any def ect i ve wor k or mat er i al s must i n no way pr event l at er r ej ect i on i f def ect i ve wor k or mat er i al s ar e di scover ed, nor obl i gat e t he Cont r act i ng Of f i cer t o accept such wor k.

- - End of Sect i on - -

SECTI ON 01 45 35 Page 22